Switchgear from catalogue, busbars by heat balance, GA + SLD + BOM + 3D.
IEC 61439 · IEC 62271
| Field | Type / default | Meaning |
|---|---|---|
| Project | ||
| Client | text default M/s Ministry of External Affairs | |
| Consultant / PMC | text default NBCC India Ltd | |
| Contractor | text default M/s Globe Civil Projects Pvt Ltd | |
| Job / drawing no. prefix | text default DL-2026-001 | |
| Revision | text default R0 | |
| Released for | choice default approval | Information, Approval, Manufacturing, As-built |
| Tagging style | choice default both | Vendor style (1F, 1F1, 1T1, 1D10), IEC 81346 (=Q1, -X1:1, wire 1L1-01), Both (vendor on drawings, IEC in brackets) |
| Import from SLD project (code) | text | type a saved SLD / VD project code and press Import — panels and feeders are filled from the resolved SLD |
| System | ||
| LT system voltage | choice default 415 | 415 V, 433 V, 400 V, 380 V, 480 V, 690 V |
| HT system (for HT panels) | choice default 11 | 11 kV, 33 kV, 6.6 kV, 22 kV, 24 kV |
| Fault level Icw (LT) | number (kA) default 50 | |
| Fault level (HT) | number (kA) default 26.3 | |
| Short-circuit duration | choice default 1 | 1 s, 3 s (HT), 0.5 s |
| Design ambient | number (°C) default 45 | |
| Altitude | number (m) default 300 | |
| Installation | choice default indoor | Indoor, floor mounted, free standing, Outdoor (canopy, IP55 min, double door) |
| Reference design (IEC 61439 verification) | choice default calc | Own design — verified by calculation / design rules (IEC 61439-1 Cl. 10, IEC 60890), L&T tested system (Tipco), Siemens SIVACON S8, Schneider Prisma / Blokset, ABB MNS, Legrand XL³ |
| Paint shade | choice default 7032 | RAL 7032 pebble grey, RAL 7035 light grey, Siemens grey (RAL 7035), RAL 9002 |
| Header band / end cover | choice default 5017 | RAL 5017 traffic blue, RAL 3000 red, Same as panel |
| Sheet — load bearing | choice default 2.0 | 2.0 mm CRCA, 2.5 mm CRCA, 2.0 mm GI |
| Sheet — doors / partitions | choice default 2.0 | 1.6 mm, 2.0 mm |
| Gland plate | choice default 3.0 | 3.0 mm CRCA (multi-core), 3.0 mm non-magnetic (single-core cables), 4.0 mm |
| Base channel | choice default 100 | ISMC 75 × 40, ISMC 100 × 50, None (plinth) |
| Max shipping section length | number (mm) default 2400 | |
| Switchboard room (NBCS 2026 D2 cl. 5.3.6.7, Fig. 2) | ||
| Indian code edition | choice default nbcs2026 | NBCS 2026 (SP 7:2026) Part D Sec 2, NBC 2016 Part 8 Sec 2 (superseded — same clearances, full neutral) |
| Clear space in front of the board | number (mm) default 1000 | NBCS 5.3.6.7 (a): ≥ 1 m (shutter opening must keep the 1 m) |
| Space behind the board (blank = auto) | number (mm) | NBCS 5.3.6.7 (b): < 200 mm if not accessible, > 750 mm if accessible from behind; auto = 100 / 1000 mm by access (double front or rear busduct) |
| End passage each side | number (mm) default 600 | NBCS 5.3.6.7 (c): rear > 750 mm needs a passage from either end clear to 1.8 m; width is project practice |
| Distance to a facing board (blank = none) | number (mm) | NBCS 5.3.6.7 (d): ≥ 2.0 m between two boards facing each other |
| Room length (blank = not checked) | number (m) | |
| Room width / depth (blank = not checked) | number (m) | |
| Room clear height (blank = not checked) | number (m) | |
| Busbar policy | ||
| Busbar material | choice default al | Aluminium E91E (IS 5082) — CPWD default, Copper ETP (IS 613 / 5082) |
| Permissible temperature rise | choice default 35 | 35 K (IS 8623 practice, bare joints), 50 K (IEC 61439-1 Table 6, sleeved / plated joints) |
| Neutral | choice default 100 | 100 % (NBCS 2026 D2 8.2.9.1, harmonic loads, CPWD), 50 % (NBC 2016 only — not with harmonics) |
| Earth bar | choice default al | Aluminium, Copper, GI |
| Dropper / vertical bus sizing | choice default 1.25 | 1.0 × feeder In, 1.25 × feeder In, 1.5 × feeder In |
| Phase centre spacing (LT) | number (mm) default 150 | |
| Busbar sleeving | choice default yes | Heat-shrink PVC sleeves R/Y/B/black, Bare with colour bands |
| Switchgear policy | ||
| ACB make | choice default lt | L&T, Siemens, Schneider Electric, ABB, Legrand, Havells, C&S Electric, Make-neutral (IS/IEC 60947-2) |
| MCCB make | choice default lt | L&T, Siemens, Schneider Electric, ABB, Legrand, Havells, C&S Electric, Make-neutral (IS/IEC 60947-2) |
| MCB make | choice default lt | L&T, Siemens, Schneider Electric, ABB, Legrand, Havells, C&S Electric, Make-neutral (IS/IEC 60947-2) |
| Contactor / starter make | choice default lt | L&T, Siemens, Schneider Electric, ABB, Legrand, Havells, C&S Electric, Make-neutral (IS/IEC 60947-2) |
| VCB make (HT) | choice default siemens | L&T, Siemens, Schneider Electric, ABB, Legrand, Havells, C&S Electric, Make-neutral (IS/IEC 60947-2) |
| Meters / relays make | text default L&T / Secure / Schneider | |
| CT make | text default AE / Kappa / Pragati | |
| Lamps, PBs, selector switches | text default Esbee / Siemens / Teknic | |
| Terminals | text default Elmex / Connectwell / Phoenix | |
| Capacitors / reactors | text default L&T / Epcos | |
| Release policy | choice default cpwd | Basic: TM up to 630 A, µP LSI above, CPWD: ACB µP LSIG; MCCB ≥ 250 A µP LSI; 100–200 A TM adjustable; ≤ 63 A TM, Premium: all electronic LSIG with metering / comms |
| Ics = 100 % Icu required | yes / no default True | |
| ACB drawout | choice default yes | Drawout (EDO ≥ 1600 A, MDO below), All EDO drawout, Fixed |
| Earth leakage on outgoings ≥ 100 A | choice default elr | None, ELR + CBCT (shunt trip), Ground-fault (G) in release |
| Spare feeders (if none listed) | number (%) default 20 | |
| Controls & interface | ||
| Control supply | choice default ups | 230 V AC from UPS, 230 V AC control transformer (per section), 24 V DC PSU (with 230 V for lamps), 110 V DC station battery (HT) |
| BMS / SCADA interface | choice default rs485 | None, RS-485 Modbus loop from MFMs + status contacts, PLC based load manager + BMS |
| Indication lamps | choice default led | 22.5 mm LED (ON red, OFF green, TRIP amber), 16 mm LED |
| R-Y-B phase lamps | choice default incomer | On incomers only, On every ACB / MCCB feeder, None |
| Annunciator on main incomers | yes / no default True | |
| SPD at main panel | choice default 1+2 | None, Type 1+2, 12.5 kA (10/350), Type 2, 40 kA (8/20) |
| AMF / auto changeover (DG incomers) | yes / no default True | |
| Wiring policy | ||
| Control wiring | choice default 1.5 | 1.0 mm², 1.5 mm², 2.5 mm² |
| CT wiring | choice default 2.5 | 2.5 mm², 4.0 mm² |
| AC power auxiliary | choice default 1.5 | 1.5 mm², 2.5 mm² |
| DC wiring | choice default 2.5 | 1.5 mm², 2.5 mm² |
| Door / earth continuity | choice default 2.5 | 2.5 mm², 4.0 mm², 6.0 mm² |
| Power connections by wire up to | choice default 63 | above this: busbar droppers / strips 32 A, 63 A, 100 A, 125 A |
| Wire type | choice default frls | FRLS PVC Cu flexible (IS 694), 1100 V, PVC Cu flexible (IS 694), Heat-resistant 105 °C |
| Ferrules / lugs | choice default printed | Printed PVC ferrules both ends, tubular pin lugs, Ring-type lugs, engraved ferrules |
| Wire colours | choice default cpwd | Control black · AC aux R/Y/B, N black · CT R/Y/B · DC grey · earth green (CPWD), IEC 60204-1: black power, red AC control, blue DC, orange interlock, green-yellow PE |
| Panels | ||
| One row per panel | table, one row per item | Columns: Panel tag; Title; Type; Form — IEC 61439-2 Annex 8.101; 3b minimum here; Access; Cable entry; Busduct entry; IP; Icw kA (blank = system); Bus sections — bus coupler between sections; Height (mm) — excluding base channel; Qty; Busbar override — e.g. 2x10x150 AL — blank = sized; Notes |
| Feeders | ||
| One row per feeder (incomers, couplers, outgoings) | table, one row per item | Columns: Panel; Sec; Role; Description / to; Device; In (A); Poles; Function; Load kW — motor / feeder demand (for RDF and heat); Ib A (blank = kW); Metering; ACB; Release; Make; Model override; Cable / link; BMS |
| Output | Content |
|---|---|
| GA drawings | front, internal, top, rear, side, section A-A per panel — A3 DXF sheet set with title block |
| Panel SLD + feeder schedule | IEC 60617 symbols, ratings, releases, CTs, metering, cables |
| Control schematics | one per typical: power & metering circuit, ladder with wire numbers, terminal strips 1T1–1T4 |
| Wiring list | from – to for every wire, size and colour |
| BOM | switchgear per unit + busbar kg, steel kg, supports, sleeves, wiring m, lugs, glands, hardware, paint, labels |
| Verification | IEC 61439-1 matrix, IEC 60890 heat check, RDF, Ipk, clearances, nameplate, routine-test checklist |
| 3D | micro-detailed model of each panel |