USER GUIDE

HT & LT panel GA drawings

Switchgear from catalogue, busbars by heat balance, GA + SLD + BOM + 3D.

IEC 61439 · IEC 62271

How to use it

  1. Import the feeders: type a saved SLD / VD project code and press 'From SLD project', or download the Excel template, fill Panels + Feeders and upload it — or type into the two tables directly.
  2. Set the policies once: system (voltage, kA, ambient, IP, reference design), busbar (Al / Cu, rise, neutral %), switchgear makes and release policy, controls (aux supply, BMS), wiring sizes and colours.
  3. Per panel: type, form (3b minimum for main panels), front, entry, busduct, sections; per feeder: role, device, In, poles, function, kW, metering, make / model overrides.
  4. Read the checks (busbar rating, RDF, incomer vs ΣIb, Icu vs fault level, heat per column) and fix the red ones.
  5. GA views tab: front / internal / top-rear-side / section per panel. SLD & schematics tab: panel SLD with feeder table, then one schematic per typical with wire numbers and terminal detail.
  6. 3D tab: pick the panel — the micro-detailed model builds on demand; untick 'Doors' and 'Enclosure sheets' to look inside; click any part for its description.
  7. Schedules & BOM tab: feeder schedule, GA modules, heat check, BOM (kg / m), terminal plan, wiring list. Export the A3 DXF sheet set, the report and the Excel (BOM with rate column).

Inputs

FieldType / defaultMeaning
Project
Clienttext default M/s Ministry of External Affairs
Consultant / PMCtext default NBCC India Ltd
Contractortext default M/s Globe Civil Projects Pvt Ltd
Job / drawing no. prefixtext default DL-2026-001
Revisiontext default R0
Released forchoice default approval
Information, Approval, Manufacturing, As-built
Tagging stylechoice default both
Vendor style (1F, 1F1, 1T1, 1D10), IEC 81346 (=Q1, -X1:1, wire 1L1-01), Both (vendor on drawings, IEC in brackets)
Import from SLD project (code)texttype a saved SLD / VD project code and press Import — panels and feeders are filled from the resolved SLD
System
LT system voltagechoice default 415
415 V, 433 V, 400 V, 380 V, 480 V, 690 V
HT system (for HT panels)choice default 11
11 kV, 33 kV, 6.6 kV, 22 kV, 24 kV
Fault level Icw (LT)number (kA) default 50
Fault level (HT)number (kA) default 26.3
Short-circuit durationchoice default 1
1 s, 3 s (HT), 0.5 s
Design ambientnumber (°C) default 45
Altitudenumber (m) default 300
Installationchoice default indoor
Indoor, floor mounted, free standing, Outdoor (canopy, IP55 min, double door)
Reference design (IEC 61439 verification)choice default calc
Own design — verified by calculation / design rules (IEC 61439-1 Cl. 10, IEC 60890), L&T tested system (Tipco), Siemens SIVACON S8, Schneider Prisma / Blokset, ABB MNS, Legrand XL³
Paint shadechoice default 7032
RAL 7032 pebble grey, RAL 7035 light grey, Siemens grey (RAL 7035), RAL 9002
Header band / end coverchoice default 5017
RAL 5017 traffic blue, RAL 3000 red, Same as panel
Sheet — load bearingchoice default 2.0
2.0 mm CRCA, 2.5 mm CRCA, 2.0 mm GI
Sheet — doors / partitionschoice default 2.0
1.6 mm, 2.0 mm
Gland platechoice default 3.0
3.0 mm CRCA (multi-core), 3.0 mm non-magnetic (single-core cables), 4.0 mm
Base channelchoice default 100
ISMC 75 × 40, ISMC 100 × 50, None (plinth)
Max shipping section lengthnumber (mm) default 2400
Switchboard room (NBCS 2026 D2 cl. 5.3.6.7, Fig. 2)
Indian code editionchoice default nbcs2026
NBCS 2026 (SP 7:2026) Part D Sec 2, NBC 2016 Part 8 Sec 2 (superseded — same clearances, full neutral)
Clear space in front of the boardnumber (mm) default 1000NBCS 5.3.6.7 (a): ≥ 1 m (shutter opening must keep the 1 m)
Space behind the board (blank = auto)number (mm)NBCS 5.3.6.7 (b): < 200 mm if not accessible, > 750 mm if accessible from behind; auto = 100 / 1000 mm by access (double front or rear busduct)
End passage each sidenumber (mm) default 600NBCS 5.3.6.7 (c): rear > 750 mm needs a passage from either end clear to 1.8 m; width is project practice
Distance to a facing board (blank = none)number (mm)NBCS 5.3.6.7 (d): ≥ 2.0 m between two boards facing each other
Room length (blank = not checked)number (m)
Room width / depth (blank = not checked)number (m)
Room clear height (blank = not checked)number (m)
Busbar policy
Busbar materialchoice default al
Aluminium E91E (IS 5082) — CPWD default, Copper ETP (IS 613 / 5082)
Permissible temperature risechoice default 35
35 K (IS 8623 practice, bare joints), 50 K (IEC 61439-1 Table 6, sleeved / plated joints)
Neutralchoice default 100
100 % (NBCS 2026 D2 8.2.9.1, harmonic loads, CPWD), 50 % (NBC 2016 only — not with harmonics)
Earth barchoice default al
Aluminium, Copper, GI
Dropper / vertical bus sizingchoice default 1.25
1.0 × feeder In, 1.25 × feeder In, 1.5 × feeder In
Phase centre spacing (LT)number (mm) default 150
Busbar sleevingchoice default yes
Heat-shrink PVC sleeves R/Y/B/black, Bare with colour bands
Switchgear policy
ACB makechoice default lt
L&T, Siemens, Schneider Electric, ABB, Legrand, Havells, C&S Electric, Make-neutral (IS/IEC 60947-2)
MCCB makechoice default lt
L&T, Siemens, Schneider Electric, ABB, Legrand, Havells, C&S Electric, Make-neutral (IS/IEC 60947-2)
MCB makechoice default lt
L&T, Siemens, Schneider Electric, ABB, Legrand, Havells, C&S Electric, Make-neutral (IS/IEC 60947-2)
Contactor / starter makechoice default lt
L&T, Siemens, Schneider Electric, ABB, Legrand, Havells, C&S Electric, Make-neutral (IS/IEC 60947-2)
VCB make (HT)choice default siemens
L&T, Siemens, Schneider Electric, ABB, Legrand, Havells, C&S Electric, Make-neutral (IS/IEC 60947-2)
Meters / relays maketext default L&T / Secure / Schneider
CT maketext default AE / Kappa / Pragati
Lamps, PBs, selector switchestext default Esbee / Siemens / Teknic
Terminalstext default Elmex / Connectwell / Phoenix
Capacitors / reactorstext default L&T / Epcos
Release policychoice default cpwd
Basic: TM up to 630 A, µP LSI above, CPWD: ACB µP LSIG; MCCB ≥ 250 A µP LSI; 100–200 A TM adjustable; ≤ 63 A TM, Premium: all electronic LSIG with metering / comms
Ics = 100 % Icu requiredyes / no default True
ACB drawoutchoice default yes
Drawout (EDO ≥ 1600 A, MDO below), All EDO drawout, Fixed
Earth leakage on outgoings ≥ 100 Achoice default elr
None, ELR + CBCT (shunt trip), Ground-fault (G) in release
Spare feeders (if none listed)number (%) default 20
Controls & interface
Control supplychoice default ups
230 V AC from UPS, 230 V AC control transformer (per section), 24 V DC PSU (with 230 V for lamps), 110 V DC station battery (HT)
BMS / SCADA interfacechoice default rs485
None, RS-485 Modbus loop from MFMs + status contacts, PLC based load manager + BMS
Indication lampschoice default led
22.5 mm LED (ON red, OFF green, TRIP amber), 16 mm LED
R-Y-B phase lampschoice default incomer
On incomers only, On every ACB / MCCB feeder, None
Annunciator on main incomersyes / no default True
SPD at main panelchoice default 1+2
None, Type 1+2, 12.5 kA (10/350), Type 2, 40 kA (8/20)
AMF / auto changeover (DG incomers)yes / no default True
Wiring policy
Control wiringchoice default 1.5
1.0 mm², 1.5 mm², 2.5 mm²
CT wiringchoice default 2.5
2.5 mm², 4.0 mm²
AC power auxiliarychoice default 1.5
1.5 mm², 2.5 mm²
DC wiringchoice default 2.5
1.5 mm², 2.5 mm²
Door / earth continuitychoice default 2.5
2.5 mm², 4.0 mm², 6.0 mm²
Power connections by wire up tochoice default 63above this: busbar droppers / strips
32 A, 63 A, 100 A, 125 A
Wire typechoice default frls
FRLS PVC Cu flexible (IS 694), 1100 V, PVC Cu flexible (IS 694), Heat-resistant 105 °C
Ferrules / lugschoice default printed
Printed PVC ferrules both ends, tubular pin lugs, Ring-type lugs, engraved ferrules
Wire colourschoice default cpwd
Control black · AC aux R/Y/B, N black · CT R/Y/B · DC grey · earth green (CPWD), IEC 60204-1: black power, red AC control, blue DC, orange interlock, green-yellow PE
Panels
One row per paneltable, one row per item
Columns: Panel tag; Title; Type; Form — IEC 61439-2 Annex 8.101; 3b minimum here; Access; Cable entry; Busduct entry; IP; Icw kA (blank = system); Bus sections — bus coupler between sections; Height (mm) — excluding base channel; Qty; Busbar override — e.g. 2x10x150 AL — blank = sized; Notes
Feeders
One row per feeder (incomers, couplers, outgoings)table, one row per item
Columns: Panel; Sec; Role; Description / to; Device; In (A); Poles; Function; Load kW — motor / feeder demand (for RDF and heat); Ib A (blank = kW); Metering; ACB; Release; Make; Model override; Cable / link; BMS

What you get

OutputContent
GA drawingsfront, internal, top, rear, side, section A-A per panel — A3 DXF sheet set with title block
Panel SLD + feeder scheduleIEC 60617 symbols, ratings, releases, CTs, metering, cables
Control schematicsone per typical: power & metering circuit, ladder with wire numbers, terminal strips 1T1–1T4
Wiring listfrom – to for every wire, size and colour
BOMswitchgear per unit + busbar kg, steel kg, supports, sleeves, wiring m, lugs, glands, hardware, paint, labels
VerificationIEC 61439-1 matrix, IEC 60890 heat check, RDF, Ipk, clearances, nameplate, routine-test checklist
3Dmicro-detailed model of each panel

Standards applied

Good to know