Design Link calc Power factor correction · APFC + Active harmonic filter

Inputs

Minimum: load kW, existing pf, target pf. Everything else has standard defaults.

Bank & steps

Capacitor feeder & notes

Method

Q = P · (tan φ₁ − tan φ₂)  ·  bank = next standard ≥ Q (+ 5 % kVATR fixed)  ·  Qc,rated = Q / (1 − p) · (Ur/Un)²
In = Q / (√3·U)  ·  breaker ≥ 1.5 In (IS 13340 / IEC 60831)  ·  cable ≥ 1.43 In

AHF: Iload = P/(√3·U·pf₁) · Ih = Iload · share · THDnl · Iallowed = Iload · THDtarget · IAHF = √((Ih − Iallowed)² + Iq²) · (1 + margin) → next unit rating (30…600 A, parallel above 400 A)

Reactor choice by harmonic current distortion: ≤ 5 % plain, 5–15 % 7 % detuned, > 15 % 14 % detuned. Cable sizes are indicative (Cu/Al XLPE in air); size the actual feeder in the voltage-drop calculator.