HVAC noise — calculation report
Sample project — Tower A · NBCS 2026 with international methods
Generated 28 Nov 2026 17:16 designlink calc
NC
32
Target
NC 35
RC
28(RH)
Level
38
dB(A)
Governing band
63
Hz
1. Checks
Check
Result
Limit
Status
What to do
NC in the room against the target for Conference / meeting room
NC 32 (governing band 63 Hz)
≤ NC 35
OK
A-weighted level against the acceptable indoor level
38 dB(A)
≤ 40 dB(A)
OK
Sound quality (RC, simplified) — advisory
RC 28(RH) — rumble (R): treat 63–250 Hz at the unit; hiss (H): treat the outlets
neutral (N)
—
2. Results per octave band
Path: AHU-1 supply
Hz
63
125
250
500
1000
2000
4000
8000
Source Lw — Centrifugal, backward curved / aerofoil fan, 8000 m³/h at 600 Pa (fan-law estimate, typical)
Each band: Lw into the room = source Lw − Σ path attenuation (+ regenerated noise, added as energy) Room effect (Schultz): Lp = Lw − 5 log10(V) − 3 log10(f) − 10 log10(r) + 12 e.g. 1000 Hz, first path: Lw at the outlet 37.0 dB → Lp = 37.0 − 5 log10(72) − 3 log10(1000) − 10 log10(2) + 12 = 27.7 dB All paths summed as energy → NC 32 (tangent at 63 Hz), RC 28(RH), 38 dB(A) (A-weighting per band, then summed)
5. Basis and notes
NBCS 2026 (SP 7:2026) Part D Section 3 Table 1, cl. 3.4.8.1 (p. 1877–1878); Part D Section 4 Table 4, cl. 4.1 (p. 2146); Table 10 A-weighting (p. 2177)
ASHRAE Handbook — HVAC Applications, Noise and Vibration Control (duct attenuation, end reflection, Schultz room effect)
NC curves (Beranek); RC Mark II (simplified)
NC target: NBCS 2026 Part D Section 3, Table 1 Requirements of Acoustic Comfort, cl. 3.4.8.1, p. 1877–1878, class B
dB(A) target: NBCS 2026 Part D Section 4, Table 4 Acceptable Indoor Noise Levels for Various Buildings, cl. 4.1, p. 2146 (Conference rooms, small offices and libraries: 35 to 40 dBA)
Source sound power levels and attenuation data are typical — replace with the manufacturer's certified octave-band data for the selected unit, silencer and diffusers.
Breakout through the duct wall and casing-radiated noise of units above the ceiling are not modelled; for a unit above a lay-in ceiling enter its casing Lw as a second path.
RC is the simplified form (mean of 500–2000 Hz with the rumble / hiss tests on the −5 dB / octave line).
Design aid — values marked typical are practice values, not code values; an engineer reviews before issue.