SAMPLEAcoustics — level addition, distance, NC rating — this is what your report looks like, generated from demo inputs.Generate yours →2 free designs every day for every signed-in account · 1 design free on sign-in · ₹99 + GST per design (report + Excel + DXF) · free for DesignLink companies
Report ready — use Print → Save as PDF (A4 landscape).
calc.designlink.in
Acoustics — level addition, distance, NC rating
Sample project — Tower A · HVAC
Generated 28 Nov 2026 16:09 Add sound sources, attenuate with distance (point / line source), estimate NC from octave-… Project code SAMPLE
5. NC (tangent method): lowest NC curve not exceeded in any band = governing band 1000 Hz: 42 dB ≤ NC-45 46 dB (NC-40: 41 dB exceeded) = NC-45
6. NC target: NC ≤ target → NC-45 ≤ NC-35 CHECK(D3 Table 1 iii) a), class B)
7. Indoor noise level: LA ≤ upper limit of D4 Table 4 → 49.0 ≤ 40 dB(A) CHECK(Conference rooms, small offices and libraries: 35–40 dB(A))
5. Notes
NC by the tangent method: the lowest NC curve not exceeded in any octave band (ASHRAE Fundamentals ch. 8).
NBCS 2026 D3 3.4.8.1 / Table 1: class A aspirational, B acceptable, C minimum acceptable; RT and STI per class are also given there (not checked here). Spaces not listed: nearest representative category (Table 1 Note 3).
NBCS 2026 D4 4.1 / Table 4: acceptable indoor noise levels in dB(A) — the lower value is the ideal, the upper value the limit used in the check.
Plant rooms and AHU rooms: sound insulation and noise control per D3 3.4.1.6 / 3.4.2.12 and Part D Sec 4.
6. Standards and references
ASHRAE Handbook — Fundamentals 2021 — Psychrometrics (ch. 1), climatic design (ch. 14), cooling/heating load (ch. 18), solar (1997 ch. 29): Load calculation method, solar heat gain, sol-air temperature
ISO 3744 / ASHRAE ch. 8 — Sound power / acoustics: Level addition, distance, NC curves
NBCS 2026 (SP 7:2026) Part D Sec 3 — National Building Construction Standards — Air conditioning, heating and mechanical ventilation: Design conditions (Table 3), ventilation (Table 7), duct velocities (Table 18), clean rooms (Table 31), automation
NBCS 2026 (SP 7:2026) Part D Sec 4 — National Building Construction Standards — Acoustics, sound insulation and noise control: Noise criteria and background levels by room
Prepared by
Checked by
Approved by
Results are design aids computed by designlink calc (calc.designlink.in) and must be reviewed by a qualified engineer before issue. Ground levels marked "assumed" have no survey level within reach — verify.