Acoustics — level addition, distance, NC rating

Sample project — Tower A · HVAC
Generated 28 Nov 2026 16:09
Add sound sources, attenuate with distance (point / line source), estimate NC from octave-…
Project code SAMPLE
Sum
76.8 dB
At receiver
56.8 dB
NC
NC-45
dB(A)
49.0 dB(A)
NC target
NC-35

1. Inputs

GroupInputValueUnit
Code basis & roomDesign regimeIndia — NBCS 2026 D3 Table 1 (NC) + D4 Table 4 (dB(A))
Code basis & roomRoom type (NBCS D3 Table 1 / D4 Table 4)Office — executive and private offices
Code basis & roomAcoustic classB — acceptable
Sources to addSource 1 level75dB
Sources to addSource 2 level72dB
Sources to addSource 3 level0dB
Sources to addSource 4 level0dB
DistanceReference distance1m
DistanceReceiver distance10m
DistanceSource typePoint (−6 dB per doubling)
DistanceBarrier / enclosure attenuation0dB
Octave-band levels at the receiver (blank = not used)63 Hz60dB
Octave-band levels at the receiver (blank = not used)125 Hz55dB
Octave-band levels at the receiver (blank = not used)250 Hz50dB
Octave-band levels at the receiver (blank = not used)500 Hz45dB
Octave-band levels at the receiver (blank = not used)1000 Hz42dB
Octave-band levels at the receiver (blank = not used)2000 Hz40dB
Octave-band levels at the receiver (blank = not used)4000 Hz38dB
Octave-band levels at the receiver (blank = not used)8000 Hz35dB
Octave-band levels at the receiver (blank = not used)NC target override (blank = NBCS D3 Table 1 for the room; international default NC-35)

2. Results

Levels

ItemValueUnitNote / basis
Sum of sources76.76dBL = 10·log Σ10^(Li/10) of 2 sources
Distance attenuation + barrier20.0dB
Level at receiver56.76dB
NC rating (tangent method)NC-45
A-weighted level of the bands48.95dB(A)
NC targetNC-35D3 Table 1 iii) a), class B
Acceptable indoor level (NBCS D4 Table 4)35–40dB(A)Conference rooms, small offices and libraries

NC curve compared

Hz631252505001000200040008000
Receiver6055504542403835
NC-456760544946444342
NC-35 target6052454036343332
NC rating — receiver NC-45 vs target NC-35 · 49.0 dB(A) vs D4 Table 4 35–400102030405060708090631252505001k2k4k8koctave-band centre frequency, Hzsound pressure level, dB re 20 µPaNC-15NC-20NC-25NC-30NC-35NC-40NC-45NC-50NC-55NC-60NC-65governing band 1000 Hzred: receiver spectrum · orange: rated NC-45 · blue dashed: target NC-35 · grey: NC family 15–65 (ASHRAE)

3. Checks

CheckResultNote
NC-45 ≤ NC-35 (NBCS D3 Table 1, class B)CHECKD3 Table 1 iii) a), class B
49.0 dB(A) ≤ 40 dB(A) (NBCS D4 Table 4, 35–40)CHECKConference rooms, small offices and libraries

4. Worked example

Worked from this project’s own inputs and results — each value can be traced to the schedules above.

Room noise — level sum, distance, NC and dB(A)
this calculation's own inputs
Given: Sources 75, 72 dB · Distance 1 → 10 m, point source
1. Level sum: L = 10·log Σ 10Li/10 = 10·log(107.50 + 107.20) = 76.8 dB
2. Distance attenuation: ΔL = 20·log(d2/d1) + barrier = 20 × log(10/1) + 0 = 20 dB
3. Level at the receiver: L2 = L − ΔL = 76.8 − 20.0 = 56.8 dB
4. A-weighted level: LA = 10·log Σ 10(Lb + Ab)/10 = A-corrected bands 33.8, 38.9, 41.4, 41.8, 42.0, 41.2, 39.0, 33.9 (A = D4 Table 10) = 49 dB(A)
5. NC (tangent method): lowest NC curve not exceeded in any band = governing band 1000 Hz: 42 dB ≤ NC-45 46 dB (NC-40: 41 dB exceeded) = NC-45
6. NC target: NC ≤ target → NC-45 ≤ NC-35 CHECK (D3 Table 1 iii) a), class B)
7. Indoor noise level: LA ≤ upper limit of D4 Table 4 → 49.0 ≤ 40 dB(A) CHECK (Conference rooms, small offices and libraries: 35–40 dB(A))

5. Notes

6. Standards and references

Prepared by
Checked by
Approved by