Beam angle, spot size & lux

Sample project — Tower A · Electrical
Generated 28 Nov 2026 17:16
For a spot / flood light: centre illuminance and spot diameter from the lumens, beam angle…
Project code SAMPLE
Centre lux
679.8 lx
Spot diameter
1.275 m
Peak intensity
6117.9 cd
Average in the spot
657.6 lx

1. Inputs

GroupInputValueUnit
LightCalculateLux and spot size from lumens + beam angle
LightLuminaire output1200lm
LightBeam angle24°
LightShare of the lumens inside the beam0.7
LightDistance to the lit surface3m

2. Results

Result

ItemValueUnitNote / basis
Solid angle Ω = 2π(1 − cos θ/2)0.1373sr
Intensity I = Φ·share / Ω6117.87cd
Centre lux E = I / d²679.76lx
Spot diameter 2·d·tan(θ/2)1.28m
Average lux in the spot657.56lx

3. Checks

CheckResultNote
Beam lumen share assumed — check with the maker's dataPASS

4. Worked example

Ω = 2π(1 − cos 12°) = 0.1373 sr; I = 1200 × 0.7 / 0.1373 = 6118 cd; E = 6118 / 3² = 680 lx; D = 2 × 3 × tan 12° = 1.28 m