| HVAC | | | | | | | | | | | |
| 1 | Water-cooled chiller Tower A · B2 · Plant room | 3 | | | | | 150 | | | | |
| i | Chillers — ON / OFF Command | | | | | 3 | | | ● | | Potential Free Contact from BMS to Chiller MCC Panel |
| ii | Chillers Trip / Fault | | | 3 | | | | ● | | ● | Potential Free Contact to BMS from Chiller MCC Panel |
| iii | Chiller Run Status | | | 3 | | | | ● | | | Potential Free Contact to BMS from Chiller MCC Panel |
| iv | Chiller Auto / Manual Status | | | 3 | | | | ● | | | Potential Free Contact to BMS from Chiller MCC Panel |
| v | CHW Supply Temperature | | 3 | | | | | ● | | | Sensor & field wiring |
| vi | CHW Return Temperature | | 3 | | | | | ● | | | Sensor & field wiring |
| vii | CDW Supply Temperature | | 3 | | | | | ● | | | Sensor & field wiring |
| viii | CDW Return Temperature | | 3 | | | | | ● | | | Sensor & field wiring |
| ix | Common Header CHW Supply / Return Temperature | | 2 | | | | | ● | | | Sensor & field wiring |
| x | CHW Isolation Motorised Valve ON/OFF Command | | | | | 6 | | | ● | | Potential Free Contact from BMS to motorised butterfly valve actuator |
| xi | CHW Isolation Motorised Valve ON/OFF Status | | | 6 | | | | ● | | | Potential Free Contact to BMS from valve limit switch |
| xii | CDW Isolation Motorised Valve ON/OFF Command | | | | | 6 | | | ● | | Potential Free Contact from BMS to motorised butterfly valve actuator |
| xiii | CDW Isolation Motorised Valve ON/OFF Status | | | 6 | | | | ● | | | Potential Free Contact to BMS from valve limit switch |
| xiv | Chilled Water Supply Flow Measurement | | 1 | | | | | ● | | | Sensor & field wiring |
| xv | Pressure Monitoring in Chilled Water Line | | 6 | | | | | ● | | | Sensor & field wiring |
| xvi | Chiller Header Isolation Motorised Valve Command | | | | | 6 | | | ● | | Potential Free Contact from BMS to valve actuator |
| xvii | Chiller Header Isolation Motorised Valve Status | | | 6 | | | | ● | | | Potential Free Contact to BMS from valve limit switch |
| xviii | Outside Air Temperature and RH Sensor | | 2 | | | | | ● | | | Sensor & field wiring |
| xix | CHW Flow Switch at Chiller Evaporator — flow proving interlock | | | 3 | | | | ● | | ● | Chiller enable interlock requires proven evaporator flow. |
| xx | CDW Flow Switch at Chiller Condenser — flow proving interlock | | | 3 | | | | ● | | ● | Chiller enable interlock requires proven condenser flow. |
| xxi | Chilled Water Header BTU / Energy Meter | | 1 | | | | | ● | | | Required for ECBC energy reporting and plant kW/TR. |
| xxii | Condenser Water Header Flow Measurement | | 1 | | | | | ● | | | Condenser side flow was not measured. |
| xxiii | Protocol integration (soft points) | | | | | | 150 | ● | | | Modbus/BACnet Integration (Chiller Plant Manager — 50 objects per machine, covers all intrinsic parameters) |
| 2 | Primary chilled-water pump (VFD) Tower A · B2 | 4 | | | | | 60 | | | | |
| i | Primary CHW Pump ON / OFF Command | | | | | 4 | | | ● | | Potential Free Contact from BMS to MCC Panel |
| ii | Primary CHW Pump Auto / Manual Status | | | 4 | | | | ● | | | Potential Free Contact to BMS from MCC Panel |
| iii | Primary CHW Pump Run Status | | | 4 | | | | ● | | | Sensor & field wiring |
| iv | Primary CHW Pump Trip Status | | | 4 | | | | ● | | ● | Potential Free Contact to BMS from MCC Panel |
| v | Primary CHW Pump VFD Speed Command | | | | 4 | | | | ● | | 0-10 V DC / 4-20 mA output from BMS to VFD |
| vi | Primary CHW Pump VFD Frequency Feedback | | 4 | | | | | ● | | | 0-10 V DC / 4-20 mA input to BMS from VFD |
| vii | Primary CHW Pump VFD Soft Integration | | | | | | 60 | ● | | | 6 drives × 15 registers. Previously shown as "x" and counted as nil. |
| 3 | Cooling tower cell Terrace | 3 | | | | | | | | | |
| i | Cooling Tower Fan ON / OFF Command | | | | | 3 | | | ● | | Potential Free Contact from BMS to MCC Panel |
| ii | Cooling Tower Fan Auto / Manual Status | | | 3 | | | | ● | | | Potential Free Contact to BMS from MCC Panel |
| iii | Cooling Tower Fan ON / OFF Status | | | 3 | | | | ● | | | Sensor & field wiring |
| iv | Cooling Tower Fan Trip Status | | | 3 | | | | ● | | ● | Potential Free Contact to BMS from MCC Panel |
| v | Cooling Tower Sump Low Level | | | 3 | | | | ● | | ● | Sensor & field wiring |
| vi | Cooling Tower Sump High Level (overflow) | | | 3 | | | | ● | | ● | Only low level was provided; overflow was undetected. |
| vii | Cooling Tower Inlet Isolation Valve Open / Close Command | | | | | 6 | | | ● | | Relay output (1 SPDT open / close) @ 2 A, 230 V and wiring to valve actuator |
| viii | Cooling Tower Inlet Isolation Valve Open / Close Status | | | 6 | | | | ● | | ● | Potential Free Contact to BMS from valve actuator limit switch |
| ix | Condenser Water Inlet and Outlet Temperature at Cooling Tower | | 6 | | | | | ● | | | Sensor & field wiring |
| x | Header Temperature from Cooling Tower Outlet | | 1 | | | | | ● | | | Sensor & field wiring |
| 4 | Air handling unit — floor mounted Tower A | 12 | | | | | 240 | | | | |
| i | Unit ON / OFF Command | | | | | 12 | | | ● | | Potential Free Contact from BMS to MCC Panel |
| ii | Unit Run Status | | | 12 | | | | ● | | | Sensor & field wiring |
| iii | Unit Auto / Manual Status | | | 12 | | | | ● | | | Potential Free Contact to BMS from MCC Panel |
| iv | Pre-Filter Clogged Status | | | 12 | | | | ● | | ● | Sensor & field wiring |
| v | Fine Filter Clogged Status | | | 12 | | | | ● | | ● | Sensor & field wiring |
| vi | Unit Trip Status | | | 12 | | | | ● | | ● | Potential Free Contact to BMS from MCC Panel |
| vii | Duct Static Pressure | | 12 | | | | | ● | | | Sensor & field wiring |
| viii | Return Air Temperature and Humidity Monitoring | | 24 | | | | | ● | | ● | Sensor & field wiring — 1 combined sensor per unit giving 2 analogue signals |
| ix | Supply Air Temperature Monitoring | | 12 | | | | | ● | | ● | 1 sensor per unit = 1 AI. Previously counted as 2 AI per unit against 1 device. |
| x | 2-Way CHW Valve Modulating Control | | | | 12 | | | | ● | | Output signal from DDC controller, wiring to valve actuator |
| xi | 2-Way CHW Valve Position Feedback | | 12 | | | | | ● | | | Feedback signal from valve actuator to DDC controller |
| xii | CHW Line Supply and Return Temperature Monitoring | | 24 | | | | | ● | | | Sensor & field wiring |
| xiii | Motorised Fresh Air Damper Modulating Command | | | | 12 | | | | ● | | Output signal from DDC controller, wiring to damper actuator |
| xiv | Motorised Fresh Air Damper Position Feedback | | 12 | | | | | ● | | | Feedback signal from damper actuator to DDC controller |
| xv | VFD Speed Control Output | | | | 12 | | | | ● | | Input signal (0-10 V) to control VFD frequency on return air basis |
| xvi | VFD Frequency Feedback | | 12 | | | | | ● | | | 0-10 V feedback from VFD to DDC to monitor frequency. Register data included in the 20 objects per unit at Sr. 4. |
| xvii | CO2 Sensor in Return Air Duct | | 12 | | | | | ● | | ● | Sensor & field wiring |
| xviii | Fire Damper Open / Close Status | | | 48 | | | | ● | | ● | 4 dampers per unit (was 2). To be reconciled against the approved fire damper schedule. |
| xix | Duct Smoke Detector Status — supply and return air duct | | | 24 | | | | ● | | ● | AHU smoke-sensitive devices for actuation and control — shutdown on duct smoke detection (NBCS 2026 Part F cl. 3.5.7.2.1). Not provided in the previous issue. |
| xx | Protocol integration (soft points) | | | | | | 240 | ● | | | Modbus/BACnet Integration — 20 objects per unit (includes VFD register data) |
| 5 | Fan coil unit | 60 | | | | | 600 | | | | |
| i | Protocol integration (soft points) | | | | | | 600 | ● | | | Modbus/BACnet Integration — 10 objects per unit |
| VENTILATION | | | | | | | | | | | |
| 6 | Smoke / exhaust fan — fire-rated axial B1 | 8 | | | | | | | | | |
| i | Fan Auto / Manual Status | | | 15 | | | | ● | | | Potential Free Contact to BMS from Fan Starter Panel |
| ii | Fan Trip Status | | | 15 | | | | ● | | ● | Potential Free Contact to BMS from Fan Starter Panel |
| iii | Fan ON / OFF Status | | | 15 | | | | ● | | | Potential Free Contact to BMS from Fan Starter Panel |
| iv | Fan Auto / Manual Status | | | 15 | | | | ● | | | Potential Free Contact to BMS from Fan Starter Panel |
| v | Fan Trip Status | | | 15 | | | | ● | | ● | Potential Free Contact to BMS from Fan Starter Panel |
| vi | Fan ON / OFF Status | | | 15 | | | | ● | | | Potential Free Contact to BMS from Fan Starter Panel |
| vii | Fan Auto / Manual Status | | | 7 | | | | ● | | | Potential Free Contact to BMS from Fan Starter Panel |
| viii | Fan Trip Status | | | 7 | | | | ● | | ● | Potential Free Contact to BMS from Fan Starter Panel |
| ix | Fan ON / OFF Status | | | 7 | | | | ● | | | Potential Free Contact to BMS from Fan Starter Panel |
| x | Fan Auto / Manual Status | | | 7 | | | | ● | | | Potential Free Contact to BMS from Fan Starter Panel |
| xi | Fan Trip Status | | | 7 | | | | ● | | ● | Potential Free Contact to BMS from Fan Starter Panel |
| xii | Fan ON / OFF Status | | | 7 | | | | ● | | | Potential Free Contact to BMS from Fan Starter Panel |
| xiii | Fan Auto / Manual Status | | | 7 | | | | ● | | | Potential Free Contact to BMS from Fan Starter Panel |
| xiv | Fan Trip Status | | | 7 | | | | ● | | ● | Potential Free Contact to BMS from Fan Starter Panel |
| xv | Fan ON / OFF Status | | | 7 | | | | ● | | | Potential Free Contact to BMS from Fan Starter Panel |
| xvi | Fan Auto / Manual Status | | | 2 | | | | ● | | | Potential Free Contact to BMS from Fan Starter Panel |
| xvii | Fan Trip Status | | | 2 | | | | ● | | ● | Potential Free Contact to BMS from Fan Starter Panel |
| xviii | Fan ON / OFF Status | | | 2 | | | | ● | | | Potential Free Contact to BMS from Fan Starter Panel |
| xix | Fan Auto / Manual Status | | | 2 | | | | ● | | | Potential Free Contact to BMS from Fan Starter Panel |
| xx | Fan Trip Status | | | 2 | | | | ● | | ● | Potential Free Contact to BMS from Fan Starter Panel |
| xxi | Fan ON / OFF Status | | | 2 | | | | ● | | | Potential Free Contact to BMS from Fan Starter Panel |
| 7 | Staircase pressurisation fan | 4 | | | | | 12 | | | | |
| i | Fan Auto / Manual Status | | | 4 | | | | ● | | | Potential Free Contact to BMS from Fan Starter Panel, plus soft integration (dual path — life safety) |
| ii | Fan Auto / Manual Status | | | | | | 4 | ● | | | Potential Free Contact to BMS from Fan Starter Panel, plus soft integration (dual path — life safety) |
| iii | Fan Trip Status | | | 4 | | | | ● | | ● | Potential Free Contact to BMS from Fan Starter Panel, plus soft integration (dual path — life safety) |
| iv | Fan Trip Status | | | | | | 4 | ● | | ● | Potential Free Contact to BMS from Fan Starter Panel, plus soft integration (dual path — life safety) |
| v | Fan ON / OFF Status | | | 4 | | | | ● | | | Potential Free Contact to BMS from Fan Starter Panel, plus soft integration (dual path — life safety) |
| vi | Fan ON / OFF Status | | | | | | 4 | ● | | | Potential Free Contact to BMS from Fan Starter Panel, plus soft integration (dual path — life safety) |
| PLUMBING AND WATER | | | | | | | | | | | |
| 8 | Domestic water transfer pump B2 | 2 | | | | | | | | | |
| i | Pump ON / OFF Command | | | | | 2 | | | ● | | Potential Free Contact from BMS to Pump Starter Panel. Quantity was blank in the previous issue — the pumps could not be started by BMS. |
| ii | Pump Auto / Manual Status | | | 2 | | | | ● | | | 1 DI per pump (was 2 per pump against a quantity of 16). |
| iii | Pump Run Status | | | 2 | | | | ● | | | 1 DI per pump. Sensor & field wiring |
| iv | Pump Trip Status | | | 2 | | | | ● | | ● | 1 DI per pump. Potential Free Contact to BMS from Pump Starter Panel |
| 9 | Water tank level monitoring | 6 | | | | | | | | | |
| i | Water Tank High and Low Level Status | | | 12 | | | | ● | | ● | Sensor & field wiring |
| ii | Water Tank Continuous Level Measurement | | 6 | | | | | ● | | | Analogue level transmitter per tank for water accounting and pump control; only switches were provided. |
| FIRE FIGHTING | | | | | | | | | | | |
| 10 | Fire-fighting pump set (main, standby, jockey, sprinkler) | 1 | | | | | | | | | |
| i | DIESEL FIRE PUMP — Run, Trip, Auto/Manual Status | | | 24 | | | | ● | | ● | 3 DI per pump. Monitoring only — no BMS command to fire pumps; life-safety systems are stand-alone and pump status is monitored at the FA panel (NBCS 2026 Part D Sec 3 cl. 15.1.2 / NBCS 2026 Part F cl. 4.9 (j)). |
| ii | ELECTRICAL HYDRANT PUMP — Run, Trip, Auto/Manual Status | | | 12 | | | | ● | | ● | 3 DI per pump. Monitoring only — no BMS command to fire pumps; life-safety systems are stand-alone and pump status is monitored at the FA panel (NBCS 2026 Part D Sec 3 cl. 15.1.2 / NBCS 2026 Part F cl. 4.9 (j)). |
| iii | JOCKEY PUMP FOR HYDRANT — Run, Trip, Auto/Manual Status | | | 12 | | | | ● | | ● | 3 DI per pump. Monitoring only — no BMS command to fire pumps; life-safety systems are stand-alone and pump status is monitored at the FA panel (NBCS 2026 Part D Sec 3 cl. 15.1.2 / NBCS 2026 Part F cl. 4.9 (j)). |
| iv | JOCKEY PUMP FOR SPRINKLER — Run, Trip, Auto/Manual Status | | | 12 | | | | ● | | ● | 3 DI per pump. Monitoring only — no BMS command to fire pumps; life-safety systems are stand-alone and pump status is monitored at the FA panel (NBCS 2026 Part D Sec 3 cl. 15.1.2 / NBCS 2026 Part F cl. 4.9 (j)). |
| v | ELECTRICAL SPRINKLER PUMP — Run, Trip, Auto/Manual Status | | | 12 | | | | ● | | ● | 3 DI per pump. Monitoring only — no BMS command to fire pumps; life-safety systems are stand-alone and pump status is monitored at the FA panel (NBCS 2026 Part D Sec 3 cl. 15.1.2 / NBCS 2026 Part F cl. 4.9 (j)). |
| vi | WATER CURTAIN PUMP — Run, Trip, Auto/Manual Status | | | 12 | | | | ● | | ● | 3 DI per pump. Monitoring only — no BMS command to fire pumps; life-safety systems are stand-alone and pump status is monitored at the FA panel (NBCS 2026 Part D Sec 3 cl. 15.1.2 / NBCS 2026 Part F cl. 4.9 (j)). |
| vii | JOCKEY PUMP FOR WATER CURTAIN — Run, Trip, Auto/Manual Status | | | 12 | | | | ● | | ● | 3 DI per pump. Monitoring only — no BMS command to fire pumps; life-safety systems are stand-alone and pump status is monitored at the FA panel (NBCS 2026 Part D Sec 3 cl. 15.1.2 / NBCS 2026 Part F cl. 4.9 (j)). |
| viii | Pressure Monitoring at Hydrant and Sprinkler Headers | | 2 | | | | | ● | | ● | Sensor & field wiring |
| FIRE ALARM AND LIFE SAFETY | | | | | | | | | | | |
| 11 | Fire alarm system interface | 1 | | | | | 25000 | | | | |
| i | Fire Alarm System — Pin Point Alarm Devices | | | | | | 25000 | ● | | ● | INDICATIVE. Read over a single protocol interface at the FAS network controller. To be confirmed against the approved Fire Alarm device schedule — refer Note 5. |
| ii | Fire Zone Trigger Contact to BMS (hardwired, per fire zone) | | | 1 | | | | ● | | ● | Hardwired isolated potential free contact per fire zone from the FACP. Quantity to be fixed against the approved fire zone schedule. |
| LIFTS AND ESCALATORS | | | | | | | | | | | |
| 12 | Lift monitoring | 6 | | | | | 90 | | | | |
| i | Lift Fireman’s Return / Fire Mode Status (hardwired) | | | 6 | | | | ● | | ● | Life safety status must not depend solely on the lift controller network. |
| ii | Protocol integration (soft points) | | | | | | 90 | ● | | | Modbus/BACnet Integration — 15 objects per lift — floor position, direction, load / overload, door status, modes (attendant, automatic, independent, fire service, seismic, EMS, inspection) (NBCS 2026 Part D Sec 5 cl. 9.8 (a)); lift control only through a BA interface, potential-free contacts give monitoring only |
| ELECTRICAL | | | | | | | | | | | |
| 13 | UPS system | 2 | | | | | 50 | | | | |
| i | UPS Trip Status | | | 2 | | | | ● | | ● | Potential Free Contact to BMS from UPS Panel |
| ii | UPS Auto / Manual Status | | | 2 | | | | ● | | | Potential Free Contact to BMS from UPS Panel |
| iii | UPS Inverter Failure | | | 2 | | | | ● | | ● | Potential Free Contact to BMS from UPS Panel |
| iv | Protocol integration (soft points) | | | | | | 50 | ● | | | Modbus/BACnet Integration — electrical and battery parameters |
| 14 | HT breaker (33 kV / 11 kV) | 4 | | | | | 80 | | | | |
| i | Breaker ON / OFF Status | | | 4 | | | | ● | | | Potential Free Contact to SCADA from HT / LT Panel |
| ii | Breaker Trip Status | | | 4 | | | | ● | | ● | Potential Free Contact to SCADA from HT / LT Panel |
| iii | Breaker Auto / Manual Status | | | 4 | | | | ● | | | Potential Free Contact to SCADA from HT / LT Panel |
| iv | Protocol integration (soft points) | | | | | | 80 | ● | | | Modbus/BACnet Integration — MFM at 20 registers per breaker |
| 15 | Power / distribution transformer | 2 | | | | | | | | | |
| i | Transformer HV / LV Breaker ON / OFF Status | | | 2 | | | | ● | | | A transformer has no ON/OFF of its own — this is its incomer and outgoing breaker status. Potential Free Contact to SCADA from HT / LT Panel |
| ii | Transformer Trip Status | | | 2 | | | | ● | | ● | Potential Free Contact to SCADA from HT / LT Panel |
| iii | Winding Temperature Alarm | | | 2 | | | | ● | | ● | Potential Free Contact to SCADA from HT / LT Panel |
| iv | Winding Temperature Trip | | | 2 | | | | ● | | ● | Potential Free Contact to SCADA from HT / LT Panel |
| v | Oil Temperature Alarm | | | 2 | | | | ● | | ● | Potential Free Contact to SCADA from HT / LT Panel |
| vi | Oil Temperature Trip | | | 2 | | | | ● | | ● | Potential Free Contact to SCADA from HT / LT Panel |
| vii | Winding Temperature Value | | 2 | | | | | ● | | | 4-20 mA output from WTI. Previously only alarm and trip contacts — no trendable value. |
| viii | Oil Temperature Value | | 2 | | | | | ● | | | 4-20 mA output from OTI. Previously only alarm and trip contacts — no trendable value. |
| 16 | LT main ACB / bus coupler / capacitor source | 6 | | | | | 120 | | | | |
| i | Breaker ON / OFF Command | | | | | 12 | | | ● | | Potential Free Contact from SCADA to LT Panel. 2 DO per breaker (close and open), subject to the local/remote selector being in Remote. Scope of remote switchin |
| ii | Breaker ON / OFF Status | | | 6 | | | | ● | | | Potential Free Contact to SCADA from HT / LT Panel |
| iii | Breaker Trip Status | | | 6 | | | | ● | | ● | Potential Free Contact to SCADA from HT / LT Panel |
| iv | Breaker Auto / Manual Status | | | 6 | | | | ● | | | Potential Free Contact to SCADA from HT / LT Panel |
| v | Breaker Spring Charged Status | | | 6 | | | | ● | | | Potential Free Contact to SCADA from HT / LT Panel |
| vi | Protocol integration (soft points) | | | | | | 120 | ● | | | Modbus/BACnet Integration — MFM at 20 registers per breaker |
| 17 | DG set with synchronising panel | 2 | | | | | 60 | | | | |
| i | DG Internal and Outer Fuel Tank Low Level | | | 4 | | | | ● | | ● | Sensor & field wiring — flame proof level switch |
| ii | DG Fuel Tank Continuous Level Measurement | | 4 | | | | | ● | | | Level switches alone give no available run time. 4-20 mA transmitter on day and bulk tanks. |
| iii | DG Battery Under Voltage Fault | | | 2 | | | | ● | | ● | Sensor & field wiring — DC voltage transducer |
| iv | DG Battery Voltage Value | | 2 | | | | | ● | | | The DC voltage transducer is already provided; its analogue output was discarded and only a threshold contact was taken. |
| v | Protocol integration (soft points) | | | | | | 60 | ● | | | Modbus/BACnet Integration — 30 parameters per set: start/stop, sync panel status, auto/manual, on-load/off-load, low oil pressure warning and shutdown, hot wate |
| ENERGY AND METERING | | | | | | | | | | | |
| 18 | Multi-function meter — LT panel feeder | 40 | | | | | 800 | | | | |
| i | Protocol integration (soft points) | | | | | | 800 | ● | | | MOVED from the BMS I/O Summary and re-based at 20 registers per meter. The SCADA polls these meters once; the BMS reads a 5-parameter subset from the SCADA serv |
| LIGHTING CONTROL | | | | | | | | | | | |
| 19 | Lighting control circuit | 80 | | | | | | | | | |
| i | Circuit ON / OFF Status | | | 80 | | | | ● | | | Potential Free Contact to BMS from Distribution Board |
| ii | Circuit ON / OFF Command | | | | | 80 | | | ● | | Potential Free Contact from BMS to Distribution Board |