Bus bar / bus duct sizing

Sample project — Tower A · Electrical
Generated 28 Nov 2026 16:09
Continuous rating of flat copper / aluminium bars by heat balance, number of bars per phas…
Project code SAMPLE
Bar per phase
1 × 100 × 10 mm
Rating
1772.8 A
Section
1000 mm²
Current density
1.6 A/mm²
Max support spacing
396.1 mm
Loss at Ir
161.9 W/m

1. Inputs

GroupInputValueUnit
DutyConductor materialCopper
DutyRated current per phase1600A
DutyShort-circuit current (rms)50kA
DutyPeak short-circuit current (blank = 2.2 × Ik)kA
DutyFault duration1.0s
DutyArrangementOpen air (bars on edge, free convection)
ThermalAmbient temperature40°C
ThermalPermissible temperature rise35K
ThermalSurface finishBright / bare (ε ≈ 0.3)
ThermalBars per phase (0 = auto)0
ThermalPreferred bar width (0 = auto)0mm
MechanicalPhase centre spacing150mm
MechanicalSupport spacing (0 = compute maximum)0mm
MechanicalLongest straight run (busduct / rising main, 0 = n/a)0m
MechanicalRun directionHorizontal
MechanicalSupport factor β0.73 continuous beam, 3+ supports

2. Results

Continuous rating (heat balance per metre)

ItemValueUnitNote / basis
Bar surface temperature75.0°C
Convection coefficient, vertical faces6.14W/m²K
Radiation coefficient (ε = 0.30)2.47W/m²K
Heat dissipated at the rise66.26W/m
Resistance at operating temperature (incl. skin factor 1.01)21.09µΩ/m
Rating in open air1772.77A
Enclosure factor1.0
Rating in the arrangement1772.77A
Weight (three phases)26.7kg/m

Short-circuit

ItemValueUnitNote / basis
Thermal minimum section349.65mm²k = 143 A·√s/mm²
Peak current used110.0kA
Force between phases (centre phase, three-phase)13971.47N/m
Section modulus (n bars)1666.67mm³
Permissible stress120.0N/mm²
Stress at selected spacing116.35N/mm²
Maximum support spacing396.08mm

Building code — NBCS 2026 (SP 7:2026) Part D Sec 2 cl. 5.3.8

ItemValueUnitNote / basis
Neutral bar (NBCS 2026 D2 cl. 8.2.9.1 note)1 × 100 × 10 mm — same as phasefull-size neutral where harmonics are present; earth bar by Ik²t
Straight run / seismic supports (cl. 5.3.8.1)not enteredlimit 24 m horizontal
Fire compartments (cl. 5.3.8.3)fire barrier of the compartment rating at every crossingsee NBCS Part F
Coordination (cl. 5.3.8.2) / standard (5.3.8.4)trunking coordinated with the feeding switchgear; IS/IEC 61439-6 type-tested

Alternatives (rating in the arrangement)

Bars/phaseSize mmSection mm²Rating AA/mm²OK
1100 × 10100017731.6✓
250 × 10100017631.6✓
340 × 896018561.67✓
430 × 672016172.22✓
Cross-section — 1 × 100 × 10 mm per phase on edge, phase centres 150 mmL1150L2150L3150NTo scale. Bars on edge, 10 mm apart within a phase; neutral full size (NBCS 2026 D2 8.2.9.1).Rating vs bars per phase — 100 × 10 mm CU, 35 K over 40 °C02 0004 0006 0008 00010 000bars per phaseA1 × 100×10: 1 7731 7732 × 100×10: 3 1623 1623 × 100×10: 4 5354 5354 × 100×10: 5 9035 9031 × 100×102 × 100×103 × 100×104 × 100×10I_r 1600 Arating in the arrangement (A)

3. Checks

CheckResultNote
Continuous rating 1,773 A ≥ 1,600 APASS1 × 100 × 10 mm CU per phase, 35 K rise over 40 °C
Short-circuit section 1,000 mm² ≥ 350 mm²PASSA ≥ Ik·√t / k = 50.0 kA × √1.0 / 143
Bending stress 116.3 N/mm² ≤ 120.0 N/mm²PASSsupport spacing 390 mm (max 396 mm)

4. Worked example

Worked from this calculation's own inputs — each value matches the results table above.

1 × 100 × 10 mm CU per phase for 1600 A
the selected bar of this calculation
Given: Duty Ir 1600 A, Ik 50 kA for 1 s, ip 110.0 kA · Thermal ambient 40 °C, rise 35 K, ε 0.3 · Arrangement enclosure factor 1, phase spacing 150 mm
1. Convection, vertical faces: hv = 1.42 · (ΔT / w)0.25 = 1.42 · (35 / 0.1)0.25 = 6.14 W/m²K
2. Radiation: hr = ε · σ · (Ts⁴ − Ta⁴) / ΔT = 0.3 · 5.67×10⁻⁸ · (348.15⁴ − 313.15⁴) / 35 = 2.47 W/m²K
3. Heat dissipated per metre: P = Σ (h · surface) · ΔT = 66.3 W/m
4. Resistivity at the bar temperature: ρθ = ρ20 · (1 + α · (θ − 20)) = 1.72e-08 · (1 + 0.00393 · (75 − 20)) = 2.092e-08 Ω·m
5. Resistance per metre: R = ρθ / (n · w · t) · kskin = 2.092e-08 / (1 · 100 · 10 ×10⁻⁶) · 1.008 = 21.09 µΩ/m
6. Open-air rating: I = √(P / R) = √(66.3 / 2.109e-05) = 1773 A
7. Rating in the arrangement: I · kencl ≥ Ir → 1773 · 1 = 1773 A ≥ 1600 A PASS (current density 1.60 A/mm², loss 162 W/m (3 phases))
8. Thermal minimum section: Amin = Ik · √t / k = 50,000 · √1 / 143 = 349.7 mm²
9. Short-circuit section: n · w · t ≥ Amin → 1000 ≥ 349.7 mm² PASS
10. Force on the centre phase: F′ = 0.866 · 2×10⁻⁷ · ip² / a = 0.866 · 2×10⁻⁷ · 110,000² / 0.15 = 13 971 N/m
11. Section modulus (force across the thickness): Z = n · w · t² / 6 = 1 · 100 · 10² / 6 = 1666.7 mm³
12. Maximum support spacing: Lmax = √(8 · Z · σp / (β · F′)) = √(8 · 1666.7 · 120 / (0.73 · 13.971)) = 396 mm
13. Bending stress at the chosen spacing: σ = β · F′ · L² / (8 · Z) ≤ σp → 0.73 · 13.971 · 390² / (8 · 1666.7) = 116.3 ≤ 120 N/mm² PASS
Neutral bar = phase size (NBCS 2026 Part D Sec 2 cl. 8.2.9.1 note).

5. Notes

6. Standards and references

Prepared by
Checked by
Approved by

Results are design aids computed by designlink calc (calc.designlink.in) and must be reviewed by a qualified engineer before issue. Ground levels marked "assumed" have no survey level within reach — verify.