calc.designlink.inCeiling fan size & number
Sample project — Tower A · Electrical
Generated 28 Nov 2026 17:16
Sweep and number of ceiling fans for a room, spacing on the ceiling, blade height and the …
Project code SAMPLE
1. Inputs
| Group | Input | Value | Unit |
|---|
| Room | Length | 6 | m |
| Room | Width | 4.5 | m |
| Room | Ceiling height | 3.2 | m |
| Room | Sweep (0 = choose) | Choose for me | |
| Room | Blade height above floor | 2.6 | m |
2. Results
Layout
| Item | Value | Unit | Note / basis |
|---|
| Room area | 27.0 | m² | |
| Area per fan | 14.0 | m² | 1200 mm sweep (typical) |
| Spacing along the length | 3.0 | m | |
| Spacing along the width | 4.5 | m | |
| First fan from the walls | 1.50 / 2.25 | m | |
| Down-rod length | 0.3 | m | ceiling − blade height − motor & canopy 0.3 m |
3. Checks
| Check | Result | Note |
|---|
| Blade height 2.6 m ≥ 2.4 m | PASS | |
| Ceiling high enough for the blade height | PASS | use a hugger fan or a lower blade height if negative |
4. Worked example
Area 27.0 m² ÷ 14 m² per 1200 mm fan → 2 × 1 = 2 fans; down-rod = 3.2 − 2.6 − 0.3 = 0.30 m
5. Notes
- Choose BEE star-rated (BLDC) fans; air delivery and service value per IS 374 from the maker's data.
6. Standards and references
- NBC 2016 Part 8 Sec 2 — National Building Code — Electrical and allied installations (load assessment): Load assessment per occupancy, demand factors, sub-circuits, DBs
- IS 374 — Electric ceiling type fans and regulators: Ceiling fans
Prepared by
Checked by
Approved by
Results are design aids computed by designlink calc (calc.designlink.in) and must be reviewed by a qualified engineer before issue. Ground levels marked "assumed" have no survey level within reach — verify.