Conduit & trunking size

Sample project — Tower A · Electrical
Generated 28 Nov 2026 17:16
Smallest conduit or trunking for the cables drawn in: cable areas from the overall diamete…
Project code SAMPLE
Cables
12
Cable area
134.8 mm²
Selected
25 mm
Fill
37.5 %

1. Inputs

GroupInputValueUnit
CablesCables — one group per line: count x size mm² (or count x OD mm)6 x 1.5 4 x 2.5 2 x 4
ContainerRun inPVC conduit, medium (IS 9537 Part 3)
ContainerFill limit (0 = standard rule)0%

2. Results

Result

ItemValueUnitNote / basis
Cables12
Total cable area134.82mm²
Fill limit40.0%conduit 53 / 31 / 40 % for 1 / 2 / 3+ cables; trunking 45 % (typical)
Selected25 mmfill 37.5 %

Cables

GroupOD mmArea mm²
6 × 1.5 mm²3.351
4 × 2.5 mm²450
2 × 4 mm²4.633

Sizes (limit 40 %)

SizeInternal Ø mmFill %
16 mm13101.6—
20 mm16.960.1—
25 mm21.437.5OK
32 mm27.822.2OK
40 mm35.413.7OK
50 mm44.48.7OK
63 mm56.45.4OK

3. Checks

CheckResultNote
25 mm at 37.5 % ≤ 40 %PASS

4. Worked example

Area = Σ n·π·d²/4 = 135 mm²; 25 mm: 135 / internal area = 37.5 %