calc.designlink.inConduit & trunking size
Sample project — Tower A · Electrical
Generated 28 Nov 2026 17:16
Smallest conduit or trunking for the cables drawn in: cable areas from the overall diamete…
Project code SAMPLE
1. Inputs
| Group | Input | Value | Unit |
|---|
| Cables | Cables — one group per line: count x size mm² (or count x OD mm) | 6 x 1.5
4 x 2.5
2 x 4 | |
| Container | Run in | PVC conduit, medium (IS 9537 Part 3) | |
| Container | Fill limit (0 = standard rule) | 0 | % |
2. Results
Result
| Item | Value | Unit | Note / basis |
|---|
| Cables | 12 | | |
| Total cable area | 134.82 | mm² | |
| Fill limit | 40.0 | % | conduit 53 / 31 / 40 % for 1 / 2 / 3+ cables; trunking 45 % (typical) |
| Selected | 25 mm | | fill 37.5 % |
Cables
| Group | OD mm | Area mm² |
|---|
| 6 × 1.5 mm² | 3.3 | 51 |
| 4 × 2.5 mm² | 4 | 50 |
| 2 × 4 mm² | 4.6 | 33 |
Sizes (limit 40 %)
| Size | Internal Ø mm | Fill % | |
|---|
| 16 mm | 13 | 101.6 | — |
| 20 mm | 16.9 | 60.1 | — |
| 25 mm | 21.4 | 37.5 | OK |
| 32 mm | 27.8 | 22.2 | OK |
| 40 mm | 35.4 | 13.7 | OK |
| 50 mm | 44.4 | 8.7 | OK |
| 63 mm | 56.4 | 5.4 | OK |
3. Checks
| Check | Result | Note |
|---|
| 25 mm at 37.5 % ≤ 40 % | PASS | |
4. Worked example
Area = Σ n·π·d²/4 = 135 mm²; 25 mm: 135 / internal area = 37.5 %
5. Notes
- Cable diameters and conduit bores are typical values — take the maker's figures for the final check; long runs with many bends need a lower fill (draw-in boxes every two bends / ~10 m, typical).
6. Standards and references
- BS 7671:2018+A2 — Requirements for Electrical Installations (IET Wiring Regulations): Radial / ring circuit arrangements, diversity (Appendix 15 / on-site guide)
- IS 9537 Part 1, 2, 3 — Conduits for electrical installations: MS and PVC conduits
- NFPA 70 (NEC 2023) — National Electrical Code: Wiring methods, articles 250, 450, 520, 620, 640, 700, 760, 800
Prepared by
Checked by
Approved by
Results are design aids computed by designlink calc (calc.designlink.in) and must be reviewed by a qualified engineer before issue. Ground levels marked "assumed" have no survey level within reach — verify.