Building drainage — stacks, branches, vents

Sample project — Tower A · Indian regime · NBCS 2026 (SP 7:2026) Part E Sec 2 · two-pipe (soil + waste + vent)
Generated 28 Nov 2026 16:09
Fixture units → branches, stacks, vents, building drain
Project code SAMPLE
Stacks
3
Fixtures
108
Total DFU
210.0
Largest stack
100 mm
Building drains
3
Largest drain
125 mm

1. Design basis

ItemValueReference
Code editionNBCS 2026 (SP 7:2026) Part E Sec 2settings · code_edition
Systemtwo-pipe (soil + waste + vent)NBCS 2026 Part E Sec 2 (two-pipe / one-pipe)
Fixture unitsDFU per fixture, public basisNBCS 2026 Part E Sec 2 Table 20 (+ Table 21 by trap size)
MethodDFU summed per branch, accumulated down the stack; stack by DFU and branch intervals; building drain by DFU and slope; vent by stack size, DFU and developed lengthNBCS 2026 Part E Sec 2 Table 22 col 3, NBCS 2026 Part E Sec 2 Table 22 cols 4–6, NBCS 2026 Part E Sec 2 Table 23, NBCS 2026 Part E Sec 2 Table 19
Stack size reductionnot used — stack uniform over its heightcl. 4.5.2.4.2.1 / 4.5.3.2.1
Minimum sizessoil stack / WC branch 100 mm, waste 75 mm, vent 50 mm, building drain 100 mm at 1.0 %cl. 4.5.3.2, 4.5.3.3, 4.5.3.4.6, Table 23 note 2; vent ≥ ½ stack and ≥ 32 mm (4.5.3.4.7); building-drain vent ≥ 75 mm (4.5.3.4.6 a)
MaterialuPVC SWR (IS 13592) / CI (IS 3989)IS 13592 / IS 3989
Branch interval3.0 m (storey height)project

2. Fixture units

DFU values: NBCS 2026 Part E Sec 2 Table 20.

FixtureNosDFU eachDFU
WC — flush tank24496
Urinal18236
Floor trap / floor drain30260
Wash basin24124
AHU / FCU drain616
Kitchen sink6212
Total108210.0

3. Riser diagram

VENT 75 mmSS-1 · SOIL 100 mm · 132 DFUF5100 mm · 22 DFU4 × WC, 3 × UrinalΣ 22F4100 mm · 22 DFU4 × WC, 3 × UrinalΣ 44F3100 mm · 22 DFU4 × WC, 3 × UrinalΣ 66F2100 mm · 22 DFU4 × WC, 3 × UrinalΣ 88F1100 mm · 22 DFU4 × WC, 3 × UrinalΣ 110GF100 mm · 22 DFU4 × WC, 3 × UrinalΣ 132VENT 50 mmWS-1 · WASTE 75 mm · 54 DFUF575 mm · 9 DFU4 × Wash basin, 2 × Floor trap / floor drain, 1 × AHU / FCU Σ 9F475 mm · 9 DFU4 × Wash basin, 2 × Floor trap / floor drain, 1 × AHU / FCU Σ 18F375 mm · 9 DFU4 × Wash basin, 2 × Floor trap / floor drain, 1 × AHU / FCU Σ 27F275 mm · 9 DFU4 × Wash basin, 2 × Floor trap / floor drain, 1 × AHU / FCU Σ 36F175 mm · 9 DFU4 × Wash basin, 2 × Floor trap / floor drain, 1 × AHU / FCU Σ 45GF75 mm · 9 DFU4 × Wash basin, 2 × Floor trap / floor drain, 1 × AHU / FCU Σ 54VENT 50 mmWS-2 · WASTE 75 mm · 24 DFUF575 mm · 4 DFU1 × Kitchen sink, 1 × Floor trap / floor drainΣ 4F475 mm · 4 DFU1 × Kitchen sink, 1 × Floor trap / floor drainΣ 8F375 mm · 4 DFU1 × Kitchen sink, 1 × Floor trap / floor drainΣ 12F275 mm · 4 DFU1 × Kitchen sink, 1 × Floor trap / floor drainΣ 16F175 mm · 4 DFU1 × Kitchen sink, 1 × Floor trap / floor drainΣ 20GF75 mm · 4 DFU1 × Kitchen sink, 1 × Floor trap / floor drainΣ 24GROUND · BUILDING DRAINBD-1: SS-1 → IC-1 · 100 mm @ 1 % · 132 DFU · 8 mBD-2: WS-1, WS-2 → IC-2 · 100 mm @ 1 % · 78 DFU · 14 mBD-3: SS-1, WS-1, WS-2 → municipal sewer · 125 mm @ 1 % · 210 DFU · 25 m

4. DFU accumulation down each stack

SS-1 · soil stack 100 mm · Σ 132 DFU · 6 branch intervalsF5Σ 22stack 100 · branch 100 mmF4Σ 44stack 100 · branch 100 mmF3Σ 66stack 100 · branch 100 mmF2Σ 88stack 100 · branch 100 mmF1Σ 110stack 100 · branch 100 mmGFΣ 132stack 100 · branch 100 mmlimit 500 DFU — NBCS 2026 Part E Sec 2 Table 22 cols 4–6, 100 mmper interval ≤ 90WS-1 · waste stack 75 mm · Σ 54 DFU · 6 branch intervalsF5Σ 9stack 75 · branch 75 mmF4Σ 18stack 75 · branch 75 mmF3Σ 27stack 75 · branch 75 mmF2Σ 36stack 75 · branch 75 mmF1Σ 45stack 75 · branch 75 mmGFΣ 54stack 75 · branch 75 mmlimit 72 DFU — NBCS 2026 Part E Sec 2 Table 22 cols 4–6, 75 mmper interval ≤ 20WS-2 · waste stack 75 mm · Σ 24 DFU · 6 branch intervalsF5Σ 4stack 75 · branch 75 mmF4Σ 8stack 75 · branch 75 mmF3Σ 12stack 75 · branch 75 mmF2Σ 16stack 75 · branch 75 mmF1Σ 20stack 75 · branch 75 mmGFΣ 24stack 75 · branch 75 mmlimit 72 DFU — NBCS 2026 Part E Sec 2 Table 22 cols 4–6, 75 mmper interval ≤ 20dark bar = branch DFU at the floor · light bar = DFU accumulated down to that floor

5. Stacks and branches

SS-1 — soil stack 100 mm · vent 75 mm

6 branch intervals: total 132 ≤ 500, per interval 22 ≤ 90 · vent: Table 19: stack 100 mm, ≤ 140 DFU, developed length 21 ≤ 61 m

FloorFixtures on the branchBranch DFUBranch dia mmΣ DFU belowStack dia mm
F54 × WC, 3 × Urinal22.010022.0100
F44 × WC, 3 × Urinal22.010044.0100
F34 × WC, 3 × Urinal22.010066.0100
F24 × WC, 3 × Urinal22.010088.0100
F14 × WC, 3 × Urinal22.0100110.0100
GF4 × WC, 3 × Urinal22.0100132.0100

WS-1 — waste stack 75 mm · vent 50 mm

6 branch intervals: total 54 ≤ 72, per interval 9 ≤ 20 · vent: Table 19: stack 75 mm, ≤ 102 DFU, developed length 21 ≤ 26 m

FloorFixtures on the branchBranch DFUBranch dia mmΣ DFU belowStack dia mm
F54 × Wash basin, 2 × Floor trap / floor drain, 1 × AHU / FCU drain9.0759.075
F44 × Wash basin, 2 × Floor trap / floor drain, 1 × AHU / FCU drain9.07518.075
F34 × Wash basin, 2 × Floor trap / floor drain, 1 × AHU / FCU drain9.07527.075
F24 × Wash basin, 2 × Floor trap / floor drain, 1 × AHU / FCU drain9.07536.075
F14 × Wash basin, 2 × Floor trap / floor drain, 1 × AHU / FCU drain9.07545.075
GF4 × Wash basin, 2 × Floor trap / floor drain, 1 × AHU / FCU drain9.07554.075

WS-2 — waste stack 75 mm · vent 50 mm

6 branch intervals: total 24 ≤ 72, per interval 4 ≤ 20 · vent: Table 19: stack 75 mm, ≤ 53 DFU, developed length 21 ≤ 29 m

FloorFixtures on the branchBranch DFUBranch dia mmΣ DFU belowStack dia mm
F51 × Kitchen sink, 1 × Floor trap / floor drain4.0754.075
F41 × Kitchen sink, 1 × Floor trap / floor drain4.0758.075
F31 × Kitchen sink, 1 × Floor trap / floor drain4.07512.075
F21 × Kitchen sink, 1 × Floor trap / floor drain4.07516.075
F11 × Kitchen sink, 1 × Floor trap / floor drain4.07520.075
GF1 × Kitchen sink, 1 × Floor trap / floor drain4.07524.075

6. Building drains

SectionStacksToDFUSlope %Dia mmTable limit DFULength mFall mIL up / down mV half-full m/s
BD-1SS-1IC-1132.01.0100180 @ 1 %8.00.08-0.600 / -0.6800.57
BD-2WS-1, WS-2IC-278.01.0100180 @ 1 %14.00.14-0.600 / -0.7400.57
BD-3SS-1, WS-1, WS-2municipal sewer210.01.0125390 @ 1 %25.00.25-0.600 / -0.8500.66

Capacity: NBCS 2026 Part E Sec 2 Table 23 (columns 1/200, 1/100, 1/50, 1/25; the steepest column not steeper than the drain slope is used). Self-cleansing: half-full velocity ≥ 0.75 m/s (≥ 0.61 m/s where a flatter gradient is unavoidable), ≤ 2.4 m/s — cl. 4.5.3.5.2.2–4, Table 24; shown for information, the DFU table governs the size.

BD-1: SS-1 → IC-1 · Ø100 mm · 132 DFU (limit 180 — NBCS 2026 Part E Sec 2 Table 23, column 1 %)GL ±0.00 (assumed level)stack footIC-1IL -0.600IL -0.6800 m5 mL 8 m @ 1 % (1/100) · fall 0.080 m · V half-full 0.57 m/sBD-2: WS-1, WS-2 → IC-2 · Ø100 mm · 78 DFU (limit 180 — NBCS 2026 Part E Sec 2 Table 23, column 1 %)GL ±0.00 (assumed level)stack footIC-2IL -0.600IL -0.7400 m5 m10 mL 14 m @ 1 % (1/100) · fall 0.140 m · V half-full 0.57 m/sBD-3: SS-1, WS-1, WS-2 → municipal sewer · Ø125 mm · 210 DFU (limit 390 — NBCS 2026 Part E Sec 2 Table 23, column 1 %)GL ±0.00 (assumed level)stack footmunicipal sewerIL -0.600IL -0.8500 m5 m10 m15 m20 m25 mL 25 m @ 1 % (1/100) · fall 0.250 m · V half-full 0.66 m/svertical scale exaggerated · invert at the stack foot = drain depth setting unless entered · velocity: NBCS 2026 Part E Sec 2 cl. 4.5.3.5.2.2–5 (n 0.015)

7. Bill of quantities

ItemQtyUnit
Soil / waste stack 100 mm19.5m
Soil / waste stack 75 mm39.0m
Vent stack 75 mm21.0m
Vent stack 50 mm42.0m
Building drain 100 mm22.0m
Building drain 125 mm25.0m

8. Checks

CheckResult
Every stack within Table 22 (no stack above 300 mm)PASS
Soil branches / stacks with WCs ≥ 100 mm (cl. 4.5.2.4.2 g, 4.5.3.2); vertical waste ≥ 75 mm (cl. 4.5.3.3)PASS
Vent stacks within Table 19 for DFU and developed length; ≥ ½ stack, ≥ 32 mm (cl. 4.5.3.4.7)PASS
Building drains sized by Table 23 at their slope; all stacks connectedPASS
Drain slopes not flatter than 1/200 (flattest Table 23 column)PASS

9. Worked examples — from this project

Worked from this project’s own inputs and results — each value can be traced to the schedules above.

Stack SS-1 — soil, 6 branch intervals
the largest stack (132 DFU) of the two-pipe (soil + waste + vent)
Given: Branch at F5 4 × WC, 3 × Urinal
1. Branch fixture units: DFU = Σ n · DFUfixture = 4 × 4 + 3 × 2 = 22 DFU (NBCS 2026 Part E Sec 2 Table 20, public)
2. Horizontal branch: 22 DFU ≤ capacity of 100 mm → NBCS 2026 Part E Sec 2 Table 22 col 3 → 100 mm takes 160 DFU (WC on the branch → ≥ 100 mm) PASS
3. Stack load: Σ DFU over all branches (accumulated downwards) = 22 + 22 + 22 + 22 + 22 + 22 = 132 DFU (largest branch interval 22 DFU)
4. Stack size: NBCS 2026 Part E Sec 2 Table 22 cols 4–6, > 3 branch intervals → 100 mm: total 132 ≤ 500, per interval 22 ≤ 90 PASS (minimum 100 mm)
5. Vent developed length: Lv = intervals × storey + 3 m = 6 × 3 + 3 = 21 m
6. Vent stack: NBCS 2026 Part E Sec 2 Table 19 for a 100 mm stack → 75 mm PASS (Table 19: stack 100 mm, ≤ 140 DFU, developed length 21 ≤ 61 m)
Vent stack for SS-1 — NBCS 2026 Part E Sec 2 Table 19
stack size, DFU vented and developed length → vent diameter
Given: Stack 100 mm, 132 DFU · Developed length 21 m (from the vent connection to open air)
1. Table row: stack 100 mm, first DFU step ≥ 132 = 43, 140, 320, 540 = 140 DFU
2. Minimum vent: max(vent minimum, ½ stack, 32 mm) — cl. 4.5.3.4.6 b, 4.5.3.4.7 = max(50, 50 → 50, 32) = 50 mm

Row lengths: 50 mm ≤ 8 m · 65 mm ≤ 20 m · 75 mm ≤ 61 m · 100 mm ≤ 229 m

3. Vent size: smallest vent ≥ 50 mm with Lmax ≥ 21 m → 75 mm (Lmax 61 m) PASS
Building drain BD-3 → municipal sewer
the drain section carrying the most fixture units
Given: Stacks SS-1, WS-1, WS-2 · Slope 1 % (table column 1 % = 1/100)
1. Drain load: Σ DFU of the stacks = 132 + 54 + 24 = 210 DFU
2. Drain size: NBCS 2026 Part E Sec 2 Table 23 at 1 % → 125 mm takes 390 DFU ≥ 210 PASS (minimum 100 mm; 100 mm takes only 180 DFU)
3. Fall: Δh = L · slope = 25 × 1 / 100 = 0.25 m
4. Invert at the chamber: ILdn = ILup − Δh = -0.600 − 0.250 = -0.850 m
5. Half-full velocity: V = (1/n) (D/4)2/3 S1/2 = (1/0.015) × (0.125/4)2/3 × 0.011/2 = 0.66 m/s (NBCS cl. 4.5.3.5.2.2: ≥ 0.75 m/s self-cleansing (information))

10. Standards applied

StandardUsed for
NBCS 2026 (SP 7:2026) Part E Sec 2Drainage and sanitation — Tables 18 (single stack), 19 (vents), 20–21 (DFU), 22 (branches / stacks), 23 (building drains); cl. 4.5.2.4, 4.5.3
IS 1742:1983Building drainage — code of practice
IS 13592 / IS 3989uPVC SWR / CI pipes for soil, waste and vent
IS 5329Sanitary pipe work above ground
Prepared by
Checked by
Approved by

Results are design aids computed by designlink calc (calc.designlink.in) and must be reviewed by a qualified engineer before issue. Ground levels marked "assumed" have no survey level within reach — verify.