Design Linkcalc.designlink.in

Duct & chilled-water network sizing

Sample project — Tower A · Indian regime · NBCS 2026 (SP 7:2026) · 7 duct + 4 pipe sections
Generated 28 Nov 2026 16:09
Equal-friction ducts, velocity / friction pipes, index run → fan static / pump head
Project code SAMPLE
Air
1100 L/s
Fan static
510 Pa
Fan power
0.86 kW
Sheet
107.6 m²
Cooling
210 kW · 59.7 TR
CHW flow
9.1 L/s
Pump head
23.5 m
Fire dampers
1

1. Design basis

ItemValueReference
Code editionNBCS 2026 (SP 7:2026)NBCS 2026 (SP 7:2026) replaced NBC 2016 on 30 Apr 2026
Duct sizingequal friction 0.8 Pa/m; aspect ≤ 4.0; galvanised ε 0.09 mmASHRAE Fundamentals ch. 21; SMACNA; ISHRAE
Velocity capsmain 8 / branch 8 / run-out 4 m/s (NBCS 2026 Part D Sec 3 Table 18 — General offices, supply, main noise / friction-controlled)NBCS 2026 Part D Sec 3 cl. 8, Table 18
FittingsC × ρv²/2 with C: elbow 0.22, tee 0.5, damper 0.2, transition 0.1, outlet 1.0, fire damper 0.2ASHRAE Fundamentals ch. 21 (typical)
AHU componentsfilter 150 Pa, coil 200 Pa, diffuser 25 Pa, louvre 50 Pa, other 50 Pa = 475 Paproject
Sheet gaugeSMACNA rectangular, 500 Pa classSMACNA HVAC Duct Construction Standards
Insulation25 mm on supply ducts — Mineral / glass wool, FSK facedECBC 2017 / ASHRAE 90.1; Part F 3.5.7.3.5 non-combustible
Pressure classduct static at the AHU 110 Pa → Low; specified Low (Low ≤ +500, Medium ≤ +1000, High ≤ +2500 Pa)NBCS 2026 Part D Sec 3 Table 17
Duct supportsrectangular: angle + 2 rods at ≤ 2 400 mm; Table 40 up to 750 Pa, Table 41 aboveNBCS 2026 Part D Sec 3 cl. 17.3.11.1, Tables 40 / 41
Fire safetyfire dampers at fire walls, shaft entries, floor crossings and the compartment inlet; 120 min duct where a crossing has no damper; AHU smoke-sensitive device; non-combustible insulationNBCS 2026 Part F 3.5.7.2–3.5.7.4
Pipe sizingΔT 5.5 K; v ≤ 1.2 m/s ≤ 50 NB, ≤ 2.4 m/s above; ≤ 400.0 Pa/m; steel ε 0.045 mm; supply + returnASHRAE Fundamentals ch. 22
Equipment losseschiller 60 kPa, coil 40 kPa, cv 30 kPa, strainer 15 kPa, other 20 kPa = 165 kPaproject / vendor
Expansionsystem volume ≈ 12 L/kW → 2520 L; tank 144.0 L (2 % expansion, 35 % acceptance)ASHRAE Systems ch. 13

2. Duct network

650 × 350 · 1100 L/s · 4.84 m/s12 m · Δp 12.6 Pa · Σ 12.6 Pa500 × 300 · 600 L/s · 4.0 m/s10 m · Δp 9.8 Pa · Σ 22.4 Pa500 × 300 · 500 L/s · 3.33 m/s15 m · Δp 10.1 Pa · Σ 22.7 Pa450 × 250 · 300 L/s · 2.67 m/s4 m · Δp 6.3 Pa · Σ 28.7 Pa450 × 250 · 300 L/s · 2.67 m/s6 m · Δp 6 Pa · Σ 28.4 Pa400 × 200 · 250 L/s · 3.12 m/s5 m · Δp 8.2 Pa · Σ 30.9 Pa400 × 200 · 250 L/s · 3.12 m/s8 m · Δp 12.3 Pa · Σ 35 PaD1D2B1D3D4B2M1AHU-1red = index run (fan static governs) · line weight ∝ flow
FromToClassL/sCFMSize mmDe mmv m/sv maxPa/mL mCFittings PaΔp PaΣ PaGaugeSheet m²Check
AHU-1M1main1100.02331650 × 3505154.848.00.5612.00.425.912.612.60.80 mm (22 g)27.6PASS
M1B1branch600.01271500 × 3004204.08.00.510.00.54.89.822.40.80 mm (22 g)18.4PASS
M1B2branch500.01060500 × 3004203.338.00.3515.00.724.810.122.70.80 mm (22 g)27.6PASS
B1D1runout300.0636450 × 2503632.674.00.284.01.225.26.328.70.80 mm (22 g)6.44PASS
B1D2runout300.0636450 × 2503632.674.00.286.01.04.36.028.40.80 mm (22 g)9.66PASS
B2D3runout250.0530400 × 2003053.124.00.485.01.05.98.230.90.80 mm (22 g)6.9PASS
B2D4runout250.0530400 × 2003053.124.00.488.01.448.412.335.00.80 mm (22 g)11.04PASS

Index run: M1 → B2 → D4 = 35.0 Pa; fan external static = index + components = 510 Pa; fan power ≈ Q·Δp/η = 0.86 kW at η 0.65. Sheet 107.6 m² (0.80 mm (22 g): 107.6 m²), insulation 105.6 m². * = size fixed by the user.

Pressure profile along the index run

3931241680AHU-1→M112 m · 13M1→B215 m · 10B2→D48 m · 12Σ 13Σ 23Σ 35frictionfittingscumulative loss from the AHU (Pa)Pressure loss (Pa)

Fan static stack-up

Index run — duct friction16Index run — fittings19AHU / component: filter150AHU / component: coil200AHU / component: diffuser25AHU / component: louvre50AHU / component: other50Fan external static510 Paeach bar starts where the previous one ends — the red bar is the sum (Pa)

3. Duct construction & fire safety (NBCS 2026)

FromToSize mmStatic PaClass (Table 17)GaugeSupport tableAngle mmRod Ø mmSupports nosFire crossingsFire dampersFire-rated duct
AHU-1M1650 × 350110Low0.80 mm (22 g)Table 4040 × 40 × 58501—
M1B1500 × 30097Low0.80 mm (22 g)Table 4040 × 40 × 58500—
M1B2500 × 30097Low0.80 mm (22 g)Table 4040 × 40 × 58700—
B1D1450 × 25088Low0.80 mm (22 g)Table 4040 × 40 × 58200—
B1D2450 × 25088Low0.80 mm (22 g)Table 4040 × 40 × 58300—
B2D3400 × 20087Low0.80 mm (22 g)Table 4040 × 40 × 58300—
B2D4400 × 20087Low0.80 mm (22 g)Table 4040 × 40 × 58400—

Static at each section inlet = duct static at the AHU discharge − losses upstream; class per Table 17 (Low ≤ +500 Pa, Medium ≤ +1000 Pa, High ≤ +2500 Pa). Supports per Tables 40 / 41 (cl. 17.3.11.1), spacing ≤ 2 400 mm; vibration isolation ≥ 6 mm between duct and angle; supports independent of the false ceiling (cl. 8 e). Fire dampers (Part F 3.5.7.4) at every fire-separation wall, vertical-shaft entry and floor crossing and at the supply / return inlet of each compartment; motorised / fusible link, accessible, integrated with the fire alarm panel, manual operation provided. Ducts serving fire-safety operation keep no damper but need 120 min fire-rated ductwork (3.5.7.3.3). Ducts must not pass through exits / exit passageways; exits and lift lobbies are not return-air paths (3.5.7.3.1); inspection panels for cleaning and damper access (3.5.7.3.6).

4. Chilled-water network

80 NB · 9.11 L/s · 1.77 m/s20 m · Δp 18463 Pa · Σ 18463 Pa80 NB · 9.11 L/s · 1.77 m/s30 m · Δp 24866 Pa · Σ 43329 Pa65 NB · 5.21 L/s · 1.4 m/s15 m · Δp 21803 Pa · Σ 65132 Pa65 NB · 3.91 L/s · 1.05 m/s20 m · Δp 14190 Pa · Σ 57519 PaAHU-1AHU-2R1HDRCHILLERred = index run (pump head governs) · line weight ∝ flow
FromTokWTRL/sNBID mmv m/sv maxPa/mL mKFittings PaΔp (S+R) PaΣ PaInsul mmCheck
CHILLERHDR210.059.79.118080.91.772.438320.01.01571184631846340PASS
HDRR1210.059.79.118080.91.772.438330.00.6943248664332940PASS
R1AHU-1120.034.15.216568.91.42.429815.06.66437218036513240PASS
R1AHU-290.025.63.916568.91.052.417420.06.63621141905751940PASS

Index run: HDR → R1 → AHU-1; pump head = 65.1 kPa piping + 165 kPa equipment = 230 kPa = 23.5 m; pump power ≈ 3.0 kW at η 0.7. Pipe lengths (supply + return): 65 NB 70.0 m, 80 NB 100.0 m.

Pressure profile along the index run

72.958.443.829.214.60.0CHILLER→HDR20 m · 18.5HDR→R130 m · 24.9R1→AHU-115 m · 21.8Σ 18.5Σ 43.3Σ 65.1friction (supply + return)fittings (supply + return)cumulative loss from the pump (kPa)Pressure loss (kPa)

Pump head stack-up

Index run — pipe friction (S + R)47.2Index run — fittings (S + R)17.9Equipment: chiller60.0Equipment: coil40.0Equipment: cv30.0Equipment: strainer15.0Equipment: other20.0Pump head230.1 kPaeach bar starts where the previous one ends — the red bar is the sum (kPa)

Pump and system curves

440353265178911013duty 9 L/s @ 23.5 mFlow (L/s)Head (m)— pump curve- - system curve

Closed loop: system curve H = Hd·(Q/Qd)² through the duty point. The pump curve is indicative (shut-off ≈ 125 % of the duty head) — replace it with the selected pump's catalogue curve.

5. Checks

CheckResult
Velocity within NBCS Table 18 limits (General offices: main 8 / branch 8 / run-out 4 m/s)PASS
Friction ≤ 1.5 × target 0.8 Pa/m (auto-sized sections)PASS
Fan external static 510 Pa (index run 35.0 Pa + components 475 Pa)PASS
Pressure class (Table 17): duct static at the AHU 110 Pa → Low class; specified Low (≤ +500 Pa)PASS
Fire dampers (Part F 3.5.7.4.1): 1 at the compartment inlet; no fire-wall / floor / shaft crossing entered — confirm the route crosses nonePASS
Duct insulation Mineral / glass wool, FSK faced — non-combustible (Part F 3.5.7.3.5)PASS
AHU smoke-sensitive device to stop the AHU / close dampers (Part F 3.5.7.2.1): 1 no.PASS
Velocity within limits on every sectionPASS
Friction ≤ 400.0 Pa/m (auto-sized)PASS
Pump head 230 kPa = 23.5 m (index 65.1 kPa piping + 165 kPa equipment)PASS

6. Bill of quantities

ItemQtyUnit
GI sheet duct 0.80 mm (22 g)107.6m²
Duct insulation — Mineral / glass wool, FSK faced, 25 mm105.6m²
Duct length60.0m
Duct support set — Table 40: angle 40 × 40 × 5 + 2 × Ø8 mm rods at ≤ 2.4 m (NBCS Part D Sec 3 Tables 40 / 41)29nos
Fire damper 650 × 350 mm, motorised / fusible link, FAS-interlocked, with sleeve and access door (Part F 3.5.7.4)1nos
Duct smoke detector at the AHU, interlocked to stop the AHU and with the fire alarm panel (Part F 3.5.7.2.1)1nos
MS pipe 65 NB (supply + return)70.0m
MS pipe 80 NB (supply + return)100.0m
Expansion tank144.0L

7. Worked examples — from this project

Worked from this project’s own inputs and results — each value can be traced to the schedules above.

Duct section AHU-1 → M1 (main, 650 × 350 mm)
the section carrying the largest airflow in the duct network
Given: Length 12 m · Fittings C 0.42 · Air ρ 1.2 kg/m³, μ 1.8×10⁻⁵ Pa·s, ε 0.09 mm
1. Airflow: Q = Σ flows of the sections below = 600 + 500 = 1100 L/s (2331 CFM)
2. Velocity limit (main): NBCS Table 18 — lower of noise-controlled and friction-controlled main = General offices: min(8, 10) = 8 m/s (Part D Sec 3 cl. 8)
3. Round size: smallest D (10 mm steps) with Δp/m ≤ 0.8 Pa/m and v ≤ 8 m/s (main), rounded up to 50 mm = at D 500 mm: Δp/m 0.65 Pa/m, v 5.60 m/s = 500 mm
4. Rectangular equivalent: w × h (50 mm steps, w/h ≤ 4) with De ≥ D = D = 500 mm = 650 × 350 mm
5. Equivalent diameter: De = 1.3·(w·h)0.625 / (w + h)0.25 = 1.3 · (650 · 350)0.625 / (650 + 350)0.25 = 515 mm (engine 515 mm)
6. Velocity: v = Q / (w·h) = 1.1 / (0.65 × 0.35) = 4.84 m/s (engine 4.84 m/s)
7. Reynolds number: Re = ρ·vDe·De / μ, vDe = Q / (π·De²/4) = 1.2 · 5.27 · 0.515 / 1.8×10⁻⁵ = 181 199
8. Friction factor: 1/√f = −2·log10(ε/3.7De + 2.51/(Re·√f)) = ε/De = 0.00017, iterated (Colebrook) = 0.0172
9. Friction rate: Δp/m = f·ρ·vDe² / (2·De) = 0.0172 · 1.2 · 5.27² / (2 · 0.515) = 0.56 Pa/m (engine 0.56 Pa/m)
10. Fitting loss: Δpfit = C·ρ·v²/2 = 0.42 · 1.2 · 4.84² / 2 = 5.9 Pa (C: elbow 0.22, tee 0.5, damper 0.2, transition 0.1, fire damper 0.2 × 1; engine 5.9 Pa)
11. Section loss: Δp = Δp/m · L + Δpfit = 0.556 · 12 + 5.9 = 12.6 Pa (engine 12.6 Pa)
12. Velocity: v ≤ vmax (main) → 4.84 ≤ 8 m/s PASS
13. Friction: Δp/m ≤ 1.5 × target → 0.56 ≤ 1.20 Pa/m PASS
Index run M1 → B2 → D4 → fan external static
the terminal with the highest cumulative pressure loss governs the fan
1. Index run loss: Σ Δp along the run = 12.6 + 10.1 + 12.3 = 35 Pa
2. AHU components: Σ component losses = 150 + 200 + 25 + 50 + 50 = 475 Pa (filter 150, coil 200, diffuser 25, louvre 50, other 50)
3. Fan external static: SP = index run + components = 35 + 475 = 510 Pa
4. Fan power: P = Q·SP / η = 1.1 · 510 / 0.65 / 1000 = 0.86 kW
5. Index terminal: highest Σ Δp of all terminals → D4 35 Pa ≥ D1 28.7, D2 28.4, D3 30.9 PASS
Construction & fire safety — section AHU-1 → M1 (650 × 350 mm)
NBCS 2026 Table 17 class, Tables 40 / 41 supports and the Part F fire-damper count
1. Duct static at the AHU: P0 = index run + diffuser + other = 35 + 25 + 50 = 110 Pa
2. Static at the section inlet: P = P0 − Σ Δp upstream = 110 − 0 = 110 Pa (Table 17 → Low class)
3. Supports: n = ⌈L / 2.4 m⌉ = ⌈12 / 2.4⌉ = 5 nos (Table 40 (larger side 650 mm, static ≤ 750 Pa): angle 40 × 40 × 5, rod Ø8 mm)
4. Fire dampers: N = fire-wall / floor / shaft crossings + compartment inlets = 0 + 1 = 1 nos (Part F 3.5.7.3.3 / 3.5.7.4.1)
5. Pressure class: required ≤ specified → Low ≤ Low PASS
CHW pipe CHILLER → HDR (80 NB)
the pipe section carrying the largest chilled-water flow
Given: Length 20 m (supply + return counted) · Fittings K 1 · Water ρ 1000 kg/m³, μ 1.0×10⁻³ Pa·s, steel ε 0.045 mm
1. Cooling load: Σ loads below = 210 = 210 kW (59.7 TR)
2. Water flow: Q = kW / (cp·ΔT) = 210 / (4.19 × 5.5) = 9.11 L/s (engine 9.11 L/s)
3. Next smaller 65 NB (ID 68.9 mm): v ≤ 2.4 m/s and Δp/m ≤ 400 Pa/m → v 2.44 m/s, Δp/m 860 Pa/m CHECK (rejected — the engine takes the first size that meets both limits)
4. Velocity: v = Q / (π·ID²/4) = 0.0091 / (π × 0.0809² / 4) = 1.77 m/s (engine 1.77 m/s)
5. Reynolds number: Re = ρ·v·ID / μ = 1000 · 1.77 · 0.0809 / 10⁻³ = 143 418
6. Friction factor: Colebrook, ε/ID = 0.00056 = 0.0197
7. Friction rate: Δp/m = f·ρ·v² / (2·ID) = 0.0197 · 1000 · 1.77² / (2 · 0.0809) = 383 Pa/m (engine 383 Pa/m)
8. Fitting loss: Δpfit = K·ρ·v²/2 = 1 · 1000 · 1.77² / 2 = 1571 Pa (K: elbow 0.3, tee 0.6, gate 0.2, globe 6, check 2, butterfly 0.5)
9. Section loss (supply + return): Δp = 2·(Δp/m · L + Δpfit) = 2 · (383.0 · 20 + 1571) = 18 463 Pa (engine 18463 Pa)
10. Velocity: v ≤ 2.4 m/s (> 50 NB) → 1.77 m/s PASS
11. Friction: Δp/m ≤ 400 Pa/m → 383 Pa/m PASS
12. Index run piping: Σ Δp HDR → R1 → AHU-1 = 18463 + 24866 + 21803 = 65.1 kPa
13. Pump head: H = piping + equipment = 65.1 + 165 kPa = 230 kPa; ÷ 9.81 = 23.5 m (chiller 60, coil 40, cv 30, strainer 15, other 20 kPa)
14. Pump power: P = Q·H / η = 0.0091 · 230 / 0.7 = 3 kW

8. Standards applied

StandardUsed for
ASHRAE Fundamentals 2021 ch. 21 / 22Duct and pipe design — friction, fittings, velocity limits
SMACNA HVAC Duct Construction StandardsSheet gauge, reinforcement, hangers
ASHRAE 90.1Duct insulation, fan power
NBCS 2026 (SP 7:2026) Part D Sec 3cl. 8 Table 17 pressure classes, Table 18 max duct velocities, aspect ≤ 1:4; cl. 17.3.11.1 Tables 40 / 41 duct supports; 19.6 fire safety
NBCS 2026 Part F 3.5.7AHU smoke-sensitive devices (3.5.7.2.1), duct work (3.5.7.3), fire / smoke dampers (3.5.7.4), non-combustible insulation (3.5.7.3.5)
ISHRAE HVAC HandbookIndian practice — velocities, insulation
ECBC 2017Duct / pipe insulation, fan power limits
IS 655Metal air ducts
Prepared by
Checked by
Approved by