Duct & chilled-water network sizing
Sample project — Tower A · Indian regime · NBCS 2026 (SP 7:2026) · 7 duct + 4 pipe sections
Generated 28 Nov 2026 16:09 Equal-friction ducts, velocity / friction pipes, index run → fan static / pump head Project code SAMPLE
main 8 / branch 8 / run-out 4 m/s (NBCS 2026 Part D Sec 3 Table 18 — General offices, supply, main noise / friction-controlled)
NBCS 2026 Part D Sec 3 cl. 8, Table 18
Fittings
C × ρv²/2 with C: elbow 0.22, tee 0.5, damper 0.2, transition 0.1, outlet 1.0, fire damper 0.2
ASHRAE Fundamentals ch. 21 (typical)
AHU components
filter 150 Pa, coil 200 Pa, diffuser 25 Pa, louvre 50 Pa, other 50 Pa = 475 Pa
project
Sheet gauge
SMACNA rectangular, 500 Pa class
SMACNA HVAC Duct Construction Standards
Insulation
25 mm on supply ducts — Mineral / glass wool, FSK faced
ECBC 2017 / ASHRAE 90.1; Part F 3.5.7.3.5 non-combustible
Pressure class
duct static at the AHU 110 Pa → Low; specified Low (Low ≤ +500, Medium ≤ +1000, High ≤ +2500 Pa)
NBCS 2026 Part D Sec 3 Table 17
Duct supports
rectangular: angle + 2 rods at ≤ 2 400 mm; Table 40 up to 750 Pa, Table 41 above
NBCS 2026 Part D Sec 3 cl. 17.3.11.1, Tables 40 / 41
Fire safety
fire dampers at fire walls, shaft entries, floor crossings and the compartment inlet; 120 min duct where a crossing has no damper; AHU smoke-sensitive device; non-combustible insulation
NBCS 2026 Part F 3.5.7.2–3.5.7.4
Pipe sizing
ΔT 5.5 K; v ≤ 1.2 m/s ≤ 50 NB, ≤ 2.4 m/s above; ≤ 400.0 Pa/m; steel ε 0.045 mm; supply + return
system volume ≈ 12 L/kW → 2520 L; tank 144.0 L (2 % expansion, 35 % acceptance)
ASHRAE Systems ch. 13
2. Duct network
From
To
Class
L/s
CFM
Size mm
De mm
v m/s
v max
Pa/m
L m
C
Fittings Pa
Δp Pa
Σ Pa
Gauge
Sheet m²
Check
AHU-1
M1
main
1100.0
2331
650 × 350
515
4.84
8.0
0.56
12.0
0.42
5.9
12.6
12.6
0.80 mm (22 g)
27.6
PASS
M1
B1
branch
600.0
1271
500 × 300
420
4.0
8.0
0.5
10.0
0.5
4.8
9.8
22.4
0.80 mm (22 g)
18.4
PASS
M1
B2
branch
500.0
1060
500 × 300
420
3.33
8.0
0.35
15.0
0.72
4.8
10.1
22.7
0.80 mm (22 g)
27.6
PASS
B1
D1
runout
300.0
636
450 × 250
363
2.67
4.0
0.28
4.0
1.22
5.2
6.3
28.7
0.80 mm (22 g)
6.44
PASS
B1
D2
runout
300.0
636
450 × 250
363
2.67
4.0
0.28
6.0
1.0
4.3
6.0
28.4
0.80 mm (22 g)
9.66
PASS
B2
D3
runout
250.0
530
400 × 200
305
3.12
4.0
0.48
5.0
1.0
5.9
8.2
30.9
0.80 mm (22 g)
6.9
PASS
B2
D4
runout
250.0
530
400 × 200
305
3.12
4.0
0.48
8.0
1.44
8.4
12.3
35.0
0.80 mm (22 g)
11.04
PASS
Index run: M1 → B2 → D4 = 35.0 Pa; fan external static = index + components = 510 Pa; fan power ≈ Q·Δp/η = 0.86 kW at η 0.65. Sheet 107.6 m² (0.80 mm (22 g): 107.6 m²), insulation 105.6 m². * = size fixed by the user.
Pressure profile along the index run
Fan static stack-up
3. Duct construction & fire safety (NBCS 2026)
From
To
Size mm
Static Pa
Class (Table 17)
Gauge
Support table
Angle mm
Rod Ø mm
Supports nos
Fire crossings
Fire dampers
Fire-rated duct
AHU-1
M1
650 × 350
110
Low
0.80 mm (22 g)
Table 40
40 × 40 × 5
8
5
0
1
—
M1
B1
500 × 300
97
Low
0.80 mm (22 g)
Table 40
40 × 40 × 5
8
5
0
0
—
M1
B2
500 × 300
97
Low
0.80 mm (22 g)
Table 40
40 × 40 × 5
8
7
0
0
—
B1
D1
450 × 250
88
Low
0.80 mm (22 g)
Table 40
40 × 40 × 5
8
2
0
0
—
B1
D2
450 × 250
88
Low
0.80 mm (22 g)
Table 40
40 × 40 × 5
8
3
0
0
—
B2
D3
400 × 200
87
Low
0.80 mm (22 g)
Table 40
40 × 40 × 5
8
3
0
0
—
B2
D4
400 × 200
87
Low
0.80 mm (22 g)
Table 40
40 × 40 × 5
8
4
0
0
—
Static at each section inlet = duct static at the AHU discharge − losses upstream; class per Table 17 (Low ≤ +500 Pa, Medium ≤ +1000 Pa, High ≤ +2500 Pa). Supports per Tables 40 / 41 (cl. 17.3.11.1), spacing ≤ 2 400 mm; vibration isolation ≥ 6 mm between duct and angle; supports independent of the false ceiling (cl. 8 e). Fire dampers (Part F 3.5.7.4) at every fire-separation wall, vertical-shaft entry and floor crossing and at the supply / return inlet of each compartment; motorised / fusible link, accessible, integrated with the fire alarm panel, manual operation provided. Ducts serving fire-safety operation keep no damper but need 120 min fire-rated ductwork (3.5.7.3.3). Ducts must not pass through exits / exit passageways; exits and lift lobbies are not return-air paths (3.5.7.3.1); inspection panels for cleaning and damper access (3.5.7.3.6).
4. Chilled-water network
From
To
kW
TR
L/s
NB
ID mm
v m/s
v max
Pa/m
L m
K
Fittings Pa
Δp (S+R) Pa
Σ Pa
Insul mm
Check
CHILLER
HDR
210.0
59.7
9.11
80
80.9
1.77
2.4
383
20.0
1.0
1571
18463
18463
40
PASS
HDR
R1
210.0
59.7
9.11
80
80.9
1.77
2.4
383
30.0
0.6
943
24866
43329
40
PASS
R1
AHU-1
120.0
34.1
5.21
65
68.9
1.4
2.4
298
15.0
6.6
6437
21803
65132
40
PASS
R1
AHU-2
90.0
25.6
3.91
65
68.9
1.05
2.4
174
20.0
6.6
3621
14190
57519
40
PASS
Index run: HDR → R1 → AHU-1; pump head = 65.1 kPa piping + 165 kPa equipment = 230 kPa = 23.5 m; pump power ≈ 3.0 kW at η 0.7. Pipe lengths (supply + return): 65 NB 70.0 m, 80 NB 100.0 m.
Pressure profile along the index run
Pump head stack-up
Pump and system curves
Closed loop: system curve H = Hd·(Q/Qd)² through the duty point. The pump curve is indicative (shut-off ≈ 125 % of the duty head) — replace it with the selected pump's catalogue curve.
5. Checks
Check
Result
Velocity within NBCS Table 18 limits (General offices: main 8 / branch 8 / run-out 4 m/s)
Fan external static 510 Pa (index run 35.0 Pa + components 475 Pa)
PASS
Pressure class (Table 17): duct static at the AHU 110 Pa → Low class; specified Low (≤ +500 Pa)
PASS
Fire dampers (Part F 3.5.7.4.1): 1 at the compartment inlet; no fire-wall / floor / shaft crossing entered — confirm the route crosses none
PASS
Duct insulation Mineral / glass wool, FSK faced — non-combustible (Part F 3.5.7.3.5)
PASS
AHU smoke-sensitive device to stop the AHU / close dampers (Part F 3.5.7.2.1): 1 no.
PASS
Velocity within limits on every section
PASS
Friction ≤ 400.0 Pa/m (auto-sized)
PASS
Pump head 230 kPa = 23.5 m (index 65.1 kPa piping + 165 kPa equipment)
PASS
6. Bill of quantities
Item
Qty
Unit
GI sheet duct 0.80 mm (22 g)
107.6
m²
Duct insulation — Mineral / glass wool, FSK faced, 25 mm
105.6
m²
Duct length
60.0
m
Duct support set — Table 40: angle 40 × 40 × 5 + 2 × Ø8 mm rods at ≤ 2.4 m (NBCS Part D Sec 3 Tables 40 / 41)
29
nos
Fire damper 650 × 350 mm, motorised / fusible link, FAS-interlocked, with sleeve and access door (Part F 3.5.7.4)
1
nos
Duct smoke detector at the AHU, interlocked to stop the AHU and with the fire alarm panel (Part F 3.5.7.2.1)
1
nos
MS pipe 65 NB (supply + return)
70.0
m
MS pipe 80 NB (supply + return)
100.0
m
Expansion tank
144.0
L
7. Worked examples — from this project
Worked from this project’s own inputs and results — each value can be traced to the schedules above.
Duct section AHU-1 → M1 (main, 650 × 350 mm)
the section carrying the largest airflow in the duct network
Given: Length 12 m · Fittings C 0.42 · Air ρ 1.2 kg/m³, μ 1.8×10⁻⁵ Pa·s, ε 0.09 mm
1. Airflow: Q = Σ flows of the sections below = 600 + 500 = 1100 L/s(2331 CFM)
2. Velocity limit (main): NBCS Table 18 — lower of noise-controlled and friction-controlled main = General offices: min(8, 10) = 8 m/s(Part D Sec 3 cl. 8)
3. Round size: smallest D (10 mm steps) with Δp/m ≤ 0.8 Pa/m and v ≤ 8 m/s (main), rounded up to 50 mm = at D 500 mm: Δp/m 0.65 Pa/m, v 5.60 m/s = 500 mm
4. Rectangular equivalent: w × h (50 mm steps, w/h ≤ 4) with De ≥ D = D = 500 mm = 650 × 350 mm
3. Next smaller 65 NB (ID 68.9 mm): v ≤ 2.4 m/s and Δp/m ≤ 400 Pa/m → v 2.44 m/s, Δp/m 860 Pa/m CHECK(rejected — the engine takes the first size that meets both limits)
AHU smoke-sensitive devices (3.5.7.2.1), duct work (3.5.7.3), fire / smoke dampers (3.5.7.4), non-combustible insulation (3.5.7.3.5)
ISHRAE HVAC Handbook
Indian practice — velocities, insulation
ECBC 2017
Duct / pipe insulation, fan power limits
IS 655
Metal air ducts
Prepared by
Checked by
Approved by
Results are design aids computed by designlink calc (calc.designlink.in) and must be reviewed by a qualified engineer before issue. Ground levels marked "assumed" have no survey level within reach — verify.