SAMPLEOccupant load & means of egress (NBCS 2026 / NBC 2016 / IBC) — this is what your report looks like, generated from demo inputs.Generate yours →2 free designs every day for every signed-in account · 1 design free on sign-in · ₹99 + GST per design (report + Excel + DXF) · free for DesignLink companies
Report ready — use Print → Save as PDF (A4 landscape).
calc.designlink.in
Occupant load & means of egress (NBCS 2026 / NBC 2016 / IBC)
Sample project — Tower A · Structure & architecture
Generated 28 Nov 2026 16:09 Occupant load per occupancy, required exit width for stairs / level components & ramps / d… Project code SAMPLE
Occupants
212
Stair width required
2250 mm
Door width required
1500 mm
Exits required
2
Travel limit
60 m
1. Inputs
Group
Input
Value
Unit
Floor
Code
Indian — NBCS 2026 / NBC 2016
Floor
Indian code edition
NBCS 2026 (SP 7:2026) Part F
Floor
Occupancy
Business / office (E)
Floor
Floor area (net or gross as the occupancy factor states)
1500
m²
Floor
Declared occupants (0 = from area; NBC uses the larger)
0
Floor
Stair sizing
Floor by floor — largest floor served (NBCS 4.4.2.3 e)
Floor
Identical floors above served by the same stairs
0
Floor
Occupants of other floors served (comma-separated, optional)
Add mezzanine occupants that discharge through this floor (4.3). Commercial kitchens 9.3 m² net, dormitories of homes for the aged etc. 7.5 m² gross, car parking 30 m² per person (Table 2 Notes 2, 3, 5).
Exits as remote as possible: separation ≥ half the diagonal (unsprinklered) or one third (sprinklered) — NBCS Fig. 10.
Stair geometry: tread ≥ 250 mm residential / 300 mm others; riser ≤ 175 mm one/two-family, 150 mm others; ≤ 15 risers per flight (12 recommended); handrail projection ≤ 90 mm (4.4.2.4.3).
Local bye-laws and the fire authority's practice prevail — confirm before submission. Seating aisles, horizontal exits and refuge areas are not covered here.
6. Standards and references
NBC 2016 Part 4 — National Building Code — Fire and life safety: Occupant load (Table 5), exit width (Table 22), travel distance (Table 21), stair widths
NBCS 2026 (SP 7:2026) Part F — National Building Construction Standards — Fire and life safety: Means of egress (Tables 2–4, cl. 4.4.2), staircase / lobby / lift-well pressurisation (cl. 4.4.2.5, Table 5), emergency lighting (cl. 3.5.6), fire-fighting installations by occupancy (Tables 7A–7J), demand, pumps and duration (Tables 7K / 7M), mains (Table 8), hydrant pressure 3.5–7 bar (cl. 5.1.1 f), sprinklers (cl. 5.1.3), gaseous suppression (cl. 5.1.6 / 5.1.9)
IBC 2021 Chapter 10 — International Building Code — means of egress: Occupant load factors, egress width per occupant, travel distance
NFPA 101:2021 — Life Safety Code: Means of egress (international option)
Prepared by
Checked by
Approved by
Results are design aids computed by designlink calc (calc.designlink.in) and must be reviewed by a qualified engineer before issue. Ground levels marked "assumed" have no survey level within reach — verify.