SAMPLEElectrical layouts — lighting circuits, DB diagrams, cable tray — this is what your report looks like, generated from demo inputs.Generate yours →2 free designs every day for every signed-in account · 1 design free on sign-in · ₹99 + GST per design (report + Excel + DXF) · free for DesignLink companies
Report ready — use Print → Save as PDF (A4 landscape).
calc.designlink.in
Electrical layouts
Sample project — Tower A · Lighting circuits & wiring on the plan · DB wiring diagrams · cable-tray plan
Generated 28 Nov 2026 16:09 From the lighting model and the feeder schedule Project code SAMPLE
Floors
1
Luminaires
43
Circuits
6
Connected
1401 W
Wire
787.8 m
Conduit
227.8 m
1. Lighting circuits — basis
Item
Value
Regime
Indian — NBCS 2026 (SP 7:2026) Part D Sec 2
Circuit limits
800 W / 10 points per circuit (CPWD General Specifications for Electrical Works Part I; NBCS 2026 cl. 5.4.4.3 allows a dedicated lighting circuit 800 W or 20 points, so the 10-point packing is the stricter)
MCB
In ≥ Ib, 6 A up to 500 W, 10 A above — the same rule as the load estimate and the CAD circuits (NBCS 6.2: breaker matched to the circuit)
Wiring
1.5 mm² FRLS Cu in MS conduit, loop-in from the room switch
Emergency luminaires
separate circuits — NBCS Part F 3.5.6.1: source independent of the normal lighting (DG-backed), on within 5 s, ≥ 90 min, battery packs not in lieu of the DG
Phases
R-Y-B balanced on TPN DBs (largest circuit first)
Switches
at the room entrance nearest the DB
Common areas
own circuits — NBCS 5.4.4.4 (corridors, lobbies, stairs …); 3-wire individual + master control near the entrance of large halls
Window (daylight) zone
not split — set a window-zone width to group them — NBCS 5.4.4.5 / 5.4.4.6
Voltage drop
VD basis: split: 6 % to the final DB + 3 % final circuit — NBCS 2026 (SP 7:2026) Part D Sec 2 cl. 6.2 / 5.6 Note a; final-circuit limit per DB below (LDB-Ground ≤ 3 %): whole circuit current over the longest path, 2-core Cu mV/A/m — conservative
2. Ground — LDB-Ground
Circuit
Phase
Description
Points
W
Ib A
MCB
Wire
Wiring m
VD path m
VD %
Limit %
VD check
L1
R
Lighting — Corridor
6
90
0.43
6 A
1.5 mm²
31.0
31.3
0.17
3.0
PASS
L2
Y
Emergency lighting — Corridor
1
15
0.07
6 A
1.5 mm²
15.2
15.5
0.01
3.0
PASS
L3
R
Lighting — Office 2, Open office
10
360
1.74
6 A
1.5 mm²
42.1
29.2
0.64
3.0
PASS
L4
B
Emergency lighting — Office 2, Open office, Office 1
9
324
1.57
6 A
1.5 mm²
54.8
49.9
0.98
3.0
PASS
L5
Y
Lighting — Open office
10
360
1.74
6 A
1.5 mm²
53.9
65.8
1.44
3.0
PASS
L6
B
Lighting — Open office, Office 1
7
252
1.22
6 A
1.5 mm²
35.0
43.8
0.67
3.0
PASS
Final-circuit VD limit 3 % — DB → last point ≤ 3 % (split basis: the DB itself ≤ 6 % from the transformer) (NBCS 2026 (SP 7:2026) Part D Sec 2 cl. 6.2 / 5.6 Note a).
DB
Ways
Type
Connected
Ib
Incomer
RCCB
R / Y / B W
LDB-Ground
8
TPN
1401 W
2.2 A
32 A
40 A 30 mA
450 / 375 / 576
3. Lighting checks
Check
Result
Every lighting circuit ≤ 800 W and ≤ 10 points (CPWD packing; NBCS 2026 cl. 5.4.4.3 allows a dedicated lighting circuit 800 W or 20 points — stricter here)
PASS
Emergency luminaires on separate circuits, fed from a source independent of the normal lighting (DG-backed emergency supply), on within 5 s, ≥ 90 min; battery packs not in lieu of the DG — NBCS Part F 3.5.6.1 (b, f, g)
PASS
Phase unbalance ≤ 20 % on every TPN DB
PASS
LDB-Ground: final-circuit voltage drop ≤ 3 % — DB → last point ≤ 3 % (split basis: the DB itself ≤ 6 % from the transformer) (NBCS 2026 (SP 7:2026) Part D Sec 2 cl. 6.2 / 5.6 Note a) — worst L5 1.44 % over 65.8 m
PASS
Common-area lighting (corridors, lobbies, stairs) on separate circuits — NBCS 2026 cl. 5.4.4.4
PASS
4. Cable tray plan
Cables routed
1 / 1
Tray
39.5 m
Widest
100 mm
Segment
Length m
Cables
Runs
Need mm
Tray
Fill %
Supports
Cables
T1
11.5
1
1
53
CT 100×50
22
8
F1
T2
28.0
1
1
53
CT 100×50
22
19
F1
Cable
From
To
Size
Runs
OD mm
Tray length m
Total m
Routed
F1
MAIN LT PANEL
LDB-GF
4C X 16 Sq.mm, Cu
1
22.0
39.5
46.5
PASS
Sizing: single layer, fill ≤ 50 % of the width (IEC 61537 / NEMA VE 2 practice), 20 % spare, standard widths; depth from the largest cable; supports every 1.5 m.
5. Tray checks
Check
Result
Fill ≤ 50 % of the tray width (single layer) on every segment
PASS
Every cable routed on the tray network
PASS
No more than 3 tiers
PASS
6. Bill of quantities
Item
Qty
Unit
Luminaire — LED downlight 15 W (15 W)
7
nos
Luminaire — LED panel 600×600 36 W (36 W)
36
nos
Wire 1.5 mm² FRLS Cu (P+N+E)
787.8
m
MS conduit
227.8
m
Switch boards
4
nos
DB — 8-way TPN DB, 32 A incomer + 40 A RCCB
1
nos
Perforated tray 100 × 50 mm HDG
39.5
m
Supports / hangers
27
nos
7. Worked examples — from this project
Worked from this project’s own inputs and results — each value can be traced to the schedules above.
Given: Luminaires 10 nos at 36 W · Rule ≤ 800 W and ≤ 10 points per circuit (Indian regime) · Supply 230 V 1φ, pf 0.9
1. Circuit load: P = Σ luminaire watts = 10 × 36 = 360 W
2. Watts: P ≤ 800 W → 360 W PASS
3. Points: n ≤ 10 → 10 PASS
4. Design current: Ib = P / (230 · cosφ) = 360 / (230 · 0.9) = 1.74 A
5. MCB: next standard rating ≥ max(Ib, 6 A) = 1.74 A = 6 A SP (10 A minimum above 500 W — same rule as the load estimate and the CAD circuits)
6. Wire: 1.5 mm² Cu for a 6 A MCB → 1.5 mm² PASS
7. Wiring length: Σ (loop-in chain from the switch × 1.15 + 0.6 m per luminaire) = 42.1 m(2 room(s), nearest-neighbour chain on the plan; × 3 for phase + neutral + earth in the BOQ)
8. Voltage drop to the last point: ΔU = mV/A/m · Ib · L / 1000; ΔU % = ΔU / 230 = 29 · 1.74 · 29.2 / 1000 = 1.47 V = 0.64 %(L = home run + loop of the farthest room; whole current at the end (conservative))
9. Final-circuit VD: ΔU ≤ 3 % (NBCS 2026 (SP 7:2026) Part D Sec 2 cl. 6.2 / 5.6 Note a, split basis) → 0.64 % PASS
4. Supports: n = ⌈L / spacing⌉ = ⌈28.0 / 1.5⌉ = 19 nos
8. Standards applied
Standard
Used for
NBCS 2026 (SP 7:2026) Part D Sec 2
cl. 5.4.4.3 circuit limits, 5.4.4.4 common-area circuits, 5.4.4.5 / 5.4.4.6 window-zone controls, 6.2 / 5.6 Note a voltage drop (6 % to the final DB, 3 % DB → last point — split or total basis)
CPWD General Specifications for Electrical Works Part I (Internal) 2023
Points per circuit, 800 W limit, wiring, conduits, DBs
IS 732:2019
Code of practice for electrical wiring installations
IS 7098 / IS 1554
Cable dimensions
IEC 61537
Cable tray and ladder systems
Prepared by
Checked by
Approved by
Results are design aids computed by designlink calc (calc.designlink.in) and must be reviewed by a qualified engineer before issue. Ground levels marked "assumed" have no survey level within reach — verify.