calc.designlink.inExhaust fan size by air changes
Sample project — Tower A · HVAC
Generated 28 Nov 2026 16:13
Room volume × air changes per hour → exhaust airflow, number and sweep of wall / window ex…
Project code SAMPLE
Make-up opening
0.05 m² free
1. Inputs
| Group | Input | Value | Unit |
|---|
| Room | Length | 4 | m |
| Room | Width | 3 | m |
| Room | Height | 3 | m |
| Room | Use (air changes, typical) | Toilet / bathroom — 10 ACH | |
| Fans | Number of fans (0 = choose) | 0 | |
| Fans | Derating for louvre / short duct | 20 | % |
| Fans | Velocity through the make-up opening | 2.0 | m/s |
2. Results
Ventilation
| Item | Value | Unit | Note / basis |
|---|
| Volume | 36.0 | m³ | |
| Air changes | 10 | per h | Toilet / bathroom (typical) |
| Exhaust airflow | 360.0 | m³/h | |
| Per fan before derating | 360.0 | m³/h | |
| Per fan free-air (÷ derating) | 450.0 | m³/h | |
| Selected sweep | 200 | mm | ≈ 600 m³/h free air (typical maker data) |
3. Checks
| Check | Result | Note |
|---|
| 1 × 200 mm fan(s) ≥ 360 m³/h after derating | PASS | |
4. Worked example
Q = 4 × 3 × 3 × 10 = 360 m³/h; per fan 360 / 0.80 = 450 m³/h → 200 mm
5. Notes
- Air changes are typical design values — the building code or the client's standard may ask for more (e.g. kitchens with hoods are sized from the hood, not ACH).
- Keep the make-up air path (door undercut / grille) on the opposite side from the fan.
6. Standards and references
- ASHRAE 62.1-2022 — Ventilation for Acceptable Indoor Air Quality: Occupant density and outdoor air rates per space type
- NBC 2016 Part 8 Section 3 — Air-conditioning, heating and mechanical ventilation: Design conditions, ventilation rates, ducting and safety (India)
Prepared by
Checked by
Approved by
Results are design aids computed by designlink calc (calc.designlink.in) and must be reviewed by a qualified engineer before issue. Ground levels marked "assumed" have no survey level within reach — verify.