SAMPLE Gas suppression — Novec 1230 / FM-200 / inert / CO₂ — this is what your report looks like, generated from demo inputs. Generate yours → 2 free designs every day for every signed-in account · 1 design free on sign-in · ₹99 + GST per design (report + Excel + DXF) · free for DesignLink companies
Report ready — use Print → Save as PDF (A4 landscape).
Design Linkcalc.designlink.in

Gas suppression — Novec 1230 / FM-200 / inert / CO₂

Sample project — Tower A · Fire
Generated 28 Nov 2026 16:09
Agent quantity per NFPA 2001 (halocarbon W = V/s · C/(100−C); inert X = 2.303 · Vs/s · log…
Project code SAMPLE
Agent (required)
231.0 kg
Min. design conc.
4.7 %
Max. expected conc.
4.955 %
Containers
2 × 106 L
Nozzles
4
Discharge
8.5 / 10 s
Vent area
0.219 m²
Floor load
2045.8 kg/m²

1. Inputs

GroupInputValueUnit
HazardAgentFK-5-1-12 (Novec 1230)
HazardHazard classClass C — energised electrical (server / data / control rooms)
HazardMinimum design concentration (blank = NFPA 2001 minimum for the class)%
HazardExtra design factor on agent quantity1.0
HazardNormally occupiedTrue
HazardMinimum anticipated room temperature20.0°C
HazardMaximum anticipated room temperature35.0°C
HazardSite altitude220m
EnclosureRoom length12m
EnclosureRoom width8m
EnclosureRoom height (floor to ceiling)3.0m
EnclosureRaised-floor void (0 = none)0.6m
EnclosureCeiling void (0 = none or not protected)0m
EnclosureImpermeable fixed volume to deduct (columns, ducts)0m³
EnclosureEnclosure strength (pressure-relief design)250Pa
EnclosureInstalled pressure-relief vent free area (0 = none yet)0m²
EnclosureHold time10min
SystemCylinder size (blank = auto)L
SystemHalocarbon design fill density (blank = auto, fewest containers ≤ max fill)kg/L
SystemNozzle coverage (side of square)9.8m
SystemMax height per nozzle tier4.9m
SystemPipe run cylinders → farthest nozzle25m
SystemDischarge design target (blank = 8.5 s halocarbon / 50 s inert)s
System100 % connected reserve bankFalse

2. Results

Design basis

ItemValueUnitNote / basis
AgentFK-5-1-12 (Novec 1230)
Building codeNBCS 2026 (SP 7:2026) Part F 5.1.6 / 5.1.9, Tables 9 and 11gas system where water / foam unsuitable; agent design to the accepted standards F(25) — unchanged from NBC 2016 Part 4
StandardsNFPA 2001 (2022) Ch. 5 (5.4.2 design concentration, 5.5.1 / 5.5.2 quantity, 5.5.3.3 altitude), Annex A constants; ISO 14520-1; IS 15493:2021
Hazard classC — energised electrical
Minimum design concentration4.7%NFPA 2001 5.4.2 minimum for class C: 4.7 % (EC A 3.5 % (C = 3.5 × 1.35 = 4.7), heptane 4.5 % × 1.3 = 5.9; A 4.5 % listed)
Extra design factor on agent quantity1.01.0 = NFPA minimum
Concentration with the supplied quantity at 20 °C4.7%
Maximum expected concentration at 35 °C4.96%
NOAEL / LOAEL10 / 10%
Normally occupiedyes
Enclosure temperature range20 – 35°C
Specific volume s = k1 + k2·T0.07188 (min) / 0.07599 (max)m³/kg
Site elevation / atmospheric correction factor220 m / 0.974P/P₀ standard atmosphere (NFPA 2001 5.5.3.3 / ISO 14520-1 table)
Discharge time limit / design target10 / 8.5s
Hold time10.0min

Agent source

ItemValueUnitNote / basis
Container assembly106 L @ 25 bar, fill density 1.090 kg/L (max 1.44)
Number of main containers2
Number of reserve containers0
Agent per container115.5kg
Agent required / supplied (whole containers)231.00 / 231.00kg
Container empty / full weight130 / 246kg
Weight, all containers + agent491.0kg
Floor area per container0.12m²
Floor loading per container2045.85kg/m²
Bank footprint1.4 × 1.4m1 row(s), 0.45 m pitch, height 1.55 m; manifold with check valves, master + slave actuators
Locationfire-rated cylinder room or inside the hazard, 0–50 °C, ventilated, not in the egress path

Distribution and pipe (preliminary — listed hydraulic program governs)

ItemValueUnitNote / basis
Peak discharge rate at the target time27.18kg/s
Main pipeDN80 (Sch 40 black steel, ID 77.9 mm)run 25 m to the farthest nozzle
Estimated pipe volume (main + branches)81.56L
Agent in pipe56.49%≤ 80 % typical listing limit
Nozzle type360° radial in the field, 180° against walls; ≤ 9.8 m square, one tier per 4.9 m height
Balancing ruletee splits ≤ 2:1 by mass; agent before first tee ≥ 10 %; nozzle-to-nozzle ± 10 %; each enclosure must reach its adjusted quantity individually

Enclosure integrity and pressure relief

ItemValueUnitNote / basis
Enclosure strength (allowed pressure)250.0Pa
Negative-phase vent area required (cooling)0.219m²
Positive-phase vent area required (displacement)0.0342m²
Governing free vent area0.219m²Bernoulli, Cd 0.61, air 1.2 kg/m³
Installed vent areanot entered
Predicted enclosure pressuren/a
Door-fan testhold 10 min at the protected height; ELA within the listed limit; dampers, door closers, penetration seals

Detection, alarm and release (NFPA 72 / IS 2189)

ItemValueUnitNote / basis
Smoke detectors, cross-zoned (≤ 50 m² each)6zone A + zone B coincidence
Detectors in the floor void4
Release paneldual-zone coincidence, 30 s pre-discharge delay, abort (hold-to-abort), manual release at exits, maintenance lock-off
Alarms1st stage on single zone; 2nd stage (pulsing) on coincidence; 'gas discharged — do not enter' strobe outside; door status
InterlocksAHU / fresh air stop, fire dampers and pressure-relief damper, door closers, HVAC restart after purge
Signage / safetyat entrances; ODS (O₂) monitor for inert; SCBA for CO₂; egress within 1 min (halocarbon) / 3 min (inert)

Enclosure report

Encl.NameL × W × H (m)Gross m³Non-permeable m³Net m³Min conc %Conc (supplied) %Max conc %Min agent kgRequired agent kgNozzles
E1Room12 × 8 × 3288.00.0288.04.74.74.96192.5192.52
E2Raised-floor void12 × 8 × 0.657.6057.64.74.74.9638.538.52
Total345.60.0345.6231.0231.04

Nozzle schedule

NozzleEnclosureTypeCoverageAgent kgFlow kg/sSizeOrifice (indicative)
E1-N1Room360° radial6.00 × 8.00 m96.259.625DN50≈ 535 mm²
E1-N2Room360° radial6.00 × 8.00 m96.259.625DN50≈ 535 mm²
E2-N1Raised-floor void360° radial6.00 × 8.00 m19.251.925DN32≈ 107 mm²
E2-N2Raised-floor void360° radial6.00 × 8.00 m19.251.925DN32≈ 107 mm²

Review checklist (what an approving engineer verifies on the supplier's flow calculation)

#ItemThis designAsk the supplier for
1Calculation run statusn/a (sizing sheet)a report with no 'data changed after calculation' warning, same revision as the drawings
2Per-enclosure deliveryE1 192.5 kg; E2 38.5 kgpredicted delivered ≥ adjusted required for EVERY enclosure, not just the total
3Pressure relief0.219 m² required, installed not enteredinstalled vent area entered and predicted pressure ≤ enclosure strength
4Discharge timetarget 8.5 s vs limit 10 s≥ 0.5 s margin below the limit
5Site elevation220 m, factor 0.974actual site altitude in the run
6Concentration at max temperature4.96 % vs NOAEL 10 %≤ NOAEL for occupied spaces, egress time stated
7Floor loading2046 kg/m² per containerstructural confirmation of the cylinder location
8Reservenoneas the DBR standby clause
9Agent in pipe / before first tee≈ 56 %within the listing limits of the nozzle / valve family

Bill of quantities (preliminary)

ItemQtyUnit
FK-5-1-12 (Novec 1230) agent231.0kg
Container 106 L with valve, gauge, bracket, actuator2nos
Discharge nozzles4nos
Pipe DN80 main + branches (steel)45m
Manifold, check valves, flexible discharge hoses1set
Smoke detectors (cross-zoned)10nos
Release panel + abort + manual release1set
Sounders / strobes / signs4set
Pressure-relief damper (free area 0.22 m²)1nos
Door-fan integrity test1job

NFPA 2001 (2022) 5.4.2 minimum design concentrations (shared with the CAD tool)

AgentClass A %Class B %Class C %NOAEL %Discharge sBasis
FK-5-1-12 (Novec 1230)4.55.94.710.010.0EC A 3.5 % (C = 3.5 × 1.35 = 4.7), heptane 4.5 % × 1.3 = 5.9; A 4.5 % listed
HFC-227ea (FM-200)7.09.07.09.010.0EC A 5.2 % × 1.35 = 7.0 (C), FM-listed A 7.0, heptane 6.7–6.9 % × 1.3 = 9.0
HFC-125 (ECARO-25)8.011.39.07.510.0listing values
IG-541 (Inergen: N₂ 52 % · Ar 40 % · CO₂ 8 %)34.240.638.543.060.0EC A 28.5 % × 1.2 = 34.2, × 1.35 = 38.5 (C); heptane 31.25 % × 1.3 = 40.6
IG-55 (Argonite: N₂ 50 % · Ar 50 %)40.347.545.343.060.0EC A 33.6 % × 1.2 = 40.3, × 1.35 = 45.3 (C); heptane × 1.3 = 47.5
IG-100 (Nitrogen)40.347.545.343.060.0listing values
Carbon dioxide (NFPA 12, total flooding)34.034.050.0—60.0NFPA 12 flooding factors
ABABABCylinder bank 2 × 106 LDN80FK-5-1-12 (Novec 1230): room 12 × 8 × 3 m — nozzles (red +) with coverage squares, detectors zone A (amber) / B (violet), cylinder bank right. 231 kg.

3. Checks

CheckResultNote
Minimum design concentration 4.7 % vs NFPA 2001 (2022) 5.4.2 minimum 4.7 % for class C (EC × 1.35)PASSFK-5-1-12 (Novec 1230)
Design factor 1 on agent → concentration 4.70 % at 20 °C with the supplied quantityPASSquantity, not concentration, carries any extra margin (as listed flow programs do)
Maximum expected concentration 4.96 % at 35 °C ≤ NOAEL 10 % (normally occupied)PASS
Each enclosure gets its own quantity through its own nozzles: E1 192.5 kg / 2 noz; E2 38.5 kg / 2 nozPASSthe supplier's flow calculation must show predicted delivered ≥ adjusted required for every enclosure individually, not only in total
Discharge design target 8.5 s ≤ limit 10 s (margin 1.5 s)PASSsize pipe for the target so valve / fabrication tolerances stay inside the limit
Site altitude 220 m → atmospheric correction 0.974PASSenter the real site elevation; 0 m at an elevated site is conservative but unsubstantiated
Pressure relief: required free area 0.219 m² (negative 0.219 / positive 0.034) at 250 Pa; installed vent area not enteredCHECKenter the installed vent / damper free area or design one — unrelieved discharge pressure damages doors, ceilings and glazing
Floor loading under each container 2046 kg/m² (246 kg on 0.12 m²)PASS
Hold time 10 min (NFPA 2001 §5.6, ≥ 10 min) — door-fan integrity test requiredPASSseal penetrations, dampers close on pre-discharge
Reserve bank: none — confirm against the DBR standby-cylinder clausePASS
Agent in pipe ≈ 56 % of charge (preliminary DN80, 25 m run)PASSlisted flow programs limit agent-in-pipe (typically ≤ 80 %); shorten the run or enlarge the bank if exceeded

4. Worked example

Worked from this project’s own inputs and results — each value can be traced to the schedules above.

Novec 1230 — Room (288.0 m³)
largest protected enclosure of this design; the other enclosures follow the same steps
Given: Agent / class FK-5-1-12 (Novec 1230), class C · Net volume 288.00 m³ · Temperatures min 20 °C / max 35 °C · Altitude 220 m
1. Minimum design concentration: Cmin = EC × 1.35 (class C) = EC A 3.5 % (C = 3.5 × 1.35 = 4.7), heptane 4.5 % × 1.3 = 5.9; A 4.5 % listed = 4.7 % (NFPA 2001 5.4.2 / ISO 14520 listing value)
2. Specific volume at the minimum temperature: S = k1 + k2·T = 0.0664 + 0.000274 × 20 = 0.07188 m³/kg
3. Atmospheric correction: fa = (1 − 2.25577·10−5·h)5.25588 = h = 220 m = 0.9742 (NFPA 2001 5.5.3.3 / ISO 14520-1 table)
4. Agent for the enclosure: W = V / S × C / (100 − C) × fa = 288.00 / 0.07188 × 4.7 / 95.3 × 0.9742 = 192.5 kg (NFPA 2001 eq. 5.5.1)
5. All enclosures: ΣQ = 192.50 + 38.50 = 231 kg
6. Containers: n = ⌈Q / (size × fill)⌉ = ⌈231.00 / (106 × 1.44)⌉ → 2 × 106 L = 1.09 kg/L (fill 0.5 – 1.44 kg/L)
7. Concentration achieved (supplied quantity, min temperature): C = 100·Q·S/(V + Q·S) = Q = 231.00 kg, V = 345.60 m³, T = 20 °C = 4.7 %
8. Highest concentration at the maximum temperature: C(35 °C) ≤ NOAEL 10 % → 4.96 % PASS
9. Pressure-relief free area: A = Qv / (Cd·√(2·Δp/ρ)) = 2.727 / (0.61 × √(2 × 250 / 1.2)) = 0.219 m²
10. Room nozzles: ⌈L/cov⌉ × ⌈W/cov⌉ × ⌈H/htier⌉ = ⌈12/9.8⌉ × ⌈8/9.8⌉ × ⌈3/4.9⌉ = 2 × 1 × 1 = 2 nos (96.25 kg each, 9.625 kg/s; flow per nozzle ≤ 15 kg/s)
Code basis: NBCS 2026 Part F 5.1.6 / 5.1.9 — accepted standards IS 15493:2021 and ISO 14520 with NFPA 2001 (2022).

5. Notes

6. Standards and references

Prepared by
Checked by
Approved by