SAMPLEHot water — demand, storage, heater / heat pump, recirculation — this is what your report looks like, generated from demo inputs.Generate yours →2 free designs every day for every signed-in account · 1 design free on sign-in · ₹99 + GST per design (report + Excel + DXF) · free for DesignLink companies
Report ready — use Print → Save as PDF (A4 landscape).
calc.designlink.in
Hot water — demand, storage, heater / heat pump, recirculation
Sample project — Tower A · Plumbing / PHE
Generated 28 Nov 2026 16:09 Daily and peak-hour hot-water demand by occupancy (ASHRAE / ASPE practice) with the NBCS 2… Project code SAMPLE
Daily
9.0 m³
Storage
1080.0 L
Heater
29.3 kW
Units
2 × 15 kW
Recirc
12.9 L/min
Vessel (NBCS +20 %)
1296.0 L
1. Inputs
Group
Input
Value
Unit
Demand
Occupancy
Hotel (per guest)
Demand
Number of persons / beds / meals / showers
200
Demand
Litres per unit per day at 60 °C (0 = design-practice table)
0
L
Demand
Peak-hour fraction of daily (0 = table)
0
Demand
Storage temperature
60
°C
Demand
Cold water inlet
20
°C
Demand
Use temperature (info)
43
°C
Plant
Usable storage as fraction of peak-hour demand
0.8
Plant
Recovery period
3
h
Plant
Heat source
Air-source heat pump
Plant
Heat pump COP
3.5
Plant
Heaters in parallel
2
Recirculation
Recirculation loop length (flow + return)
300
m
Recirculation
Insulated pipe heat loss
15
W/m
Recirculation
Allowed temperature drop in loop
5
K
Recirculation
Hot-water pipe material
Copper (NBCS 4.8.6: ≤ 1.5 m/s)
NBCS 2026 checks
Longest draw-off pipe (dead leg) — largest internal Ø
20
mm
NBCS 2026 checks
Its length from the tap to the tank / circulation pipe
10
m
2. Results
Hot water system
Item
Value
Unit
Note / basis
Occupancy basis
Hotel (per guest): 45 L/unit/day at 60 °C, peak-hour fraction 0.15
design-practice value (ASHRAE / ASPE) — NBCS 2026 has no per-occupancy table
9. Network temperature: thot − ΔTloop ≥ 50 °C → 60 − 5 = 55 °C PASS(NBCS E1 4.2.3)
10. Dead leg: L ≤ Table 5 limit → Ø20 mm: 10 m vs 12 m PASS(NBCS E1 Table 5)
11. Storage balance (assumed hourly shape): usable storage stays > 0 over 24 h → lowest level 0 L; ≈ 6 L/day not covered — add storage or recovery (typical draw shape for the occupancy, scaled to the peak-hour fraction — see the figure)
5. Notes
Per-unit demands are design-practice values (ASHRAE HVAC Applications ch. 51 / ASPE Data Book 2): NBCS 2026 Part E Sec 1 gives no per-occupancy hot-water table. NBCS gives the dwelling rule (4.14.3: 50–75 L per bath tub, 25 L per shower / tap at 60 °C, vessel + 20 %) and the bathing allowance (Table 1: 35 LPCD, cold : hot 60 : 40).
Legionella: store at 60 °C (NBCS E1 4.14.2.2), keep ≥ 50 °C at all points of the network and cold ≤ 20 °C (4.2.3); mix to 41–43 °C at the fixtures (4.14.2.1) with TMVs.
IS 2065:1983 — Code of practice for water supply in buildings: Building water supply, risers, storage
ASHRAE Handbook — HVAC Applications ch. 51 — Service water heating: Hot-water demand, storage and recovery
IS 16368 (Parts 1–3) — Air-source heat pump water heaters: Heat-pump water heater performance
NBCS 2026 (SP 7:2026) Part E Sec 1 — National Building Construction Standards — Water supply: Per-capita demand, storage, fixture units and probable flow, pressures and zoning
ASPE Data Book vol. 2 — Plumbing systems — sanitary drainage: Fixture-unit method, stack and vent sizing (International)
ASHRAE 188-2021 — Legionellosis: risk management for building water systems: Water-management program
Prepared by
Checked by
Approved by
Results are design aids computed by designlink calc (calc.designlink.in) and must be reviewed by a qualified engineer before issue. Ground levels marked "assumed" have no survey level within reach — verify.