| Item | Value | Basis |
|---|---|---|
| Method | Carrier E20 ETD Tables 19/20 with design-condition correction; glass solar from ASHRAE clear-sky SHGF × SC × storage factor | Carrier System Design Manual Part 1 / ASHRAE Fundamentals ch. 18 & 28 |
| Design hour | peak search 08–18 h (each room at its own peak; block at the building peak) | months: summer 6, monsoon 8, winter 1 |
| Code edition | NBCS 2026 (SP 7:2026) Part D Sec 3 | NBCS 2026 (SP 7:2026) replaced NBC 2016 on 30 Apr 2026 |
| Outside conditions | summer 105.8 °F DB / 69.8 °F WB (57.2 gr/lb, h 34.45) · monsoon 87.8 / 81.0 (158.4 gr) · winter 48.7 / 43.7 · daily range 26.0 °F · altitude 1,400 ft · latitude 26.9 °N | Jaipur — NBCS 2026 D3 Table 3 (IS 7896:2023) Jaipur, Sl 60, PDF p. 1883 — 1 % cooling / 1 % evaporation / 99 % heating (comfort, cl. 3.5) |
| Inside conditions | per room type (75 °F / 50 % offices, 74 hotel, 72 server) — overridable per room; NBCS limits checked per room: cooling ≤ 26 °C, heating ≥ 18 °C, RH 30–70 % (toilet default capped at 26 °C); patient rooms 21–24 °C, RH ≤ 60 %; server rooms 18–27 °C, RH 8–60 % | NBCS D3 cl. 3.6, Table 27, cl. 13.4.4 |
| Occupancy, lighting, equipment, fresh air | ASHRAE 90.1-2019 lighting power density; fresh air V = Rp·P + Ra·A by NBCS D3 Table 7 (= ASHRAE 62.1 Table 6-1, 1 L/s = 2.119 cfm); hospital patient rooms ≥ 2 outdoor / ≥ 6 total ACH (NBCS D3 Table 27); ASHRAE Fundamentals equipment; Carrier Table 48 people gains | defaults per room type, overridable |
| Constructions | wall brick230_plaster (U 0.350), roof rcc150_screed, floor rcc150, partition brick115_plaster, glass single_clear (U 1.02, SC 0.95), shading none | typical Indian constructions / ECBC 2017 prescriptive values |
| Factors | bypass factor 0.15 · supply duct gain 10 % · return duct 5 % · safety S/L 0 / 0 % · ballast 1.25 · storage factor 0.85 · partition ΔT = (To − Ti) − 10.0 °F · ground ΔT 10.0 °F | Carrier E20 practice |
| Storey | Room | Type | Area ft² | Persons | Fresh air cfm | RSH Btu/h | RLH Btu/h | OA on coil | Grand total Btu/h | TR | Supply CFM | ADP °F | ft²/TR | CFM/ft² | Design | Heating Btu/h |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Ground | KITCHEN | Kitchen (commercial) | 275 | 5 | 70 | 20,489 | 2,331 | 737 | 24,736 | 2.06 | 1,175 | 59.4 | 133 | 4.28 | summer 16:00 | -3,156 |
| Ground | BEDROOM 2 | Residential bedroom | 275 | 3 | 31 | 7,462 | 298 | 699 | 8,881 | 0.74 | 387 | 54.6 | 371 | 1.41 | summer 17:00 | -5,974 |
| Ground | OFFICE | Office — open plan | 636 | 3 | 53 | 22,534 | 559 | 1,180 | 25,486 | 2.12 | 1,169 | 54.8 | 299 | 1.84 | summer 8:00 | -10,602 |
| Ground | BEDROOM 1 | Residential bedroom | 480 | 5 | 54 | 15,329 | 495 | 1,194 | 17,868 | 1.49 | 795 | 54.7 | 322 | 1.66 | summer 18:00 | -10,254 |
| Ground | LIVING | Residential living / dining | 356 | 4 | 41 | 9,900 | 398 | 918 | 11,776 | 0.98 | 514 | 54.6 | 362 | 1.44 | summer 15:00 | -5,517 |
| First (1/2) | KITCHEN | Kitchen (commercial) | 275 | 5 | 70 | 19,160 | 2,331 | 737 | 23,340 | 1.94 | 1,098 | 59.3 | 141 | 4.00 | summer 16:00 | -1,760 |
| First (1/2) | BEDROOM 2 | Residential bedroom | 275 | 3 | 31 | 6,132 | 298 | 699 | 7,485 | 0.62 | 318 | 54.5 | 440 | 1.16 | summer 17:00 | -4,578 |
| First (1/2) | OFFICE | Office — open plan | 636 | 3 | 53 | 19,455 | 559 | 1,180 | 22,254 | 1.85 | 1,009 | 54.8 | 343 | 1.59 | summer 8:00 | -7,369 |
| First (1/2) | BEDROOM 1 | Residential bedroom | 480 | 5 | 54 | 13,006 | 495 | 1,194 | 15,430 | 1.29 | 675 | 54.6 | 373 | 1.41 | summer 18:00 | -7,815 |
| First (1/2) | LIVING | Residential living / dining | 356 | 4 | 41 | 8,179 | 398 | 918 | 9,969 | 0.83 | 424 | 54.5 | 428 | 1.19 | summer 15:00 | -3,709 |
| First (2/2) | KITCHEN | Kitchen (commercial) | 275 | 5 | 70 | 24,983 | 2,331 | 737 | 29,454 | 2.45 | 1,432 | 59.6 | 112 | 5.21 | summer 16:00 | -5,851 |
| First (2/2) | BEDROOM 2 | Residential bedroom | 275 | 3 | 31 | 12,649 | 298 | 699 | 14,328 | 1.19 | 656 | 54.8 | 230 | 2.39 | summer 13:00 | -8,249 |
| First (2/2) | OFFICE | Office — open plan | 636 | 3 | 53 | 32,961 | 559 | 1,180 | 36,435 | 3.04 | 1,710 | 54.9 | 209 | 2.69 | summer 13:00 | -15,870 |
| First (2/2) | BEDROOM 1 | Residential bedroom | 480 | 5 | 54 | 23,943 | 495 | 1,194 | 26,914 | 2.24 | 1,242 | 54.9 | 214 | 2.59 | summer 14:00 | -14,229 |
| First (2/2) | LIVING | Residential living / dining | 356 | 4 | 41 | 16,797 | 398 | 918 | 19,018 | 1.58 | 871 | 54.8 | 224 | 2.45 | summer 14:00 | -8,463 |
| Storey | Rooms | Area ft² | TR | CFM | Fresh air cfm | ft²/TR |
|---|---|---|---|---|---|---|
| Ground | 5 | 2,021 | 7.40 | 4,039 | 250 | 273 |
| First (1/2) | 5 | 2,021 | 6.54 | 3,525 | 250 | 309 |
| First (2/2) | 5 | 2,021 | 10.51 | 5,912 | 250 | 192 |
Each bar is the room's grand total on its E20 sheet (design season), split into envelope, glass, internal, fresh-air and duct / safety parts.
Summer block load of all rooms together at each sun hour (peak search on — the block peak sets the plant).
Coil process of the largest room by the bypass-factor method: O and R mix to M at the fresh-air fraction of the supply air; the coil line M → ADP, leaving at S = ADP + BF·(M − ADP); S → R is the room ESHF line. Green box: NBCS D3 cl. 3.6 occupied-space limits.
| Check | Value | Limit / reference value | Result | Clause |
|---|---|---|---|---|
| Outside design conditions | used summer 105.8 °F DB / 69.8 WB, monsoon WB 81.0 °F | Table 3 Jaipur: summer 105.8 / 69.8 °F, monsoon WB 81.0 °F, winter 48.7 °F | PASS | NBCS D3 cl. 3.5 / Table 3 |
| All rooms | 45 checks pass, 0 to review | cooling ≤ 26 °C, heating ≥ 18 °C, RH 30–70 %; patient rooms 21–24 °C, RH ≤ 60 %, 2 / 6 ACH; server 18–27 °C, RH 8–60 % | PASS | NBCS D3 cl. 3.6, Table 27, cl. 13.4.4 |
| Item | Area / qty | U / factor | TD summer | Btu/h | TD monsoon | Btu/h | TD winter | Btu/h |
|---|---|---|---|---|---|---|---|---|
| N wall | 240.5 | 0.350 | 13.8 | 1,162 | -4.2 | -354 | -29.3 | -2,466 |
| W wall | 104.9 | 0.350 | 21.8 | 800 | 3.8 | 139 | -29.3 | -1,075 |
| Floor on ground | 274.7 | 0.440 | 10.0 | 1,209 | 10.0 | 1,209 | -10.0 | -1,209 |
| Partition (non-AC) | 233.7 | 0.510 | 17.8 | 2,121 | -0.2 | -24 | -20.0 | -2,384 |
| Glass conduction (all) | 29.1 | 1.020 | 27.8 | 824 | 9.8 | 291 | -29.3 | -869 |
| W glass solar | 29.1 | 0.950 | 181.0 | 4,997 | 186.7 | 5,155 | ||
| Lights | 274.7 | 1.363 | 3.4 | 1,277 | 3.4 | 1,277 | 3.4 | 1,277 |
| Equipment | 1,373.5 | 1.000 | 3.4 | 4,686 | 3.4 | 4,686 | 3.4 | 4,686 |
| People (sensible) | 5.0 | 246.667 | 1.0 | 1,233 | 1.0 | 1,233 | 1.0 | 1,418 |
| Ventilation (bypass) sensible | 70.5 | 0.162 | 27.8 | 317 | 9.8 | 112 | -29.3 | -334 |
| Space sensible | 18,627 | 13,724 | -955 | |||||
| Supply duct gain + safety | 1,863 | 1,372 | -96 | |||||
| Total room sensible (RSH) | 20,489 | 15,097 | -1,051 | |||||
| People (latent) | 5.0 | 503.333 | 1.0 | 2,517 | 1.0 | 2,517 | 1.0 | 2,265 |
| Ventilation (bypass) latent | 70.5 | 0.102 | -25.8 | -185 | 75.4 | 542 | -46.7 | -336 |
| Total room latent (RLH) | 2,331 | 3,059 | 1,929 | |||||
| Outside air on coil: cfm × (1 − BF) × 4.5 × Δh | 70.5 | 3.825 | 2.74 | 737 | 14.25 | 3,841 | -14.41 | -3,885 |
| Return duct gain | 1,178 | 1,100 | -150 | |||||
| Grand total heat | 24,736 | 23,096 | -3,156 | |||||
| TR | 2.06 | 1.92 | -0.26 | |||||
| SHR · ADP · selected supply temp · CFM | 0.898 · 59.4 °F · 59 °F · 1,175 cfm | 0.832 · 58.4 · 58 · 822 |
Check figures: 133 ft²/TR · 4.28 cfm/ft² · 570 cfm/TR · 90.0 Btu/h·ft² · 23.7 ACPH · ETD correction 9.8 °F
| Item | Area / qty | U / factor | TD summer | Btu/h | TD monsoon | Btu/h | TD winter | Btu/h |
|---|---|---|---|---|---|---|---|---|
| N wall | 240.5 | 0.350 | 17.8 | 1,498 | -0.2 | -17 | -26.3 | -2,214 |
| Floor on ground | 274.7 | 0.440 | 10.0 | 1,209 | 10.0 | 1,209 | -10.0 | -1,209 |
| Partition (non-AC) | 220.1 | 0.510 | 20.8 | 2,335 | 2.8 | 314 | -20.0 | -2,245 |
| Lights | 274.7 | 0.625 | 3.4 | 586 | 3.4 | 586 | 3.4 | 586 |
| Equipment | 82.4 | 1.000 | 3.4 | 281 | 3.4 | 281 | 3.4 | 281 |
| People (sensible) | 3.0 | 239.167 | 1.0 | 718 | 1.0 | 718 | 1.0 | 825 |
| Ventilation (bypass) sensible | 31.5 | 0.162 | 30.8 | 157 | 12.8 | 65 | -26.3 | -134 |
| Space sensible | 6,784 | 3,156 | -4,110 | |||||
| Supply duct gain + safety | 678 | 316 | -411 | |||||
| Total room sensible (RSH) | 7,462 | 3,472 | -4,521 | |||||
| People (latent) | 3.0 | 110.833 | 1.0 | 332 | 1.0 | 332 | 1.0 | 299 |
| Ventilation (bypass) latent | 31.5 | 0.102 | -10.9 | -35 | 90.3 | 290 | -31.8 | -102 |
| Total room latent (RLH) | 298 | 623 | 197 | |||||
| Outside air on coil: cfm × (1 − BF) × 4.5 × Δh | 31.5 | 3.825 | 5.80 | 699 | 17.32 | 2,086 | -11.34 | -1,366 |
| Return duct gain | 423 | 309 | -284 | |||||
| Grand total heat | 8,881 | 6,489 | -5,974 | |||||
| TR | 0.74 | 0.54 | -0.50 | |||||
| SHR · ADP · selected supply temp · CFM | 0.962 · 54.6 °F · 54 °F · 387 cfm | 0.848 · 52.5 · 52 · 164 |
Check figures: 371 ft²/TR · 1.41 cfm/ft² · 523 cfm/TR · 32.3 Btu/h·ft² · 7.8 ACPH · ETD correction 12.8 °F
| Item | Area / qty | U / factor | TD summer | Btu/h | TD monsoon | Btu/h | TD winter | Btu/h |
|---|---|---|---|---|---|---|---|---|
| N wall | 98.4 | 0.350 | 12.8 | 441 | -5.2 | -179 | -26.3 | -906 |
| E wall | 279.2 | 0.350 | 18.8 | 1,837 | 0.8 | 78 | -26.3 | -2,570 |
| S wall | 205.0 | 0.350 | 14.8 | 1,062 | -3.2 | -230 | -26.3 | -1,887 |
| Floor on ground | 636.0 | 0.440 | 10.0 | 2,799 | 10.0 | 2,799 | -10.0 | -2,799 |
| Partition (non-AC) | 278.8 | 0.510 | 20.8 | 2,958 | 2.8 | 398 | -20.0 | -2,844 |
| Glass conduction (all) | 32.3 | 1.020 | 30.8 | 1,014 | 12.8 | 422 | -26.3 | -866 |
| E glass solar | 32.3 | 0.950 | 181.0 | 5,552 | 186.7 | 5,727 | ||
| Lights | 636.0 | 0.762 | 3.4 | 1,655 | 3.4 | 1,655 | 3.4 | 1,655 |
| Equipment | 636.0 | 1.000 | 3.4 | 2,170 | 3.4 | 2,170 | 3.4 | 2,170 |
| People (sensible) | 3.0 | 244.167 | 1.0 | 732 | 1.0 | 732 | 1.0 | 842 |
| Ventilation (bypass) sensible | 53.2 | 0.162 | 30.8 | 265 | 12.8 | 110 | -26.3 | -227 |
| Space sensible | 20,485 | 13,683 | -7,430 | |||||
| Supply duct gain + safety | 2,049 | 1,368 | -743 | |||||
| Total room sensible (RSH) | 22,534 | 15,051 | -8,174 | |||||
| People (latent) | 3.0 | 205.833 | 1.0 | 618 | 1.0 | 618 | 1.0 | 556 |
| Ventilation (bypass) latent | 53.2 | 0.102 | -10.9 | -59 | 90.3 | 490 | -31.8 | -172 |
| Total room latent (RLH) | 559 | 1,107 | 383 | |||||
| Outside air on coil: cfm × (1 − BF) × 4.5 × Δh | 53.2 | 3.825 | 5.80 | 1,180 | 17.32 | 3,522 | -11.34 | -2,307 |
| Return duct gain | 1,214 | 984 | -505 | |||||
| Grand total heat | 25,486 | 20,665 | -10,602 | |||||
| TR | 2.12 | 1.72 | -0.88 | |||||
| SHR · ADP · selected supply temp · CFM | 0.976 · 54.8 °F · 54 °F · 1,169 cfm | 0.931 · 54.1 · 54 · 781 |
Check figures: 299 ft²/TR · 1.84 cfm/ft² · 550 cfm/TR · 40.1 Btu/h·ft² · 10.2 ACPH · ETD correction 12.8 °F
| Item | Area / qty | U / factor | TD summer | Btu/h | TD monsoon | Btu/h | TD winter | Btu/h |
|---|---|---|---|---|---|---|---|---|
| S wall | 251.8 | 0.350 | 30.8 | 2,714 | 12.8 | 1,128 | -26.3 | -2,318 |
| W wall | 205.0 | 0.350 | 32.8 | 2,353 | 11.8 | 846 | -26.3 | -1,887 |
| Floor on ground | 479.9 | 0.440 | 10.0 | 2,111 | 10.0 | 2,111 | -10.0 | -2,111 |
| Partition (non-AC) | 269.2 | 0.510 | 20.8 | 2,856 | 2.8 | 384 | -20.0 | -2,746 |
| Glass conduction (all) | 24.2 | 1.020 | 30.8 | 761 | 12.8 | 316 | -26.3 | -650 |
| S glass solar | 24.2 | 0.950 | 7.0 | 161 | 14.0 | 322 | ||
| Lights | 479.9 | 0.625 | 3.4 | 1,023 | 3.4 | 1,023 | 3.4 | 1,023 |
| Equipment | 144.0 | 1.000 | 3.4 | 491 | 3.4 | 491 | 3.4 | 491 |
| People (sensible) | 5.0 | 239.167 | 1.0 | 1,196 | 1.0 | 1,196 | 1.0 | 1,375 |
| Ventilation (bypass) sensible | 53.8 | 0.162 | 30.8 | 268 | 12.8 | 112 | -26.3 | -229 |
| Space sensible | 13,935 | 7,930 | -7,051 | |||||
| Supply duct gain + safety | 1,394 | 793 | -705 | |||||
| Total room sensible (RSH) | 15,329 | 8,723 | -7,756 | |||||
| People (latent) | 5.0 | 110.833 | 1.0 | 554 | 1.0 | 554 | 1.0 | 499 |
| Ventilation (bypass) latent | 53.8 | 0.102 | -10.9 | -60 | 90.3 | 496 | -31.8 | -174 |
| Total room latent (RLH) | 495 | 1,050 | 324 | |||||
| Outside air on coil: cfm × (1 − BF) × 4.5 × Δh | 53.8 | 3.825 | 5.80 | 1,194 | 17.32 | 3,564 | -11.34 | -2,334 |
| Return duct gain | 851 | 667 | -488 | |||||
| Grand total heat | 17,868 | 14,004 | -10,254 | |||||
| TR | 1.49 | 1.17 | -0.85 | |||||
| SHR · ADP · selected supply temp · CFM | 0.969 · 54.7 °F · 54 °F · 795 cfm | 0.893 · 53.4 · 53 · 432 |
Check figures: 322 ft²/TR · 1.66 cfm/ft² · 534 cfm/TR · 37.2 Btu/h·ft² · 9.2 ACPH · ETD correction 12.8 °F
| Item | Area / qty | U / factor | TD summer | Btu/h | TD monsoon | Btu/h | TD winter | Btu/h |
|---|---|---|---|---|---|---|---|---|
| S wall | 185.6 | 0.350 | 27.8 | 1,806 | 6.8 | 442 | -26.3 | -1,708 |
| Floor on ground | 355.6 | 0.440 | 10.0 | 1,565 | 10.0 | 1,565 | -10.0 | -1,565 |
| Partition (non-AC) | 184.6 | 0.510 | 20.8 | 1,958 | 2.8 | 264 | -20.0 | -1,883 |
| Glass conduction (all) | 19.4 | 1.020 | 30.8 | 609 | 12.8 | 253 | -26.3 | -520 |
| S glass solar | 19.4 | 0.950 | 29.0 | 535 | 55.1 | 1,014 | ||
| Lights | 355.6 | 0.625 | 3.4 | 758 | 3.4 | 758 | 3.4 | 758 |
| Equipment | 177.8 | 1.000 | 3.4 | 607 | 3.4 | 607 | 3.4 | 607 |
| People (sensible) | 4.0 | 239.167 | 1.0 | 957 | 1.0 | 957 | 1.0 | 1,100 |
| Ventilation (bypass) sensible | 41.3 | 0.162 | 30.8 | 206 | 12.8 | 86 | -26.3 | -176 |
| Space sensible | 9,000 | 5,945 | -3,387 | |||||
| Supply duct gain + safety | 900 | 595 | -339 | |||||
| Total room sensible (RSH) | 9,900 | 6,540 | -3,725 | |||||
| People (latent) | 4.0 | 110.833 | 1.0 | 443 | 1.0 | 443 | 1.0 | 399 |
| Ventilation (bypass) latent | 41.3 | 0.102 | -10.9 | -46 | 90.3 | 381 | -31.8 | -134 |
| Total room latent (RLH) | 398 | 824 | 265 | |||||
| Outside air on coil: cfm × (1 − BF) × 4.5 × Δh | 41.3 | 3.825 | 5.80 | 918 | 17.32 | 2,739 | -11.34 | -1,794 |
| Return duct gain | 561 | 505 | -263 | |||||
| Grand total heat | 11,776 | 10,608 | -5,517 | |||||
| TR | 0.98 | 0.88 | -0.46 | |||||
| SHR · ADP · selected supply temp · CFM | 0.961 · 54.6 °F · 54 °F · 514 cfm | 0.888 · 53.3 · 53 · 324 |
Check figures: 362 ft²/TR · 1.44 cfm/ft² · 523 cfm/TR · 33.1 Btu/h·ft² · 8.0 ACPH · ETD correction 12.8 °F
| Item | Area / qty | U / factor | TD summer | Btu/h | TD monsoon | Btu/h | TD winter | Btu/h |
|---|---|---|---|---|---|---|---|---|
| N wall | 240.5 | 0.350 | 13.8 | 1,162 | -4.2 | -354 | -29.3 | -2,466 |
| W wall | 104.9 | 0.350 | 21.8 | 800 | 3.8 | 139 | -29.3 | -1,075 |
| Partition (non-AC) | 233.7 | 0.510 | 17.8 | 2,121 | -0.2 | -24 | -20.0 | -2,384 |
| Glass conduction (all) | 29.1 | 1.020 | 27.8 | 824 | 9.8 | 291 | -29.3 | -869 |
| W glass solar | 29.1 | 0.950 | 181.0 | 4,997 | 186.7 | 5,155 | ||
| Lights | 274.7 | 1.363 | 3.4 | 1,277 | 3.4 | 1,277 | 3.4 | 1,277 |
| Equipment | 1,373.5 | 1.000 | 3.4 | 4,686 | 3.4 | 4,686 | 3.4 | 4,686 |
| People (sensible) | 5.0 | 246.667 | 1.0 | 1,233 | 1.0 | 1,233 | 1.0 | 1,418 |
| Ventilation (bypass) sensible | 70.5 | 0.162 | 27.8 | 317 | 9.8 | 112 | -29.3 | -334 |
| Space sensible | 17,418 | 12,516 | 254 | |||||
| Supply duct gain + safety | 1,742 | 1,252 | 25 | |||||
| Total room sensible (RSH) | 19,160 | 13,767 | 279 | |||||
| People (latent) | 5.0 | 503.333 | 1.0 | 2,517 | 1.0 | 2,517 | 1.0 | 2,265 |
| Ventilation (bypass) latent | 70.5 | 0.102 | -25.8 | -185 | 75.4 | 542 | -46.7 | -336 |
| Total room latent (RLH) | 2,331 | 3,059 | 1,929 | |||||
| Outside air on coil: cfm × (1 − BF) × 4.5 × Δh | 70.5 | 3.825 | 2.74 | 737 | 14.25 | 3,841 | -14.41 | -3,885 |
| Return duct gain | 1,111 | 1,033 | -84 | |||||
| Grand total heat | 23,340 | 21,700 | -1,760 | |||||
| TR | 1.94 | 1.81 | -0.15 | |||||
| SHR · ADP · selected supply temp · CFM | 0.892 · 59.3 °F · 59 °F · 1,098 cfm | 0.818 · 58.1 · 58 · 750 |
Check figures: 141 ft²/TR · 4.00 cfm/ft² · 565 cfm/TR · 85.0 Btu/h·ft² · 22.2 ACPH · ETD correction 9.8 °F
| Item | Area / qty | U / factor | TD summer | Btu/h | TD monsoon | Btu/h | TD winter | Btu/h |
|---|---|---|---|---|---|---|---|---|
| N wall | 240.5 | 0.350 | 17.8 | 1,498 | -0.2 | -17 | -26.3 | -2,214 |
| Partition (non-AC) | 220.1 | 0.510 | 20.8 | 2,335 | 2.8 | 314 | -20.0 | -2,245 |
| Lights | 274.7 | 0.625 | 3.4 | 586 | 3.4 | 586 | 3.4 | 586 |
| Equipment | 82.4 | 1.000 | 3.4 | 281 | 3.4 | 281 | 3.4 | 281 |
| People (sensible) | 3.0 | 239.167 | 1.0 | 718 | 1.0 | 718 | 1.0 | 825 |
| Ventilation (bypass) sensible | 31.5 | 0.162 | 30.8 | 157 | 12.8 | 65 | -26.3 | -134 |
| Space sensible | 5,575 | 1,947 | -2,901 | |||||
| Supply duct gain + safety | 557 | 195 | -290 | |||||
| Total room sensible (RSH) | 6,132 | 2,142 | -3,191 | |||||
| People (latent) | 3.0 | 110.833 | 1.0 | 332 | 1.0 | 332 | 1.0 | 299 |
| Ventilation (bypass) latent | 31.5 | 0.102 | -10.9 | -35 | 90.3 | 290 | -31.8 | -102 |
| Total room latent (RLH) | 298 | 623 | 197 | |||||
| Outside air on coil: cfm × (1 − BF) × 4.5 × Δh | 31.5 | 3.825 | 5.80 | 699 | 17.32 | 2,086 | -11.34 | -1,366 |
| Return duct gain | 356 | 243 | -218 | |||||
| Grand total heat | 7,485 | 5,093 | -4,578 | |||||
| TR | 0.62 | 0.42 | -0.38 | |||||
| SHR · ADP · selected supply temp · CFM | 0.954 · 54.5 °F · 54 °F · 318 cfm | 0.775 · 50.2 · 50 · 93 |
Check figures: 440 ft²/TR · 1.16 cfm/ft² · 510 cfm/TR · 27.2 Btu/h·ft² · 6.4 ACPH · ETD correction 12.8 °F
| Item | Area / qty | U / factor | TD summer | Btu/h | TD monsoon | Btu/h | TD winter | Btu/h |
|---|---|---|---|---|---|---|---|---|
| N wall | 98.4 | 0.350 | 12.8 | 441 | -5.2 | -179 | -26.3 | -906 |
| E wall | 279.2 | 0.350 | 18.8 | 1,837 | 0.8 | 78 | -26.3 | -2,570 |
| S wall | 205.0 | 0.350 | 14.8 | 1,062 | -3.2 | -230 | -26.3 | -1,887 |
| Partition (non-AC) | 278.8 | 0.510 | 20.8 | 2,958 | 2.8 | 398 | -20.0 | -2,844 |
| Glass conduction (all) | 32.3 | 1.020 | 30.8 | 1,014 | 12.8 | 422 | -26.3 | -866 |
| E glass solar | 32.3 | 0.950 | 181.0 | 5,552 | 186.7 | 5,727 | ||
| Lights | 636.0 | 0.762 | 3.4 | 1,655 | 3.4 | 1,655 | 3.4 | 1,655 |
| Equipment | 636.0 | 1.000 | 3.4 | 2,170 | 3.4 | 2,170 | 3.4 | 2,170 |
| People (sensible) | 3.0 | 244.167 | 1.0 | 732 | 1.0 | 732 | 1.0 | 842 |
| Ventilation (bypass) sensible | 53.2 | 0.162 | 30.8 | 265 | 12.8 | 110 | -26.3 | -227 |
| Space sensible | 17,687 | 10,884 | -4,632 | |||||
| Supply duct gain + safety | 1,769 | 1,088 | -463 | |||||
| Total room sensible (RSH) | 19,455 | 11,973 | -5,095 | |||||
| People (latent) | 3.0 | 205.833 | 1.0 | 618 | 1.0 | 618 | 1.0 | 556 |
| Ventilation (bypass) latent | 53.2 | 0.102 | -10.9 | -59 | 90.3 | 490 | -31.8 | -172 |
| Total room latent (RLH) | 559 | 1,107 | 383 | |||||
| Outside air on coil: cfm × (1 − BF) × 4.5 × Δh | 53.2 | 3.825 | 5.80 | 1,180 | 17.32 | 3,522 | -11.34 | -2,307 |
| Return duct gain | 1,060 | 830 | -351 | |||||
| Grand total heat | 22,254 | 17,432 | -7,369 | |||||
| TR | 1.85 | 1.45 | -0.61 | |||||
| SHR · ADP · selected supply temp · CFM | 0.972 · 54.8 °F · 54 °F · 1,009 cfm | 0.915 · 53.9 · 53 · 593 |
Check figures: 343 ft²/TR · 1.59 cfm/ft² · 544 cfm/TR · 35.0 Btu/h·ft² · 8.8 ACPH · ETD correction 12.8 °F
| Item | Area / qty | U / factor | TD summer | Btu/h | TD monsoon | Btu/h | TD winter | Btu/h |
|---|---|---|---|---|---|---|---|---|
| S wall | 251.8 | 0.350 | 30.8 | 2,714 | 12.8 | 1,128 | -26.3 | -2,318 |
| W wall | 205.0 | 0.350 | 32.8 | 2,353 | 11.8 | 846 | -26.3 | -1,887 |
| Partition (non-AC) | 269.2 | 0.510 | 20.8 | 2,856 | 2.8 | 384 | -20.0 | -2,746 |
| Glass conduction (all) | 24.2 | 1.020 | 30.8 | 761 | 12.8 | 316 | -26.3 | -650 |
| S glass solar | 24.2 | 0.950 | 7.0 | 161 | 14.0 | 322 | ||
| Lights | 479.9 | 0.625 | 3.4 | 1,023 | 3.4 | 1,023 | 3.4 | 1,023 |
| Equipment | 144.0 | 1.000 | 3.4 | 491 | 3.4 | 491 | 3.4 | 491 |
| People (sensible) | 5.0 | 239.167 | 1.0 | 1,196 | 1.0 | 1,196 | 1.0 | 1,375 |
| Ventilation (bypass) sensible | 53.8 | 0.162 | 30.8 | 268 | 12.8 | 112 | -26.3 | -229 |
| Space sensible | 11,824 | 5,819 | -4,939 | |||||
| Supply duct gain + safety | 1,182 | 582 | -494 | |||||
| Total room sensible (RSH) | 13,006 | 6,401 | -5,433 | |||||
| People (latent) | 5.0 | 110.833 | 1.0 | 554 | 1.0 | 554 | 1.0 | 499 |
| Ventilation (bypass) latent | 53.8 | 0.102 | -10.9 | -60 | 90.3 | 496 | -31.8 | -174 |
| Total room latent (RLH) | 495 | 1,050 | 324 | |||||
| Outside air on coil: cfm × (1 − BF) × 4.5 × Δh | 53.8 | 3.825 | 5.80 | 1,194 | 17.32 | 3,564 | -11.34 | -2,334 |
| Return duct gain | 735 | 551 | -372 | |||||
| Grand total heat | 15,430 | 11,565 | -7,815 | |||||
| TR | 1.29 | 0.96 | -0.65 | |||||
| SHR · ADP · selected supply temp · CFM | 0.963 · 54.6 °F · 54 °F · 675 cfm | 0.859 · 52.7 · 52 · 303 |
Check figures: 373 ft²/TR · 1.41 cfm/ft² · 525 cfm/TR · 32.2 Btu/h·ft² · 7.8 ACPH · ETD correction 12.8 °F
| Item | Area / qty | U / factor | TD summer | Btu/h | TD monsoon | Btu/h | TD winter | Btu/h |
|---|---|---|---|---|---|---|---|---|
| S wall | 185.6 | 0.350 | 27.8 | 1,806 | 6.8 | 442 | -26.3 | -1,708 |
| Partition (non-AC) | 184.6 | 0.510 | 20.8 | 1,958 | 2.8 | 264 | -20.0 | -1,883 |
| Glass conduction (all) | 19.4 | 1.020 | 30.8 | 609 | 12.8 | 253 | -26.3 | -520 |
| S glass solar | 19.4 | 0.950 | 29.0 | 535 | 55.1 | 1,014 | ||
| Lights | 355.6 | 0.625 | 3.4 | 758 | 3.4 | 758 | 3.4 | 758 |
| Equipment | 177.8 | 1.000 | 3.4 | 607 | 3.4 | 607 | 3.4 | 607 |
| People (sensible) | 4.0 | 239.167 | 1.0 | 957 | 1.0 | 957 | 1.0 | 1,100 |
| Ventilation (bypass) sensible | 41.3 | 0.162 | 30.8 | 206 | 12.8 | 86 | -26.3 | -176 |
| Space sensible | 7,435 | 4,380 | -1,822 | |||||
| Supply duct gain + safety | 744 | 438 | -182 | |||||
| Total room sensible (RSH) | 8,179 | 4,818 | -2,004 | |||||
| People (latent) | 4.0 | 110.833 | 1.0 | 443 | 1.0 | 443 | 1.0 | 399 |
| Ventilation (bypass) latent | 41.3 | 0.102 | -10.9 | -46 | 90.3 | 381 | -31.8 | -134 |
| Total room latent (RLH) | 398 | 824 | 265 | |||||
| Outside air on coil: cfm × (1 − BF) × 4.5 × Δh | 41.3 | 3.825 | 5.80 | 918 | 17.32 | 2,739 | -11.34 | -1,794 |
| Return duct gain | 475 | 419 | -177 | |||||
| Grand total heat | 9,969 | 8,800 | -3,709 | |||||
| TR | 0.83 | 0.73 | -0.31 | |||||
| SHR · ADP · selected supply temp · CFM | 0.954 · 54.5 °F · 54 °F · 424 cfm | 0.854 · 52.6 · 52 · 228 |
Check figures: 428 ft²/TR · 1.19 cfm/ft² · 511 cfm/TR · 28.0 Btu/h·ft² · 6.6 ACPH · ETD correction 12.8 °F
| Item | Area / qty | U / factor | TD summer | Btu/h | TD monsoon | Btu/h | TD winter | Btu/h |
|---|---|---|---|---|---|---|---|---|
| N wall | 240.5 | 0.350 | 13.8 | 1,162 | -4.2 | -354 | -29.3 | -2,466 |
| W wall | 104.9 | 0.350 | 21.8 | 800 | 3.8 | 139 | -29.3 | -1,075 |
| Roof (exposed) | 274.7 | 0.440 | 43.8 | 5,294 | 25.8 | 3,118 | -29.3 | -3,541 |
| Partition (non-AC) | 233.7 | 0.510 | 17.8 | 2,121 | -0.2 | -24 | -20.0 | -2,384 |
| Glass conduction (all) | 29.1 | 1.020 | 27.8 | 824 | 9.8 | 291 | -29.3 | -869 |
| W glass solar | 29.1 | 0.950 | 181.0 | 4,997 | 186.7 | 5,155 | ||
| Lights | 274.7 | 1.363 | 3.4 | 1,277 | 3.4 | 1,277 | 3.4 | 1,277 |
| Equipment | 1,373.5 | 1.000 | 3.4 | 4,686 | 3.4 | 4,686 | 3.4 | 4,686 |
| People (sensible) | 5.0 | 246.667 | 1.0 | 1,233 | 1.0 | 1,233 | 1.0 | 1,418 |
| Ventilation (bypass) sensible | 70.5 | 0.162 | 27.8 | 317 | 9.8 | 112 | -29.3 | -334 |
| Space sensible | 22,712 | 15,634 | -3,288 | |||||
| Supply duct gain + safety | 2,271 | 1,563 | -329 | |||||
| Total room sensible (RSH) | 24,983 | 17,197 | -3,617 | |||||
| People (latent) | 5.0 | 503.333 | 1.0 | 2,517 | 1.0 | 2,517 | 1.0 | 2,265 |
| Ventilation (bypass) latent | 70.5 | 0.102 | -25.8 | -185 | 75.4 | 542 | -46.7 | -336 |
| Total room latent (RLH) | 2,331 | 3,059 | 1,929 | |||||
| Outside air on coil: cfm × (1 − BF) × 4.5 × Δh | 70.5 | 3.825 | 2.74 | 737 | 14.25 | 3,841 | -14.41 | -3,885 |
| Return duct gain | 1,403 | 1,205 | -279 | |||||
| Grand total heat | 29,454 | 25,302 | -5,851 | |||||
| TR | 2.45 | 2.11 | -0.49 | |||||
| SHR · ADP · selected supply temp · CFM | 0.915 · 59.6 °F · 59 °F · 1,432 cfm | 0.849 · 58.7 · 58 · 937 |
Check figures: 112 ft²/TR · 5.21 cfm/ft² · 584 cfm/TR · 107.2 Btu/h·ft² · 28.9 ACPH · ETD correction 9.8 °F
| Item | Area / qty | U / factor | TD summer | Btu/h | TD monsoon | Btu/h | TD winter | Btu/h |
|---|---|---|---|---|---|---|---|---|
| N wall | 240.5 | 0.350 | 13.8 | 1,162 | -4.2 | -354 | -26.3 | -2,214 |
| Roof (exposed) | 274.7 | 0.440 | 51.8 | 6,261 | 33.8 | 4,085 | -26.3 | -3,179 |
| Partition (non-AC) | 220.1 | 0.510 | 20.8 | 2,335 | 2.8 | 314 | -20.0 | -2,245 |
| Lights | 274.7 | 0.625 | 3.4 | 586 | 3.4 | 586 | 3.4 | 586 |
| Equipment | 82.4 | 1.000 | 3.4 | 281 | 3.4 | 281 | 3.4 | 281 |
| People (sensible) | 3.0 | 239.167 | 1.0 | 718 | 1.0 | 718 | 1.0 | 825 |
| Ventilation (bypass) sensible | 31.5 | 0.162 | 30.8 | 157 | 12.8 | 65 | -26.3 | -134 |
| Space sensible | 11,499 | 5,696 | -6,080 | |||||
| Supply duct gain + safety | 1,150 | 570 | -608 | |||||
| Total room sensible (RSH) | 12,649 | 6,265 | -6,688 | |||||
| People (latent) | 3.0 | 110.833 | 1.0 | 332 | 1.0 | 332 | 1.0 | 299 |
| Ventilation (bypass) latent | 31.5 | 0.102 | -10.9 | -35 | 90.3 | 290 | -31.8 | -102 |
| Total room latent (RLH) | 298 | 623 | 197 | |||||
| Outside air on coil: cfm × (1 − BF) × 4.5 × Δh | 31.5 | 3.825 | 5.80 | 699 | 17.32 | 2,086 | -11.34 | -1,366 |
| Return duct gain | 682 | 449 | -393 | |||||
| Grand total heat | 14,328 | 9,422 | -8,249 | |||||
| TR | 1.19 | 0.79 | -0.69 | |||||
| SHR · ADP · selected supply temp · CFM | 0.977 · 54.8 °F · 54 °F · 656 cfm | 0.910 · 53.8 · 53 · 310 |
Check figures: 230 ft²/TR · 2.39 cfm/ft² · 550 cfm/TR · 52.2 Btu/h·ft² · 13.2 ACPH · ETD correction 12.8 °F
| Item | Area / qty | U / factor | TD summer | Btu/h | TD monsoon | Btu/h | TD winter | Btu/h |
|---|---|---|---|---|---|---|---|---|
| N wall | 98.4 | 0.350 | 13.8 | 475 | -4.2 | -145 | -26.3 | -906 |
| E wall | 279.2 | 0.350 | 37.8 | 3,694 | 19.8 | 1,935 | -26.3 | -2,570 |
| S wall | 205.0 | 0.350 | 20.8 | 1,492 | 2.8 | 201 | -26.3 | -1,887 |
| Roof (exposed) | 636.0 | 0.440 | 51.8 | 14,497 | 33.8 | 9,459 | -26.3 | -7,360 |
| Partition (non-AC) | 278.8 | 0.510 | 20.8 | 2,958 | 2.8 | 398 | -20.0 | -2,844 |
| Glass conduction (all) | 32.3 | 1.020 | 30.8 | 1,014 | 12.8 | 422 | -26.3 | -866 |
| E glass solar | 32.3 | 0.950 | 33.0 | 1,012 | 31.5 | 967 | ||
| Lights | 636.0 | 0.762 | 3.4 | 1,655 | 3.4 | 1,655 | 3.4 | 1,655 |
| Equipment | 636.0 | 1.000 | 3.4 | 2,170 | 3.4 | 2,170 | 3.4 | 2,170 |
| People (sensible) | 3.0 | 244.167 | 1.0 | 732 | 1.0 | 732 | 1.0 | 842 |
| Ventilation (bypass) sensible | 53.2 | 0.162 | 30.8 | 265 | 12.8 | 110 | -26.3 | -227 |
| Space sensible | 29,964 | 17,905 | -11,992 | |||||
| Supply duct gain + safety | 2,996 | 1,790 | -1,199 | |||||
| Total room sensible (RSH) | 32,961 | 19,695 | -13,191 | |||||
| People (latent) | 3.0 | 205.833 | 1.0 | 618 | 1.0 | 618 | 1.0 | 556 |
| Ventilation (bypass) latent | 53.2 | 0.102 | -10.9 | -59 | 90.3 | 490 | -31.8 | -172 |
| Total room latent (RLH) | 559 | 1,107 | 383 | |||||
| Outside air on coil: cfm × (1 − BF) × 4.5 × Δh | 53.2 | 3.825 | 5.80 | 1,180 | 17.32 | 3,522 | -11.34 | -2,307 |
| Return duct gain | 1,735 | 1,216 | -756 | |||||
| Grand total heat | 36,435 | 25,541 | -15,870 | |||||
| TR | 3.04 | 2.13 | -1.32 | |||||
| SHR · ADP · selected supply temp · CFM | 0.983 · 54.9 °F · 54 °F · 1,710 cfm | 0.947 · 54.4 · 54 · 1,022 |
Check figures: 209 ft²/TR · 2.69 cfm/ft² · 563 cfm/TR · 57.3 Btu/h·ft² · 14.9 ACPH · ETD correction 12.8 °F
| Item | Area / qty | U / factor | TD summer | Btu/h | TD monsoon | Btu/h | TD winter | Btu/h |
|---|---|---|---|---|---|---|---|---|
| S wall | 251.8 | 0.350 | 24.8 | 2,185 | 2.8 | 247 | -26.3 | -2,318 |
| W wall | 205.0 | 0.350 | 20.8 | 1,492 | 1.8 | 129 | -26.3 | -1,887 |
| Roof (exposed) | 479.9 | 0.440 | 50.8 | 10,726 | 33.8 | 7,136 | -26.3 | -5,553 |
| Partition (non-AC) | 269.2 | 0.510 | 20.8 | 2,856 | 2.8 | 384 | -20.0 | -2,746 |
| Glass conduction (all) | 24.2 | 1.020 | 30.8 | 761 | 12.8 | 316 | -26.3 | -650 |
| S glass solar | 24.2 | 0.950 | 33.4 | 768 | 68.2 | 1,569 | ||
| Lights | 479.9 | 0.625 | 3.4 | 1,023 | 3.4 | 1,023 | 3.4 | 1,023 |
| Equipment | 144.0 | 1.000 | 3.4 | 491 | 3.4 | 491 | 3.4 | 491 |
| People (sensible) | 5.0 | 239.167 | 1.0 | 1,196 | 1.0 | 1,196 | 1.0 | 1,375 |
| Ventilation (bypass) sensible | 53.8 | 0.162 | 30.8 | 268 | 12.8 | 112 | -26.3 | -229 |
| Space sensible | 21,767 | 12,604 | -10,492 | |||||
| Supply duct gain + safety | 2,177 | 1,260 | -1,049 | |||||
| Total room sensible (RSH) | 23,943 | 13,864 | -11,542 | |||||
| People (latent) | 5.0 | 110.833 | 1.0 | 554 | 1.0 | 554 | 1.0 | 499 |
| Ventilation (bypass) latent | 53.8 | 0.102 | -10.9 | -60 | 90.3 | 496 | -31.8 | -174 |
| Total room latent (RLH) | 495 | 1,050 | 324 | |||||
| Outside air on coil: cfm × (1 − BF) × 4.5 × Δh | 53.8 | 3.825 | 5.80 | 1,194 | 17.32 | 3,564 | -11.34 | -2,334 |
| Return duct gain | 1,282 | 924 | -678 | |||||
| Grand total heat | 26,914 | 19,401 | -14,229 | |||||
| TR | 2.24 | 1.62 | -1.19 | |||||
| SHR · ADP · selected supply temp · CFM | 0.980 · 54.9 °F · 54 °F · 1,242 cfm | 0.930 · 54.1 · 54 · 719 |
Check figures: 214 ft²/TR · 2.59 cfm/ft² · 554 cfm/TR · 56.1 Btu/h·ft² · 14.3 ACPH · ETD correction 12.8 °F
| Item | Area / qty | U / factor | TD summer | Btu/h | TD monsoon | Btu/h | TD winter | Btu/h |
|---|---|---|---|---|---|---|---|---|
| S wall | 185.6 | 0.350 | 24.8 | 1,611 | 2.8 | 182 | -26.3 | -1,708 |
| Roof (exposed) | 355.6 | 0.440 | 50.8 | 7,949 | 33.8 | 5,289 | -26.3 | -4,115 |
| Partition (non-AC) | 184.6 | 0.510 | 20.8 | 1,958 | 2.8 | 264 | -20.0 | -1,883 |
| Glass conduction (all) | 19.4 | 1.020 | 30.8 | 609 | 12.8 | 253 | -26.3 | -520 |
| S glass solar | 19.4 | 0.950 | 33.4 | 615 | 68.2 | 1,255 | ||
| Lights | 355.6 | 0.625 | 3.4 | 758 | 3.4 | 758 | 3.4 | 758 |
| Equipment | 177.8 | 1.000 | 3.4 | 607 | 3.4 | 607 | 3.4 | 607 |
| People (sensible) | 4.0 | 239.167 | 1.0 | 957 | 1.0 | 957 | 1.0 | 1,100 |
| Ventilation (bypass) sensible | 41.3 | 0.162 | 30.8 | 206 | 12.8 | 86 | -26.3 | -176 |
| Space sensible | 15,270 | 9,650 | -5,937 | |||||
| Supply duct gain + safety | 1,527 | 965 | -594 | |||||
| Total room sensible (RSH) | 16,797 | 10,615 | -6,531 | |||||
| People (latent) | 4.0 | 110.833 | 1.0 | 443 | 1.0 | 443 | 1.0 | 399 |
| Ventilation (bypass) latent | 41.3 | 0.102 | -10.9 | -46 | 90.3 | 381 | -31.8 | -134 |
| Total room latent (RLH) | 398 | 824 | 265 | |||||
| Outside air on coil: cfm × (1 − BF) × 4.5 × Δh | 41.3 | 3.825 | 5.80 | 918 | 17.32 | 2,739 | -11.34 | -1,794 |
| Return duct gain | 906 | 709 | -403 | |||||
| Grand total heat | 19,018 | 14,887 | -8,463 | |||||
| TR | 1.58 | 1.24 | -0.71 | |||||
| SHR · ADP · selected supply temp · CFM | 0.977 · 54.8 °F · 54 °F · 871 cfm | 0.928 · 54.1 · 54 · 551 |
Check figures: 224 ft²/TR · 2.45 cfm/ft² · 550 cfm/TR · 53.5 Btu/h·ft² · 13.6 ACPH · ETD correction 12.8 °F
Worked from this project’s own rooms — each value matches the room’s E20 sheet above (IP units, as on the sheet).
| Quantity | Formula | Reference |
|---|---|---|
| Wall / roof conduction | q = U · A_net · TD ; TD = ETD(orientation, weight, sun time) + (To − Ti) − 0.5·DR − 5 | Carrier Tables 19 / 20 / 20A |
| ASHRAE option | CLTD = (T̄_sa − Ti) + δ·(T_sa(t − lag) − T̄_sa) ; T_sa = To + α·E_t/h_o − ε·ΔR/h_o | ASHRAE Fundamentals ch. 18 (sol-air), mass-class lag / decrement |
| Glass | q = U·A·(To − Ti) + A · SC · SHGF · storage factor ; SHGF from clear-sky (A, B, C) and DSA glass t(θ), a(θ) | ASHRAE Fundamentals ch. 29 / 30 (1997); Carrier Table 15 basis |
| Partitions / ground | q = U·A·((To − Ti) − 10) ; ground floor q = U·A·10 | Carrier E20 |
| People | q_s = n · S(activity, room DB) ; q_l = n · L | Carrier Table 48 / ASHRAE ch. 18 Table 1 |
| Lights / equipment | q = W/ft² · A · ballast · 3.412 ; q = W · 3.412 | ASHRAE 90.1 / ECBC LPD |
| Fresh air | V = Rp·P + Ra·A ; patient rooms V ≥ 2 ACH, supply ≥ 6 ACH | NBCS D3 Table 7 / Table 27 |
| Ventilation | room: cfm·BF·1.08·ΔT (sensible), cfm·BF·0.68·Δgr (latent) ; coil: cfm·(1 − BF)·4.5·Δh | Carrier E20 (bypass factor method) |
| Supply air | SHR = RSH / (RSH + RLH) ; ADP from the ESHF line ; CFM = RSH / (1.08 · (Ti − T_sup) · (1 − BF)) | Carrier System Design Manual |
| Psychrometrics | Hyland-Wexler p_ws ; W = 0.622·p_w/(p − p_w) ; h = 0.24·T + W·(1061 + 0.444·T) ; p by altitude | ASHRAE Fundamentals ch. 1 |
Results are design aids computed by designlink calc (calc.designlink.in) and must be reviewed by a qualified engineer before issue. Ground levels marked "assumed" have no survey level within reach — verify.