SAMPLE Heat load — E20 sheet (Carrier / ASHRAE) — this is what your report looks like, generated from demo inputs. Generate yours → 2 free designs every day for every signed-in account · 1 design free on sign-in · ₹99 + GST per design (report + Excel + DXF) · free for DesignLink companies
Report ready — use Print → Save as PDF (A4 landscape).
Design Linkcalc.designlink.in

Cooling & heating load estimate — E20 method

Sample project — Tower A · Jaipur
Generated 28 Nov 2026 16:03
Carrier E20 ETD Tables 19/20 with design-condition correctio…
Project code SAMPLE
AC rooms
15
AC area
6,063 ft² (563 m²)
Total cooling
24.4 TR
kW refrigeration
86.0
Supply air
13,476 cfm
Fresh air
751 cfm
ft² / TR
248

1. Design basis

ItemValueBasis
MethodCarrier E20 ETD Tables 19/20 with design-condition correction; glass solar from ASHRAE clear-sky SHGF × SC × storage factorCarrier System Design Manual Part 1 / ASHRAE Fundamentals ch. 18 & 28
Design hourpeak search 08–18 h (each room at its own peak; block at the building peak)months: summer 6, monsoon 8, winter 1
Code editionNBCS 2026 (SP 7:2026) Part D Sec 3NBCS 2026 (SP 7:2026) replaced NBC 2016 on 30 Apr 2026
Outside conditionssummer 105.8 °F DB / 69.8 °F WB (57.2 gr/lb, h 34.45) · monsoon 87.8 / 81.0 (158.4 gr) · winter 48.7 / 43.7 · daily range 26.0 °F · altitude 1,400 ft · latitude 26.9 °NJaipur — NBCS 2026 D3 Table 3 (IS 7896:2023) Jaipur, Sl 60, PDF p. 1883 — 1 % cooling / 1 % evaporation / 99 % heating (comfort, cl. 3.5)
Inside conditionsper room type (75 °F / 50 % offices, 74 hotel, 72 server) — overridable per room; NBCS limits checked per room: cooling ≤ 26 °C, heating ≥ 18 °C, RH 30–70 % (toilet default capped at 26 °C); patient rooms 21–24 °C, RH ≤ 60 %; server rooms 18–27 °C, RH 8–60 %NBCS D3 cl. 3.6, Table 27, cl. 13.4.4
Occupancy, lighting, equipment, fresh airASHRAE 90.1-2019 lighting power density; fresh air V = Rp·P + Ra·A by NBCS D3 Table 7 (= ASHRAE 62.1 Table 6-1, 1 L/s = 2.119 cfm); hospital patient rooms ≥ 2 outdoor / ≥ 6 total ACH (NBCS D3 Table 27); ASHRAE Fundamentals equipment; Carrier Table 48 people gainsdefaults per room type, overridable
Constructionswall brick230_plaster (U 0.350), roof rcc150_screed, floor rcc150, partition brick115_plaster, glass single_clear (U 1.02, SC 0.95), shading nonetypical Indian constructions / ECBC 2017 prescriptive values
Factorsbypass factor 0.15 · supply duct gain 10 % · return duct 5 % · safety S/L 0 / 0 % · ballast 1.25 · storage factor 0.85 · partition ΔT = (To − Ti) − 10.0 °F · ground ΔT 10.0 °FCarrier E20 practice

2. Room summary (design condition of each room)

StoreyRoomTypeArea ft²PersonsFresh air cfmRSH Btu/hRLH Btu/hOA on coilGrand total Btu/hTRSupply CFMADP °Fft²/TRCFM/ft²DesignHeating Btu/h
GroundKITCHENKitchen (commercial)27557020,4892,33173724,7362.061,17559.41334.28summer 16:00-3,156
GroundBEDROOM 2Residential bedroom2753317,4622986998,8810.7438754.63711.41summer 17:00-5,974
GroundOFFICEOffice — open plan63635322,5345591,18025,4862.121,16954.82991.84summer 8:00-10,602
GroundBEDROOM 1Residential bedroom48055415,3294951,19417,8681.4979554.73221.66summer 18:00-10,254
GroundLIVINGResidential living / dining3564419,90039891811,7760.9851454.63621.44summer 15:00-5,517
First (1/2)KITCHENKitchen (commercial)27557019,1602,33173723,3401.941,09859.31414.00summer 16:00-1,760
First (1/2)BEDROOM 2Residential bedroom2753316,1322986997,4850.6231854.54401.16summer 17:00-4,578
First (1/2)OFFICEOffice — open plan63635319,4555591,18022,2541.851,00954.83431.59summer 8:00-7,369
First (1/2)BEDROOM 1Residential bedroom48055413,0064951,19415,4301.2967554.63731.41summer 18:00-7,815
First (1/2)LIVINGResidential living / dining3564418,1793989189,9690.8342454.54281.19summer 15:00-3,709
First (2/2)KITCHENKitchen (commercial)27557024,9832,33173729,4542.451,43259.61125.21summer 16:00-5,851
First (2/2)BEDROOM 2Residential bedroom27533112,64929869914,3281.1965654.82302.39summer 13:00-8,249
First (2/2)OFFICEOffice — open plan63635332,9615591,18036,4353.041,71054.92092.69summer 13:00-15,870
First (2/2)BEDROOM 1Residential bedroom48055423,9434951,19426,9142.241,24254.92142.59summer 14:00-14,229
First (2/2)LIVINGResidential living / dining35644116,79739891819,0181.5887154.82242.45summer 14:00-8,463

3. Storey totals

StoreyRoomsArea ft²TRCFMFresh air cfmft²/TR
Ground52,0217.404,039250273
First (1/2)52,0216.543,525250309
First (2/2)52,02110.515,912250192

4. Load breakdown and coil process

Cooling load by component — 15 largest rooms (design season, TR)Walls & doorsRoofFloor & partitionsGlass conductionGlass solarPeopleLightsEquipmentFresh air & infiltrationDuct gains & safety0123OFFICEOFFICE — Walls & doors: 0.47 TROFFICE — Roof: 1.21 TROFFICE — Floor & partitions: 0.25 TROFFICE — Glass conduction: 0.08 TROFFICE — Glass solar: 0.08 TROFFICE — People: 0.11 TROFFICE — Lights: 0.14 TROFFICE — Equipment: 0.18 TROFFICE — Fresh air & infiltration: 0.12 TROFFICE — Duct gains & safety: 0.39 TR3.04KITCHENKITCHEN — Walls & doors: 0.16 TRKITCHEN — Roof: 0.44 TRKITCHEN — Floor & partitions: 0.18 TRKITCHEN — Glass conduction: 0.07 TRKITCHEN — Glass solar: 0.42 TRKITCHEN — People: 0.31 TRKITCHEN — Lights: 0.11 TRKITCHEN — Equipment: 0.39 TRKITCHEN — Fresh air & infiltration: 0.07 TRKITCHEN — Duct gains & safety: 0.31 TR2.45BEDROOM 1BEDROOM 1 — Walls & doors: 0.31 TRBEDROOM 1 — Roof: 0.89 TRBEDROOM 1 — Floor & partitions: 0.24 TRBEDROOM 1 — Glass conduction: 0.06 TRBEDROOM 1 — Glass solar: 0.06 TRBEDROOM 1 — People: 0.15 TRBEDROOM 1 — Lights: 0.09 TRBEDROOM 1 — Equipment: 0.04 TRBEDROOM 1 — Fresh air & infiltration: 0.12 TRBEDROOM 1 — Duct gains & safety: 0.29 TR2.24OFFICEOFFICE — Walls & doors: 0.28 TROFFICE — Floor & partitions: 0.48 TROFFICE — Glass conduction: 0.08 TROFFICE — Glass solar: 0.46 TROFFICE — People: 0.11 TROFFICE — Lights: 0.14 TROFFICE — Equipment: 0.18 TROFFICE — Fresh air & infiltration: 0.12 TROFFICE — Duct gains & safety: 0.27 TR2.12KITCHENKITCHEN — Walls & doors: 0.16 TRKITCHEN — Floor & partitions: 0.28 TRKITCHEN — Glass conduction: 0.07 TRKITCHEN — Glass solar: 0.42 TRKITCHEN — People: 0.31 TRKITCHEN — Lights: 0.11 TRKITCHEN — Equipment: 0.39 TRKITCHEN — Fresh air & infiltration: 0.07 TRKITCHEN — Duct gains & safety: 0.25 TR2.06KITCHENKITCHEN — Walls & doors: 0.16 TRKITCHEN — Floor & partitions: 0.18 TRKITCHEN — Glass conduction: 0.07 TRKITCHEN — Glass solar: 0.42 TRKITCHEN — People: 0.31 TRKITCHEN — Lights: 0.11 TRKITCHEN — Equipment: 0.39 TRKITCHEN — Fresh air & infiltration: 0.07 TRKITCHEN — Duct gains & safety: 0.24 TR1.94OFFICEOFFICE — Walls & doors: 0.28 TROFFICE — Floor & partitions: 0.25 TROFFICE — Glass conduction: 0.08 TROFFICE — Glass solar: 0.46 TROFFICE — People: 0.11 TROFFICE — Lights: 0.14 TROFFICE — Equipment: 0.18 TROFFICE — Fresh air & infiltration: 0.12 TROFFICE — Duct gains & safety: 0.24 TR1.85LIVINGLIVING — Walls & doors: 0.13 TRLIVING — Roof: 0.66 TRLIVING — Floor & partitions: 0.16 TRLIVING — Glass conduction: 0.05 TRLIVING — Glass solar: 0.05 TRLIVING — People: 0.12 TRLIVING — Lights: 0.06 TRLIVING — Equipment: 0.05 TRLIVING — Fresh air & infiltration: 0.09 TRLIVING — Duct gains & safety: 0.20 TR1.58BEDROOM 1BEDROOM 1 — Walls & doors: 0.42 TRBEDROOM 1 — Floor & partitions: 0.41 TRBEDROOM 1 — Glass conduction: 0.06 TRBEDROOM 1 — Glass solar: 0.01 TRBEDROOM 1 — People: 0.15 TRBEDROOM 1 — Lights: 0.09 TRBEDROOM 1 — Equipment: 0.04 TRBEDROOM 1 — Fresh air & infiltration: 0.12 TRBEDROOM 1 — Duct gains & safety: 0.19 TR1.49BEDROOM 1BEDROOM 1 — Walls & doors: 0.42 TRBEDROOM 1 — Floor & partitions: 0.24 TRBEDROOM 1 — Glass conduction: 0.06 TRBEDROOM 1 — Glass solar: 0.01 TRBEDROOM 1 — People: 0.15 TRBEDROOM 1 — Lights: 0.09 TRBEDROOM 1 — Equipment: 0.04 TRBEDROOM 1 — Fresh air & infiltration: 0.12 TRBEDROOM 1 — Duct gains & safety: 0.16 TR1.29BEDROOM 2BEDROOM 2 — Walls & doors: 0.10 TRBEDROOM 2 — Roof: 0.52 TRBEDROOM 2 — Floor & partitions: 0.19 TRBEDROOM 2 — People: 0.09 TRBEDROOM 2 — Lights: 0.05 TRBEDROOM 2 — Equipment: 0.02 TRBEDROOM 2 — Fresh air & infiltration: 0.07 TRBEDROOM 2 — Duct gains & safety: 0.15 TR1.19LIVINGLIVING — Walls & doors: 0.15 TRLIVING — Floor & partitions: 0.29 TRLIVING — Glass conduction: 0.05 TRLIVING — Glass solar: 0.04 TRLIVING — People: 0.12 TRLIVING — Lights: 0.06 TRLIVING — Equipment: 0.05 TRLIVING — Fresh air & infiltration: 0.09 TRLIVING — Duct gains & safety: 0.12 TR0.98LIVINGLIVING — Walls & doors: 0.15 TRLIVING — Floor & partitions: 0.16 TRLIVING — Glass conduction: 0.05 TRLIVING — Glass solar: 0.04 TRLIVING — People: 0.12 TRLIVING — Lights: 0.06 TRLIVING — Equipment: 0.05 TRLIVING — Fresh air & infiltration: 0.09 TRLIVING — Duct gains & safety: 0.10 TR0.83BEDROOM 2BEDROOM 2 — Walls & doors: 0.12 TRBEDROOM 2 — Floor & partitions: 0.30 TRBEDROOM 2 — People: 0.09 TRBEDROOM 2 — Lights: 0.05 TRBEDROOM 2 — Equipment: 0.02 TRBEDROOM 2 — Fresh air & infiltration: 0.07 TRBEDROOM 2 — Duct gains & safety: 0.09 TR0.74BEDROOM 2BEDROOM 2 — Walls & doors: 0.12 TRBEDROOM 2 — Floor & partitions: 0.19 TRBEDROOM 2 — People: 0.09 TRBEDROOM 2 — Lights: 0.05 TRBEDROOM 2 — Equipment: 0.02 TRBEDROOM 2 — Fresh air & infiltration: 0.07 TRBEDROOM 2 — Duct gains & safety: 0.08 TR0.62TR (12 000 Btu/h)

Each bar is the room's grand total on its E20 sheet (design season), split into envelope, glass, internal, fresh-air and duct / safety parts.

Building cooling load by component — Σ room peaks 24.4 TRFloor & partitions3.8 TR15.5 %Roof3.7 TR15.2 %Walls & doors3.5 TR14.1 %Duct gains & safety3.1 TR12.6 %Glass solar2.5 TR10.2 %People2.3 TR9.5 %Equipment2.1 TR8.4 %Fresh air & infiltration1.4 TR5.7 %Lights1.3 TR5.4 %Glass conduction0.8 TR3.3 %
Block cooling load by sun time (summer, all rooms together), TRWalls & doorsRoofFloor & partitionsGlass conductionGlass solarPeopleLightsEquipmentFresh air & infiltrationDuct gains & safety010208:00 — Walls & doors: 2.36 TR8:00 — Roof: 2.55 TR8:00 — Floor & partitions: 3.80 TR8:00 — Glass conduction: 0.80 TR8:00 — Glass solar: 1.78 TR8:00 — People: 2.33 TR8:00 — Lights: 1.32 TR8:00 — Equipment: 2.06 TR8:00 — Fresh air & infiltration: 1.39 TR8:00 — Duct gains & safety: 2.62 TR21.08h9:00 — Walls & doors: 2.41 TR9:00 — Roof: 2.92 TR9:00 — Floor & partitions: 3.80 TR9:00 — Glass conduction: 0.80 TR9:00 — Glass solar: 1.75 TR9:00 — People: 2.33 TR9:00 — Lights: 1.32 TR9:00 — Equipment: 2.06 TR9:00 — Fresh air & infiltration: 1.39 TR9:00 — Duct gains & safety: 2.68 TR21.49h10:00 — Walls & doors: 2.55 TR10:00 — Roof: 3.22 TR10:00 — Floor & partitions: 3.80 TR10:00 — Glass conduction: 0.80 TR10:00 — Glass solar: 1.51 TR10:00 — People: 2.33 TR10:00 — Lights: 1.32 TR10:00 — Equipment: 2.06 TR10:00 — Fresh air & infiltration: 1.39 TR10:00 — Duct gains & safety: 2.71 TR21.710h11:00 — Walls & doors: 2.76 TR11:00 — Roof: 3.51 TR11:00 — Floor & partitions: 3.80 TR11:00 — Glass conduction: 0.80 TR11:00 — Glass solar: 1.15 TR11:00 — People: 2.33 TR11:00 — Lights: 1.32 TR11:00 — Equipment: 2.06 TR11:00 — Fresh air & infiltration: 1.39 TR11:00 — Duct gains & safety: 2.73 TR21.811h12:00 — Walls & doors: 2.91 TR12:00 — Roof: 3.73 TR12:00 — Floor & partitions: 3.80 TR12:00 — Glass conduction: 0.80 TR12:00 — Glass solar: 0.94 TR12:00 — People: 2.33 TR12:00 — Lights: 1.32 TR12:00 — Equipment: 2.06 TR12:00 — Fresh air & infiltration: 1.39 TR12:00 — Duct gains & safety: 2.76 TR22.012h13:00 — Walls & doors: 3.24 TR13:00 — Roof: 3.81 TR13:00 — Floor & partitions: 3.80 TR13:00 — Glass conduction: 0.80 TR13:00 — Glass solar: 1.12 TR13:00 — People: 2.33 TR13:00 — Lights: 1.32 TR13:00 — Equipment: 2.06 TR13:00 — Fresh air & infiltration: 1.39 TR13:00 — Duct gains & safety: 2.85 TR22.713h14:00 — Walls & doors: 3.52 TR14:00 — Roof: 3.73 TR14:00 — Floor & partitions: 3.80 TR14:00 — Glass conduction: 0.80 TR14:00 — Glass solar: 1.44 TR14:00 — People: 2.33 TR14:00 — Lights: 1.32 TR14:00 — Equipment: 2.06 TR14:00 — Fresh air & infiltration: 1.39 TR14:00 — Duct gains & safety: 2.93 TR23.314h15:00 — Walls & doors: 3.69 TR15:00 — Roof: 3.59 TR15:00 — Floor & partitions: 3.80 TR15:00 — Glass conduction: 0.80 TR15:00 — Glass solar: 1.64 TR15:00 — People: 2.33 TR15:00 — Lights: 1.32 TR15:00 — Equipment: 2.06 TR15:00 — Fresh air & infiltration: 1.39 TR15:00 — Duct gains & safety: 2.96 TR23.615h16:00 — Walls & doors: 3.80 TR16:00 — Roof: 3.44 TR16:00 — Floor & partitions: 3.80 TR16:00 — Glass conduction: 0.80 TR16:00 — Glass solar: 1.66 TR16:00 — People: 2.33 TR16:00 — Lights: 1.32 TR16:00 — Equipment: 2.06 TR16:00 — Fresh air & infiltration: 1.39 TR16:00 — Duct gains & safety: 2.96 TR23.616h17:00 — Walls & doors: 4.05 TR17:00 — Roof: 3.22 TR17:00 — Floor & partitions: 3.80 TR17:00 — Glass conduction: 0.80 TR17:00 — Glass solar: 1.44 TR17:00 — People: 2.33 TR17:00 — Lights: 1.32 TR17:00 — Equipment: 2.06 TR17:00 — Fresh air & infiltration: 1.39 TR17:00 — Duct gains & safety: 2.93 TR23.317h18:00 — Walls & doors: 4.09 TR18:00 — Roof: 2.99 TR18:00 — Floor & partitions: 3.80 TR18:00 — Glass conduction: 0.80 TR18:00 — Glass solar: 0.76 TR18:00 — People: 2.33 TR18:00 — Lights: 1.32 TR18:00 — Equipment: 2.06 TR18:00 — Fresh air & infiltration: 1.39 TR18:00 — Duct gains & safety: 2.80 TR22.318hsun time — peak 23.6 TR at 15:00 (negative parts, e.g. winter-side partitions, not drawn)

Summer block load of all rooms together at each sun hour (peak search on — the block peak sets the plant).

Coil process — OFFICE (summer 13:00, SHR 0.98, BF 0.15)p = 13.968 psia (1400 ft) · DB °F (bottom) / °C (top) · humidity ratio gr/lb (right)304050607080901001100510152025303540020406080100120140Dry bulb °FW gr/lbWB 40WB 50WB 60WB 7010%20%30%40%50%60%70%80%90%NBCS D3 cl. 3.6: 18–26 °C, RH 30–70 %ORMADPSO outside: 105.8 °F (41.0 °C), 57.2 gr/lbR room: 75.0 °F (23.9 °C), 68.1 gr/lbM mixed (3 % OA): 76.0 °F (24.4 °C), 67.7 gr/lbADP: 54.9 °F (12.7 °C), 67.5 gr/lbS off coil: 58.1 °F (14.5 °C), 67.6 gr/lb

Coil process of the largest room by the bypass-factor method: O and R mix to M at the fresh-air fraction of the supply air; the coil line M → ADP, leaving at S = ADP + BF·(M − ADP); S → R is the room ESHF line. Green box: NBCS D3 cl. 3.6 occupied-space limits.

5. NBCS 2026 Part D Sec 3 checks

CheckValueLimit / reference valueResultClause
Outside design conditionsused summer 105.8 °F DB / 69.8 WB, monsoon WB 81.0 °FTable 3 Jaipur: summer 105.8 / 69.8 °F, monsoon WB 81.0 °F, winter 48.7 °FPASSNBCS D3 cl. 3.5 / Table 3
All rooms45 checks pass, 0 to reviewcooling ≤ 26 °C, heating ≥ 18 °C, RH 30–70 %; patient rooms 21–24 °C, RH ≤ 60 %, 2 / 6 ACH; server 18–27 °C, RH 8–60 %PASSNBCS D3 cl. 3.6, Table 27, cl. 13.4.4

6. Room load sheets (E20 form)

KITCHEN — Ground · Kitchen (commercial) · 275 ft² · 10.8 ft · 5 persons · room 78.0 °F / 55 % · design summer 16:00 · roof: ac · floor: ground

ItemArea / qtyU / factorTD summerBtu/hTD monsoonBtu/hTD winterBtu/h
N wall240.50.35013.81,162-4.2-354-29.3-2,466
W wall104.90.35021.88003.8139-29.3-1,075
Floor on ground274.70.44010.01,20910.01,209-10.0-1,209
Partition (non-AC)233.70.51017.82,121-0.2-24-20.0-2,384
Glass conduction (all)29.11.02027.88249.8291-29.3-869
W glass solar29.10.950181.04,997186.75,155
Lights274.71.3633.41,2773.41,2773.41,277
Equipment1,373.51.0003.44,6863.44,6863.44,686
People (sensible)5.0246.6671.01,2331.01,2331.01,418
Ventilation (bypass) sensible70.50.16227.83179.8112-29.3-334
Space sensible18,62713,724-955
Supply duct gain + safety1,8631,372-96
Total room sensible (RSH)20,48915,097-1,051
People (latent)5.0503.3331.02,5171.02,5171.02,265
Ventilation (bypass) latent70.50.102-25.8-18575.4542-46.7-336
Total room latent (RLH)2,3313,0591,929
Outside air on coil: cfm × (1 − BF) × 4.5 × Δh70.53.8252.7473714.253,841-14.41-3,885
Return duct gain1,1781,100-150
Grand total heat24,73623,096-3,156
TR2.061.92-0.26
SHR · ADP · selected supply temp · CFM0.898 · 59.4 °F · 59 °F · 1,175 cfm0.832 · 58.4 · 58 · 822

Check figures: 133 ft²/TR · 4.28 cfm/ft² · 570 cfm/TR · 90.0 Btu/h·ft² · 23.7 ACPH · ETD correction 9.8 °F

BEDROOM 2 — Ground · Residential bedroom · 275 ft² · 10.8 ft · 3 persons · room 75.0 °F / 50 % · design summer 17:00 · roof: ac · floor: ground

ItemArea / qtyU / factorTD summerBtu/hTD monsoonBtu/hTD winterBtu/h
N wall240.50.35017.81,498-0.2-17-26.3-2,214
Floor on ground274.70.44010.01,20910.01,209-10.0-1,209
Partition (non-AC)220.10.51020.82,3352.8314-20.0-2,245
Lights274.70.6253.45863.45863.4586
Equipment82.41.0003.42813.42813.4281
People (sensible)3.0239.1671.07181.07181.0825
Ventilation (bypass) sensible31.50.16230.815712.865-26.3-134
Space sensible6,7843,156-4,110
Supply duct gain + safety678316-411
Total room sensible (RSH)7,4623,472-4,521
People (latent)3.0110.8331.03321.03321.0299
Ventilation (bypass) latent31.50.102-10.9-3590.3290-31.8-102
Total room latent (RLH)298623197
Outside air on coil: cfm × (1 − BF) × 4.5 × Δh31.53.8255.8069917.322,086-11.34-1,366
Return duct gain423309-284
Grand total heat8,8816,489-5,974
TR0.740.54-0.50
SHR · ADP · selected supply temp · CFM0.962 · 54.6 °F · 54 °F · 387 cfm0.848 · 52.5 · 52 · 164

Check figures: 371 ft²/TR · 1.41 cfm/ft² · 523 cfm/TR · 32.3 Btu/h·ft² · 7.8 ACPH · ETD correction 12.8 °F

OFFICE — Ground · Office — open plan · 636 ft² · 10.8 ft · 3 persons · room 75.0 °F / 50 % · design summer 8:00 · roof: ac · floor: ground

ItemArea / qtyU / factorTD summerBtu/hTD monsoonBtu/hTD winterBtu/h
N wall98.40.35012.8441-5.2-179-26.3-906
E wall279.20.35018.81,8370.878-26.3-2,570
S wall205.00.35014.81,062-3.2-230-26.3-1,887
Floor on ground636.00.44010.02,79910.02,799-10.0-2,799
Partition (non-AC)278.80.51020.82,9582.8398-20.0-2,844
Glass conduction (all)32.31.02030.81,01412.8422-26.3-866
E glass solar32.30.950181.05,552186.75,727
Lights636.00.7623.41,6553.41,6553.41,655
Equipment636.01.0003.42,1703.42,1703.42,170
People (sensible)3.0244.1671.07321.07321.0842
Ventilation (bypass) sensible53.20.16230.826512.8110-26.3-227
Space sensible20,48513,683-7,430
Supply duct gain + safety2,0491,368-743
Total room sensible (RSH)22,53415,051-8,174
People (latent)3.0205.8331.06181.06181.0556
Ventilation (bypass) latent53.20.102-10.9-5990.3490-31.8-172
Total room latent (RLH)5591,107383
Outside air on coil: cfm × (1 − BF) × 4.5 × Δh53.23.8255.801,18017.323,522-11.34-2,307
Return duct gain1,214984-505
Grand total heat25,48620,665-10,602
TR2.121.72-0.88
SHR · ADP · selected supply temp · CFM0.976 · 54.8 °F · 54 °F · 1,169 cfm0.931 · 54.1 · 54 · 781

Check figures: 299 ft²/TR · 1.84 cfm/ft² · 550 cfm/TR · 40.1 Btu/h·ft² · 10.2 ACPH · ETD correction 12.8 °F

BEDROOM 1 — Ground · Residential bedroom · 480 ft² · 10.8 ft · 5 persons · room 75.0 °F / 50 % · design summer 18:00 · roof: ac · floor: ground

ItemArea / qtyU / factorTD summerBtu/hTD monsoonBtu/hTD winterBtu/h
S wall251.80.35030.82,71412.81,128-26.3-2,318
W wall205.00.35032.82,35311.8846-26.3-1,887
Floor on ground479.90.44010.02,11110.02,111-10.0-2,111
Partition (non-AC)269.20.51020.82,8562.8384-20.0-2,746
Glass conduction (all)24.21.02030.876112.8316-26.3-650
S glass solar24.20.9507.016114.0322
Lights479.90.6253.41,0233.41,0233.41,023
Equipment144.01.0003.44913.44913.4491
People (sensible)5.0239.1671.01,1961.01,1961.01,375
Ventilation (bypass) sensible53.80.16230.826812.8112-26.3-229
Space sensible13,9357,930-7,051
Supply duct gain + safety1,394793-705
Total room sensible (RSH)15,3298,723-7,756
People (latent)5.0110.8331.05541.05541.0499
Ventilation (bypass) latent53.80.102-10.9-6090.3496-31.8-174
Total room latent (RLH)4951,050324
Outside air on coil: cfm × (1 − BF) × 4.5 × Δh53.83.8255.801,19417.323,564-11.34-2,334
Return duct gain851667-488
Grand total heat17,86814,004-10,254
TR1.491.17-0.85
SHR · ADP · selected supply temp · CFM0.969 · 54.7 °F · 54 °F · 795 cfm0.893 · 53.4 · 53 · 432

Check figures: 322 ft²/TR · 1.66 cfm/ft² · 534 cfm/TR · 37.2 Btu/h·ft² · 9.2 ACPH · ETD correction 12.8 °F

LIVING — Ground · Residential living / dining · 356 ft² · 10.8 ft · 4 persons · room 75.0 °F / 50 % · design summer 15:00 · roof: ac · floor: ground

ItemArea / qtyU / factorTD summerBtu/hTD monsoonBtu/hTD winterBtu/h
S wall185.60.35027.81,8066.8442-26.3-1,708
Floor on ground355.60.44010.01,56510.01,565-10.0-1,565
Partition (non-AC)184.60.51020.81,9582.8264-20.0-1,883
Glass conduction (all)19.41.02030.860912.8253-26.3-520
S glass solar19.40.95029.053555.11,014
Lights355.60.6253.47583.47583.4758
Equipment177.81.0003.46073.46073.4607
People (sensible)4.0239.1671.09571.09571.01,100
Ventilation (bypass) sensible41.30.16230.820612.886-26.3-176
Space sensible9,0005,945-3,387
Supply duct gain + safety900595-339
Total room sensible (RSH)9,9006,540-3,725
People (latent)4.0110.8331.04431.04431.0399
Ventilation (bypass) latent41.30.102-10.9-4690.3381-31.8-134
Total room latent (RLH)398824265
Outside air on coil: cfm × (1 − BF) × 4.5 × Δh41.33.8255.8091817.322,739-11.34-1,794
Return duct gain561505-263
Grand total heat11,77610,608-5,517
TR0.980.88-0.46
SHR · ADP · selected supply temp · CFM0.961 · 54.6 °F · 54 °F · 514 cfm0.888 · 53.3 · 53 · 324

Check figures: 362 ft²/TR · 1.44 cfm/ft² · 523 cfm/TR · 33.1 Btu/h·ft² · 8.0 ACPH · ETD correction 12.8 °F

KITCHEN — First (1/2) · Kitchen (commercial) · 275 ft² · 10.8 ft · 5 persons · room 78.0 °F / 55 % · design summer 16:00 · roof: ac · floor: ac

ItemArea / qtyU / factorTD summerBtu/hTD monsoonBtu/hTD winterBtu/h
N wall240.50.35013.81,162-4.2-354-29.3-2,466
W wall104.90.35021.88003.8139-29.3-1,075
Partition (non-AC)233.70.51017.82,121-0.2-24-20.0-2,384
Glass conduction (all)29.11.02027.88249.8291-29.3-869
W glass solar29.10.950181.04,997186.75,155
Lights274.71.3633.41,2773.41,2773.41,277
Equipment1,373.51.0003.44,6863.44,6863.44,686
People (sensible)5.0246.6671.01,2331.01,2331.01,418
Ventilation (bypass) sensible70.50.16227.83179.8112-29.3-334
Space sensible17,41812,516254
Supply duct gain + safety1,7421,25225
Total room sensible (RSH)19,16013,767279
People (latent)5.0503.3331.02,5171.02,5171.02,265
Ventilation (bypass) latent70.50.102-25.8-18575.4542-46.7-336
Total room latent (RLH)2,3313,0591,929
Outside air on coil: cfm × (1 − BF) × 4.5 × Δh70.53.8252.7473714.253,841-14.41-3,885
Return duct gain1,1111,033-84
Grand total heat23,34021,700-1,760
TR1.941.81-0.15
SHR · ADP · selected supply temp · CFM0.892 · 59.3 °F · 59 °F · 1,098 cfm0.818 · 58.1 · 58 · 750

Check figures: 141 ft²/TR · 4.00 cfm/ft² · 565 cfm/TR · 85.0 Btu/h·ft² · 22.2 ACPH · ETD correction 9.8 °F

BEDROOM 2 — First (1/2) · Residential bedroom · 275 ft² · 10.8 ft · 3 persons · room 75.0 °F / 50 % · design summer 17:00 · roof: ac · floor: ac

ItemArea / qtyU / factorTD summerBtu/hTD monsoonBtu/hTD winterBtu/h
N wall240.50.35017.81,498-0.2-17-26.3-2,214
Partition (non-AC)220.10.51020.82,3352.8314-20.0-2,245
Lights274.70.6253.45863.45863.4586
Equipment82.41.0003.42813.42813.4281
People (sensible)3.0239.1671.07181.07181.0825
Ventilation (bypass) sensible31.50.16230.815712.865-26.3-134
Space sensible5,5751,947-2,901
Supply duct gain + safety557195-290
Total room sensible (RSH)6,1322,142-3,191
People (latent)3.0110.8331.03321.03321.0299
Ventilation (bypass) latent31.50.102-10.9-3590.3290-31.8-102
Total room latent (RLH)298623197
Outside air on coil: cfm × (1 − BF) × 4.5 × Δh31.53.8255.8069917.322,086-11.34-1,366
Return duct gain356243-218
Grand total heat7,4855,093-4,578
TR0.620.42-0.38
SHR · ADP · selected supply temp · CFM0.954 · 54.5 °F · 54 °F · 318 cfm0.775 · 50.2 · 50 · 93

Check figures: 440 ft²/TR · 1.16 cfm/ft² · 510 cfm/TR · 27.2 Btu/h·ft² · 6.4 ACPH · ETD correction 12.8 °F

OFFICE — First (1/2) · Office — open plan · 636 ft² · 10.8 ft · 3 persons · room 75.0 °F / 50 % · design summer 8:00 · roof: ac · floor: ac

ItemArea / qtyU / factorTD summerBtu/hTD monsoonBtu/hTD winterBtu/h
N wall98.40.35012.8441-5.2-179-26.3-906
E wall279.20.35018.81,8370.878-26.3-2,570
S wall205.00.35014.81,062-3.2-230-26.3-1,887
Partition (non-AC)278.80.51020.82,9582.8398-20.0-2,844
Glass conduction (all)32.31.02030.81,01412.8422-26.3-866
E glass solar32.30.950181.05,552186.75,727
Lights636.00.7623.41,6553.41,6553.41,655
Equipment636.01.0003.42,1703.42,1703.42,170
People (sensible)3.0244.1671.07321.07321.0842
Ventilation (bypass) sensible53.20.16230.826512.8110-26.3-227
Space sensible17,68710,884-4,632
Supply duct gain + safety1,7691,088-463
Total room sensible (RSH)19,45511,973-5,095
People (latent)3.0205.8331.06181.06181.0556
Ventilation (bypass) latent53.20.102-10.9-5990.3490-31.8-172
Total room latent (RLH)5591,107383
Outside air on coil: cfm × (1 − BF) × 4.5 × Δh53.23.8255.801,18017.323,522-11.34-2,307
Return duct gain1,060830-351
Grand total heat22,25417,432-7,369
TR1.851.45-0.61
SHR · ADP · selected supply temp · CFM0.972 · 54.8 °F · 54 °F · 1,009 cfm0.915 · 53.9 · 53 · 593

Check figures: 343 ft²/TR · 1.59 cfm/ft² · 544 cfm/TR · 35.0 Btu/h·ft² · 8.8 ACPH · ETD correction 12.8 °F

BEDROOM 1 — First (1/2) · Residential bedroom · 480 ft² · 10.8 ft · 5 persons · room 75.0 °F / 50 % · design summer 18:00 · roof: ac · floor: ac

ItemArea / qtyU / factorTD summerBtu/hTD monsoonBtu/hTD winterBtu/h
S wall251.80.35030.82,71412.81,128-26.3-2,318
W wall205.00.35032.82,35311.8846-26.3-1,887
Partition (non-AC)269.20.51020.82,8562.8384-20.0-2,746
Glass conduction (all)24.21.02030.876112.8316-26.3-650
S glass solar24.20.9507.016114.0322
Lights479.90.6253.41,0233.41,0233.41,023
Equipment144.01.0003.44913.44913.4491
People (sensible)5.0239.1671.01,1961.01,1961.01,375
Ventilation (bypass) sensible53.80.16230.826812.8112-26.3-229
Space sensible11,8245,819-4,939
Supply duct gain + safety1,182582-494
Total room sensible (RSH)13,0066,401-5,433
People (latent)5.0110.8331.05541.05541.0499
Ventilation (bypass) latent53.80.102-10.9-6090.3496-31.8-174
Total room latent (RLH)4951,050324
Outside air on coil: cfm × (1 − BF) × 4.5 × Δh53.83.8255.801,19417.323,564-11.34-2,334
Return duct gain735551-372
Grand total heat15,43011,565-7,815
TR1.290.96-0.65
SHR · ADP · selected supply temp · CFM0.963 · 54.6 °F · 54 °F · 675 cfm0.859 · 52.7 · 52 · 303

Check figures: 373 ft²/TR · 1.41 cfm/ft² · 525 cfm/TR · 32.2 Btu/h·ft² · 7.8 ACPH · ETD correction 12.8 °F

LIVING — First (1/2) · Residential living / dining · 356 ft² · 10.8 ft · 4 persons · room 75.0 °F / 50 % · design summer 15:00 · roof: ac · floor: ac

ItemArea / qtyU / factorTD summerBtu/hTD monsoonBtu/hTD winterBtu/h
S wall185.60.35027.81,8066.8442-26.3-1,708
Partition (non-AC)184.60.51020.81,9582.8264-20.0-1,883
Glass conduction (all)19.41.02030.860912.8253-26.3-520
S glass solar19.40.95029.053555.11,014
Lights355.60.6253.47583.47583.4758
Equipment177.81.0003.46073.46073.4607
People (sensible)4.0239.1671.09571.09571.01,100
Ventilation (bypass) sensible41.30.16230.820612.886-26.3-176
Space sensible7,4354,380-1,822
Supply duct gain + safety744438-182
Total room sensible (RSH)8,1794,818-2,004
People (latent)4.0110.8331.04431.04431.0399
Ventilation (bypass) latent41.30.102-10.9-4690.3381-31.8-134
Total room latent (RLH)398824265
Outside air on coil: cfm × (1 − BF) × 4.5 × Δh41.33.8255.8091817.322,739-11.34-1,794
Return duct gain475419-177
Grand total heat9,9698,800-3,709
TR0.830.73-0.31
SHR · ADP · selected supply temp · CFM0.954 · 54.5 °F · 54 °F · 424 cfm0.854 · 52.6 · 52 · 228

Check figures: 428 ft²/TR · 1.19 cfm/ft² · 511 cfm/TR · 28.0 Btu/h·ft² · 6.6 ACPH · ETD correction 12.8 °F

KITCHEN — First (2/2) · Kitchen (commercial) · 275 ft² · 10.8 ft · 5 persons · room 78.0 °F / 55 % · design summer 16:00 · roof: exposed · floor: ac

ItemArea / qtyU / factorTD summerBtu/hTD monsoonBtu/hTD winterBtu/h
N wall240.50.35013.81,162-4.2-354-29.3-2,466
W wall104.90.35021.88003.8139-29.3-1,075
Roof (exposed)274.70.44043.85,29425.83,118-29.3-3,541
Partition (non-AC)233.70.51017.82,121-0.2-24-20.0-2,384
Glass conduction (all)29.11.02027.88249.8291-29.3-869
W glass solar29.10.950181.04,997186.75,155
Lights274.71.3633.41,2773.41,2773.41,277
Equipment1,373.51.0003.44,6863.44,6863.44,686
People (sensible)5.0246.6671.01,2331.01,2331.01,418
Ventilation (bypass) sensible70.50.16227.83179.8112-29.3-334
Space sensible22,71215,634-3,288
Supply duct gain + safety2,2711,563-329
Total room sensible (RSH)24,98317,197-3,617
People (latent)5.0503.3331.02,5171.02,5171.02,265
Ventilation (bypass) latent70.50.102-25.8-18575.4542-46.7-336
Total room latent (RLH)2,3313,0591,929
Outside air on coil: cfm × (1 − BF) × 4.5 × Δh70.53.8252.7473714.253,841-14.41-3,885
Return duct gain1,4031,205-279
Grand total heat29,45425,302-5,851
TR2.452.11-0.49
SHR · ADP · selected supply temp · CFM0.915 · 59.6 °F · 59 °F · 1,432 cfm0.849 · 58.7 · 58 · 937

Check figures: 112 ft²/TR · 5.21 cfm/ft² · 584 cfm/TR · 107.2 Btu/h·ft² · 28.9 ACPH · ETD correction 9.8 °F

BEDROOM 2 — First (2/2) · Residential bedroom · 275 ft² · 10.8 ft · 3 persons · room 75.0 °F / 50 % · design summer 13:00 · roof: exposed · floor: ac

ItemArea / qtyU / factorTD summerBtu/hTD monsoonBtu/hTD winterBtu/h
N wall240.50.35013.81,162-4.2-354-26.3-2,214
Roof (exposed)274.70.44051.86,26133.84,085-26.3-3,179
Partition (non-AC)220.10.51020.82,3352.8314-20.0-2,245
Lights274.70.6253.45863.45863.4586
Equipment82.41.0003.42813.42813.4281
People (sensible)3.0239.1671.07181.07181.0825
Ventilation (bypass) sensible31.50.16230.815712.865-26.3-134
Space sensible11,4995,696-6,080
Supply duct gain + safety1,150570-608
Total room sensible (RSH)12,6496,265-6,688
People (latent)3.0110.8331.03321.03321.0299
Ventilation (bypass) latent31.50.102-10.9-3590.3290-31.8-102
Total room latent (RLH)298623197
Outside air on coil: cfm × (1 − BF) × 4.5 × Δh31.53.8255.8069917.322,086-11.34-1,366
Return duct gain682449-393
Grand total heat14,3289,422-8,249
TR1.190.79-0.69
SHR · ADP · selected supply temp · CFM0.977 · 54.8 °F · 54 °F · 656 cfm0.910 · 53.8 · 53 · 310

Check figures: 230 ft²/TR · 2.39 cfm/ft² · 550 cfm/TR · 52.2 Btu/h·ft² · 13.2 ACPH · ETD correction 12.8 °F

OFFICE — First (2/2) · Office — open plan · 636 ft² · 10.8 ft · 3 persons · room 75.0 °F / 50 % · design summer 13:00 · roof: exposed · floor: ac

ItemArea / qtyU / factorTD summerBtu/hTD monsoonBtu/hTD winterBtu/h
N wall98.40.35013.8475-4.2-145-26.3-906
E wall279.20.35037.83,69419.81,935-26.3-2,570
S wall205.00.35020.81,4922.8201-26.3-1,887
Roof (exposed)636.00.44051.814,49733.89,459-26.3-7,360
Partition (non-AC)278.80.51020.82,9582.8398-20.0-2,844
Glass conduction (all)32.31.02030.81,01412.8422-26.3-866
E glass solar32.30.95033.01,01231.5967
Lights636.00.7623.41,6553.41,6553.41,655
Equipment636.01.0003.42,1703.42,1703.42,170
People (sensible)3.0244.1671.07321.07321.0842
Ventilation (bypass) sensible53.20.16230.826512.8110-26.3-227
Space sensible29,96417,905-11,992
Supply duct gain + safety2,9961,790-1,199
Total room sensible (RSH)32,96119,695-13,191
People (latent)3.0205.8331.06181.06181.0556
Ventilation (bypass) latent53.20.102-10.9-5990.3490-31.8-172
Total room latent (RLH)5591,107383
Outside air on coil: cfm × (1 − BF) × 4.5 × Δh53.23.8255.801,18017.323,522-11.34-2,307
Return duct gain1,7351,216-756
Grand total heat36,43525,541-15,870
TR3.042.13-1.32
SHR · ADP · selected supply temp · CFM0.983 · 54.9 °F · 54 °F · 1,710 cfm0.947 · 54.4 · 54 · 1,022

Check figures: 209 ft²/TR · 2.69 cfm/ft² · 563 cfm/TR · 57.3 Btu/h·ft² · 14.9 ACPH · ETD correction 12.8 °F

BEDROOM 1 — First (2/2) · Residential bedroom · 480 ft² · 10.8 ft · 5 persons · room 75.0 °F / 50 % · design summer 14:00 · roof: exposed · floor: ac

ItemArea / qtyU / factorTD summerBtu/hTD monsoonBtu/hTD winterBtu/h
S wall251.80.35024.82,1852.8247-26.3-2,318
W wall205.00.35020.81,4921.8129-26.3-1,887
Roof (exposed)479.90.44050.810,72633.87,136-26.3-5,553
Partition (non-AC)269.20.51020.82,8562.8384-20.0-2,746
Glass conduction (all)24.21.02030.876112.8316-26.3-650
S glass solar24.20.95033.476868.21,569
Lights479.90.6253.41,0233.41,0233.41,023
Equipment144.01.0003.44913.44913.4491
People (sensible)5.0239.1671.01,1961.01,1961.01,375
Ventilation (bypass) sensible53.80.16230.826812.8112-26.3-229
Space sensible21,76712,604-10,492
Supply duct gain + safety2,1771,260-1,049
Total room sensible (RSH)23,94313,864-11,542
People (latent)5.0110.8331.05541.05541.0499
Ventilation (bypass) latent53.80.102-10.9-6090.3496-31.8-174
Total room latent (RLH)4951,050324
Outside air on coil: cfm × (1 − BF) × 4.5 × Δh53.83.8255.801,19417.323,564-11.34-2,334
Return duct gain1,282924-678
Grand total heat26,91419,401-14,229
TR2.241.62-1.19
SHR · ADP · selected supply temp · CFM0.980 · 54.9 °F · 54 °F · 1,242 cfm0.930 · 54.1 · 54 · 719

Check figures: 214 ft²/TR · 2.59 cfm/ft² · 554 cfm/TR · 56.1 Btu/h·ft² · 14.3 ACPH · ETD correction 12.8 °F

LIVING — First (2/2) · Residential living / dining · 356 ft² · 10.8 ft · 4 persons · room 75.0 °F / 50 % · design summer 14:00 · roof: exposed · floor: ac

ItemArea / qtyU / factorTD summerBtu/hTD monsoonBtu/hTD winterBtu/h
S wall185.60.35024.81,6112.8182-26.3-1,708
Roof (exposed)355.60.44050.87,94933.85,289-26.3-4,115
Partition (non-AC)184.60.51020.81,9582.8264-20.0-1,883
Glass conduction (all)19.41.02030.860912.8253-26.3-520
S glass solar19.40.95033.461568.21,255
Lights355.60.6253.47583.47583.4758
Equipment177.81.0003.46073.46073.4607
People (sensible)4.0239.1671.09571.09571.01,100
Ventilation (bypass) sensible41.30.16230.820612.886-26.3-176
Space sensible15,2709,650-5,937
Supply duct gain + safety1,527965-594
Total room sensible (RSH)16,79710,615-6,531
People (latent)4.0110.8331.04431.04431.0399
Ventilation (bypass) latent41.30.102-10.9-4690.3381-31.8-134
Total room latent (RLH)398824265
Outside air on coil: cfm × (1 − BF) × 4.5 × Δh41.33.8255.8091817.322,739-11.34-1,794
Return duct gain906709-403
Grand total heat19,01814,887-8,463
TR1.581.24-0.71
SHR · ADP · selected supply temp · CFM0.977 · 54.8 °F · 54 °F · 871 cfm0.928 · 54.1 · 54 · 551

Check figures: 224 ft²/TR · 2.45 cfm/ft² · 550 cfm/TR · 53.5 Btu/h·ft² · 13.6 ACPH · ETD correction 12.8 °F

7. Worked example — from this project

Worked from this project’s own rooms — each value matches the room’s E20 sheet above (IP units, as on the sheet).

OFFICE — First (2/2) · Office — open plan (636 ft²)
the room with the largest cooling load; design summer 13:00 sun time
Given: Outside 105.8 °F DB, 57.2 gr/lb, h 34.45 Btu/lb · Room 75 °F, 50 % RH → 68.1 gr/lb, h 28.64 · Occupancy 3 persons, fresh air 53 cfm, BF 0.15
1. Outside design (summer): NBCS D3 Table 3, Jaipur: 1 % cooling DB / MCWB = 41 °C / 21 °C × 1.8 + 32 = 105.8 / 69.8 °F (cl. 3.5 comfort; winter 99 % heating DB 9.3 °C)
2. Fresh air: V = Rp·P + Ra·A = 5 × 3 + 0.06 × 636 = 53 cfm (NBCS D3 Table 7 (Rp, Ra of the room type))
3. Design differences: ΔT = To − Ti ; Δgr = Wo − Wi ; Δh = ho − hi = 105.8 − 75 ; 57.2 − 68.1 ; 34.45 − 28.64 = 30.8 °F ; -10.9 gr/lb ; 5.8 (Btu/lb)
4. ETD correction: corr = ΔT − 0.5·DR − 5 = 30.8 − 0.5 × 26 − 5 = 12.8 °F (Carrier Table 20A basis)
5. E wall conduction: q = U · Anet · (ETD + corr) = 0.35 × 279.2 × (25 + 12.8) = 3694 Btu/h (ETD from Carrier Table 19 (E, 100 lb/ft², 13:00) → 25 °F)
6. Roof conduction: q = U · A · (ETD + corr) = 0.44 × 636 × (39 + 12.8) = 14 497 Btu/h (ETD from Carrier Table 20 (exposed, 60 lb/ft², 13:00) → 39 °F)
7. Glass conduction: q = Ug · Ag · ΔT = 1.02 × 32.3 × 30.8 = 1014 Btu/h
8. E glass solar: q = A · SC · SHGF · SF = 32.3 × 0.95 × 38.8 × 0.85 = 1012 Btu/h (clear-sky SHGF at 26.9° N, month 6, 13:00, E → 38.8 Btu/h·ft²)
9. Lights: q = LPD · A · ballast · 3.412 = 0.61 × 636 × 1.25 × 3.412 = 1655 Btu/h
10. Equipment: q = W · 3.412 = 636 × 3.412 = 2170 Btu/h
11. People (sensible): qs = n · S = 3 × 244.2 = 732 Btu/h (S, L from Carrier Table 48 at the room DB)
12. Ventilation (bypass) sensible: q = cfm · BF · 1.08 · ΔT = 53.2 × 0.15 × 1.08 × 30.8 = 265 Btu/h
13. Other sheet items: Σ N wall, S wall, Partition (non-AC) = 475 + 1492 + 2958 = 4925 Btu/h (same U·A·TD rule (partitions / floor: TD = ΔT − 10 °F, ground 10 °F))
14. Space sensible: RSH0 = Σ items = 29 964 Btu/h (sheet 29 964)
15. Room sensible: RSH = RSH0 · (1 + duct + safety) = 29 964 × (1 + 0.1 + 0) = 32 961 Btu/h
16. People latent: ql = n · L = 3 × 205.8 = 618 Btu/h
17. Ventilation latent: q = cfm · BF · 0.68 · Δgr = 53.2 × 0.15 × 0.68 × -10.9 = -59 Btu/h
18. Room latent: RLH = Σ latent · (1 + safety) = (618 + -59) × (1 + 0) = 559 Btu/h
19. Outside air on coil: q = cfm · (1 − BF) · 4.5 · Δh = 53.2 × 0.85 × 4.5 × 5.8 = 1180 Btu/h
20. Return duct gain: q = (RSH + RLH + OA) · return % = (32 961 + 559 + 1180) × 0.05 = 1735 Btu/h
21. Grand total: GTH = RSH + RLH + OA + return = 32 961 + 559 + 1180 + 1735 = 36 435 Btu/h
22. Tonnage: TR = GTH / 12 000 = 36 435 / 12 000 = 3.04 TR (10.7 kW)
23. Sensible heat ratio: SHR = RSH / (RSH + RLH) = 32 961 / (32 961 + 559) = 0.983
24. Apparatus dew point: saturation point on the line through the room state with slope SHR = room 75 °F / 68.1 gr = 54.9 °F (supply temperature 54 °F = ⌊ADP⌋)
25. Supply air: CFM = RSH / (1.08 · (Ti − Tsup) · (1 − BF)) = 32 961 / (1.08 × (75 − 54) × 0.85) = 1710 cfm
26. Sheet agreement: recomputed GTH = E20 sheet → 36 435 vs 36 435 Btu/h PASS
27. Check figures: ft²/TR · cfm/ft² · ACPH → 209 ft²/TR · 2.69 cfm/ft² · 14.9 ACPH
Building total — 15 AC rooms
sum of room peaks and (with peak search) the coincident block load
1. Sum of room peaks: ΣTR = Σ room TR = 2.06 + 0.74 + 2.12 + 1.49 + 0.98 + 1.94 + 0.62 + 1.85 + … = 24.45 TR (86 kW refrigeration)
2. Area per TR: ft²/TR = Σ area / ΣTR = 6063 / 24.45 = 248 ft²/TR
3. Block peak: max over hours of Σ room GTH (summer) / 12 000 = 282 978 / 12 000 at 15:00 = 23.58 TR
4. Diversity: block peak / ΣTR = 23.58 / 24.45 = 0.965

8. Formulae applied

QuantityFormulaReference
Wall / roof conductionq = U · A_net · TD ; TD = ETD(orientation, weight, sun time) + (To − Ti) − 0.5·DR − 5Carrier Tables 19 / 20 / 20A
ASHRAE optionCLTD = (T̄_sa − Ti) + δ·(T_sa(t − lag) − T̄_sa) ; T_sa = To + α·E_t/h_o − ε·ΔR/h_oASHRAE Fundamentals ch. 18 (sol-air), mass-class lag / decrement
Glassq = U·A·(To − Ti) + A · SC · SHGF · storage factor ; SHGF from clear-sky (A, B, C) and DSA glass t(θ), a(θ)ASHRAE Fundamentals ch. 29 / 30 (1997); Carrier Table 15 basis
Partitions / groundq = U·A·((To − Ti) − 10) ; ground floor q = U·A·10Carrier E20
Peopleq_s = n · S(activity, room DB) ; q_l = n · LCarrier Table 48 / ASHRAE ch. 18 Table 1
Lights / equipmentq = W/ft² · A · ballast · 3.412 ; q = W · 3.412ASHRAE 90.1 / ECBC LPD
Fresh airV = Rp·P + Ra·A ; patient rooms V ≥ 2 ACH, supply ≥ 6 ACHNBCS D3 Table 7 / Table 27
Ventilationroom: cfm·BF·1.08·ΔT (sensible), cfm·BF·0.68·Δgr (latent) ; coil: cfm·(1 − BF)·4.5·ΔhCarrier E20 (bypass factor method)
Supply airSHR = RSH / (RSH + RLH) ; ADP from the ESHF line ; CFM = RSH / (1.08 · (Ti − T_sup) · (1 − BF))Carrier System Design Manual
PsychrometricsHyland-Wexler p_ws ; W = 0.622·p_w/(p − p_w) ; h = 0.24·T + W·(1061 + 0.444·T) ; p by altitudeASHRAE Fundamentals ch. 1

9. Standards and references

Prepared by
Checked by
Approved by

Results are design aids computed by designlink calc (calc.designlink.in) and must be reviewed by a qualified engineer before issue. Ground levels marked "assumed" have no survey level within reach — verify.