IDMT relay setting & grading

Sample project — Tower A · Electrical
Generated 28 Nov 2026 17:16
Overcurrent / earth-fault IDMT relays: plug setting from the load, operating time at the f…
Project code SAMPLE
Relays
3
Fastest trip
0.177 s
Slowest trip
0.439 s
Grading
OK

1. Inputs

GroupInputValueUnit
Relays (downstream first)One relay per line: name, kV, CT primary A, plug setting ×In, TMS (0 = auto), curve SI/VI/EI/LTI, max fault current at the relay AOutgoing feeder, 0.415, 400, 1.0, 0.1, SI, 18000 LT incomer, 0.415, 1600, 1.0, 0, SI, 25000 HT transformer feeder, 11, 100, 1.0, 0, SI, 4000
Relays (downstream first)Grading margin0.3s
Relays (downstream first)Lowest TMS of the relay0.05
Relays (downstream first)TMS step0.01
Plug setting check (first relay)Full-load current through the first relay320A
Plug setting check (first relay)Pick-up above full load1.25
Plug setting check (first relay)Plug setting step0.05× In

2. Results

Curve constants (IEC 60255-151)

ItemValueUnitNote / basis
Standard inversek = 0.14, α = 0.02t = TMS · k / ((I/Is)^α − 1)
Very inversek = 13.5, α = 1t = TMS · k / ((I/Is)^α − 1)
Extremely inversek = 80, α = 2t = TMS · k / ((I/Is)^α − 1)
Long-time inversek = 120, α = 1t = TMS · k / ((I/Is)^α − 1)

Relay settings and operating times

RelaykVCTPlug ×InIs ATMSCurveFault APSMt sMargin s
Outgoing feeder0.415400/114000.1SI1800045.000.177—
LT incomer0.4151600/1116000.17 (auto)SI2500015.620.4210.303
HT transformer feeder11100/111000.24 (auto)SI400040.000.4390.311
Time-current curves referred to 0.415 kV1001000100001000000.010.1110100current at 0.415 kV (A)operating time (s)Outgoing feeder (SI, TMS 0.1)LT incomer (SI, TMS 0.17)HT transformer feeder (SI, TMS 0.24)0.18 s0.42 s

3. Checks

CheckResultNote
First relay plug 1 × In ≥ 1.25 × 320 A / 400 A = 1.00 × InPASSsuggested plug 1 × In
LT incomer grades with Outgoing feeder at 18000 A (0.415 kV): 0.480 − 0.177 = 0.303 s ≥ 0.3 sPASS
HT transformer feeder grades with LT incomer at 25000 A (0.415 kV): 0.732 − 0.421 = 0.311 s ≥ 0.3 sPASSfault referred by the voltage ratio

4. Worked example

Outgoing feeder: Is = 1 × 400 = 400 A; PSM = 18000 / 400 = 45.00; t = 0.1 × 0.14 / (45.00^0.02 − 1) = 0.177 s (Standard inverse)
LT incomer: Is = 1 × 1600 = 1600 A; PSM = 25000 / 1600 = 15.62; t = 0.17 × 0.14 / (15.62^0.02 − 1) = 0.421 s (Standard inverse)
Grading Outgoing feeder → LT incomer: fault 18000 A × 0.415/0.415 = 18000 A; PSM 11.25; t = 0.480 s; margin 0.303 s
HT transformer feeder: Is = 1 × 100 = 100 A; PSM = 4000 / 100 = 40.00; t = 0.24 × 0.14 / (40.00^0.02 − 1) = 0.439 s (Standard inverse)
Grading LT incomer → HT transformer feeder: fault 25000 A × 0.415/11 = 943 A; PSM 9.43; t = 0.732 s; margin 0.311 s

5. Notes

6. Standards and references

Prepared by
Checked by
Approved by

Results are design aids computed by designlink calc (calc.designlink.in) and must be reviewed by a qualified engineer before issue. Ground levels marked "assumed" have no survey level within reach — verify.