SAMPLE Insulation thickness, condensation & condensate drain — this is what your report looks like, generated from demo inputs. Generate yours → 2 free designs every day for every signed-in account · 1 design free on sign-in · ₹99 + GST per design (report + Excel + DXF) · free for DesignLink companies
Report ready — use Print → Save as PDF (A4 landscape).
Design Linkcalc.designlink.in

Insulation thickness, condensation & condensate drain

Sample project — Tower A · HVAC
Generated 28 Nov 2026 16:09
Minimum insulation to keep the surface above dew point on chilled-water pipes, ducts and f…
Project code SAMPLE
Dew point
28.7 °C
Insulation
19 mm
Heat gain
18.7 W/m
Condensate
38.8 kg/h
Drain
DN 25 mm

1. Inputs

GroupInputValueUnit
Code basisDesign regimeIndia — NBCS 2026 (Part F 3.5.7.3.5 duct insulation non-combustible, D3 10.6)
AmbientAmbient dry bulb35°C
AmbientAmbient RH70%
AmbientOuter surface coefficient9.0W/m²K
AmbientSurface temperature margin above dew point1.0K
SurfaceGeometryPipe (round)
SurfaceFluid / inside temperature7°C
SurfacePipe outside diameter114.3mm
SurfaceInsulationNitrile rubber / elastomeric (k 0.036)
SurfaceCladding emissivity (info)0.9
SurfaceLength (for heat gain)100m
Condensate drainCooling capacity of the unit30TR
Condensate drainSensible heat ratio0.75
Condensate drainDrain slope1.0%

2. Results

Condensation control

ItemValueUnitNote / basis
Ambient35.0 °C / 70 %
Dew point28.7°C
Required surface temperature29.7°C
InsulationNitrile rubber / elastomeric (k 0.036)
Minimum thickness (calculated)15.26mmpipe: r₂·ln(r₂/r₁) = k·(T_s − T_i) / (h_o·(T_a − T_s))
Selected thickness19mm
Surface temperature with selection30.67°C
Heat gain18.65W/m1.87 kW over 100 m

Condensate drain

ItemValueUnitNote / basis
Latent load26.38kW
Condensate38.76kg/h0.65 L/min · 0.9 m³/day
Drain pipe (practice table by TR)DN 25 at ≥ 1.0 % slope
Trap depth (negative-pressure coil)≥ static pressure in mm WG + 25 mm (typically 50–100 mm)

Thickness vs surface temperature

mmT surface °CHeat gain W/m
624.138.8
926.830.6
1328.924.2
1930.718.7
2531.715.4
3232.412.9
3832.911.5
5033.49.5
6533.88.0
7534.07.3
10034.36.1
Thickness vs surface temperature and heat gain — Nitrile rubber / elastomeric, 35 °C / 70 % → 7 °C60121918382457307636950102030405060708090100insulation thickness, mmsurface temperature °Cheat gain W/mdew point 28.7 °Crequired 29.7 °Cmin 15.3 mmselected 19 mm: 30.7 °C, 18.7 W/mblue: surface temperature (dots = standard thicknesses) · orange: heat gain · red: dew point / required surface temperature

3. Checks

CheckResultNote
Surface 30.7 °C ≥ dew point 28.7 °C + 1.0 KPASS19 mm Nitrile rubber / elastomeric

4. Worked example

Worked from this project’s own inputs and results — each value can be traced to the schedules above.

Insulation for condensation control — pipe OD 114.3 mm, Nitrile rubber / elastomeric
this calculation's own inputs
Given: Ambient 35 °C / 70 % RH · Inside 7 °C · k 0.036 W/mK · ho 9 W/m²K · Margin 1 K
1. Dew point of the ambient air: tdp = f(t, RH) (psychrometrics) = 35 °C, 70 % = 28.7 °C
2. Required surface temperature: Ts = tdp + margin = 28.7 + 1 = 29.7 °C
3. Pipe equation: r2·ln(r2/r1) = k·(Ts − Ti) / (ho·(Ta − Ts)) = 0.036 × (29.7 − 7) / (9 × (35 − 29.7)) = 0.01714 m
4. Solve for r2 (bisection), r1 = OD/2: t = r2 − r1 = r1 = 0.05715 m → r2 = 0.07241 m = 15.3 mm
5. Selected standard thickness: next size ≥ t from 6, 9, 13, 19, 25, 32, 38, 50, 65, 75, 100 = 19 mm
6. Resistance per metre: R = ln(r2/r1)/(2πk) + 1/(ho·2π·r2) = ln(0.0761/0.0571)/(2π × 0.036) + 1/(9 × 2π × 0.0761) = 1.5012 mK/W
7. Heat gain: q = (Ta − Ti) / R = (35 − 7) / 1.5012 = 18.7 W/m (1.87 kW over 100 m)
8. Surface temperature: Ts = Ta − q / (ho·2π·r2) = 35 − 18.7 / (9 × 2π × 0.0761) = 30.7 °C
9. No condensation: Ts ≥ tdp + margin → 30.7 ≥ 29.7 °C PASS
10. Latent load: qL = TR × 3.517 × (1 − SHR) = 30 × 3.517 × (1 − 0.75) = 26.38 kW
11. Condensate: m = qL × 3600 / 2450 = 26.38 × 3600 / 2450 = 38.8 kg/h (drain DN 25 by the practice table)