Lift planning report — Sample project — Tower A

Generated 28 Nov 2026 17:16 · NBCS 2026

Result

7 lift(s) of 1,632 kg (24 persons) at 1.6 m/s — morning up-peak: interval 27.9 s, handling capacity 12.6 % in 5 minutes; average waiting time 24 s. Both targets are met.

1. Basis

ItemValueBasis
Building typeOffice (multi-tenant)
Code regimeNBCS 2026
Floors served above the main lobby14
Floor to floor / travel3.9 m / 54.6 m
Population (design)1,636 persons14 floors × 1100 m² ÷ 8 m²/person (nbcs); occupancy at the peak 85 %
Target handling capacity (5 min)12.5 % (range 10–15 %)code — NBCS 2026 Part D Sec 5A, cl. 4.2.1–4.2.9, Tables 1–5 (PDF p. 2225–2229)
Target interval35 scode — NBCS 2026 Part D Sec 5A, cl. 4.2.1–4.2.9, Tables 1–5 (PDF p. 2225–2229)
Target average waiting time35 scode — NBCS 2026 Part D Sec 5A, cl. 4.2.1–4.2.9, Tables 1–5 (PDF p. 2225–2229)

2. Selected lifts

ItemValue
Lifts in the group7
Rated load1,632 kg — 24 persons
Rated speed1.6 m/s — not less than 1 m/s for 14 floors; travel ÷ speed ≤ 35 s (NBCS 2026 Part D Sec 5A, cl. 4.5.1, Table 11 (PDF p. 2235); nominal travel time ≤ 35 s — NBCS 2026 Part D Sec 5A, cl. 4.2.1–4.2.9, Tables 1–5 (PDF p. 2225–2229))
Average car load19.2 persons (80 % of the rated persons)
Door times (open / close)2 / 3 s (typical) — Centre opening, 2 panel
Single-floor flight / stop time4.04 s / T − tv = 7.10 s (acceleration 1 m/s², start delay 0.5 s)
Passenger transfer time1.2 s each way
Governing patternMorning up-peak

3. Traffic by pattern

PatternStops SReversal floor HRTT sInterval sHC persons / 5 minHC % of populationCheckEquation
Morning up-peak ◄10.6313.70195.427.920612.6OKRTT = 2·H·tv + (S + 1)(T − tv) + 2·P·tp
Evening / morning down-peak10.6313.70125.017.932219.7≥ targetRTT = N·tv + (0.5·S + 1)(T − tv) + 2·P·tp
Mid-day (lunch) two-way10.6313.70309.844.326015.9≥ targetRTT = 2·H·tv + 2·S·(T − tv) + 4·P·tp

◄ governing pattern for this building type. Mid-day split: incoming 45 % / outgoing 45 % / inter-floor 10 %.

12.6 %Morning up-peak19.7 %Evening / morning down-peak15.9 %Mid-day (lunch) two-way15.7 %Up-peak, destination controltarget 12.5 %5-min handling capacity, % of population

Methods

4. Quality of service

MeasureValueHowCheck
Average waiting time (governing pattern)23.7 sAWT = [0.4 + (1.8·P/CC − 0.77)²] × INT (car loads 50–80 %) — factor 0.85 at P/CC = 0.80OK
Average transit time (up-peak)77.5 sATT = 0.5·H·tv + 0.5·S·(T − tv) + P·tp
Average time to destination101.1 stime to destination = AWT + ATT
Nominal travel time34.1 stravel ÷ rated speed
Inter-floor waiting time14.0 sAWT = INT_up-peak × (0.22 + 1.78 × A_interfloor / HC_up-peak) — inter-floor demand 2 % of the population in 5 minOK

code — average waiting time ≈ 75–85 % of the interval at 80 % car load — NBCS 2026 Part D Sec 5A, cl. 4.2.1–4.2.9, Tables 1–5 (PDF p. 2225–2229)

MeasureValueGradeBasis
Interval27.9 sVery goodcode — NBCS 2026 Part D Sec 5A, cl. 4.2.1–4.2.9, Tables 1–5 (PDF p. 2225–2229) Table 3
Average waiting time23.7 sPremium classcode — NBCS 2026 Part D Sec 5A, cl. 4.2.1–4.2.9, Tables 1–5 (PDF p. 2225–2229) Table 4
Nominal travel time34.1 sGoodcode — NBCS 2026 Part D Sec 5A, cl. 4.2.1–4.2.9, Tables 1–5 (PDF p. 2225–2229) Table 5

5. Conventional and destination control (up-peak)

ConventionalDestination control
Probable stops S10.635.20
Round trip time, s195.4156.8
Interval, s27.922.4
5-min handling capacity, persons206257
5-min handling capacity, % of population12.615.7

destination grouping model: the stops of one trip are taken on N/√L floors (passengers for the same floors share a car); the reversal floor is unchanged — typical — confirm with the lift maker. Up-peak capacity gain about 25 %.

Simulation

discrete-event simulation: Poisson arrivals with a 50 → 100 → 50 % ramp, directional collective control, trapezoidal motion, door / transfer times, capacity limit. Demand 12.5 % of the population in 5 minutes at the level part, 120 minutes, seed 1.

passenger generation for a simulation should be for 120 min and cover a minimum of 3 intervals of 5 min (cl. 4.2.1 b) — NBCS 2026 Part D Sec 5A, cl. 4.2.1–4.2.9, Tables 1–5 (PDF p. 2225–2229)

ControlPatternPassengersAWT s90th percentile wait sLongest wait sWaits over 60 s %Transit sTime to destination sLobby interval sCar load at the lobby %Not served at the end
Conventional (collective)Morning up-peak4,81844.169.59123.2101.1145.233.6870
Destination dispatchMorning up-peak4,81854.794.113742.879.5134.232.2810

Calculated (analytic) interval 27.9 s and AWT 23.7 s for comparison.

Waiting-time distribution

560–10 s9910–20 s12920–30 s231530–45 s281845–60 s233060–90 s1290–120 s> 120 sConventional (collective) — AWT 44 sDestination dispatch — AWT 55 swaiting time band — % of passengers

Queue over time

710ConventionalDestination dispatchtime, min (0 – 120) — passengers waiting on all floors

6. Dimensions — Passenger, Traction, machine-room-less (MRL)

ItemValueUnitBasis
Rated load1 632kggiven
24 persons at 68 kg
Rated speed1.6m/sgiven
Car inside width1 500mmcode — NBCS 2026 Part D Sec 5A, Table 27 (PDF p. 2269)
Car inside depth2 400mmcode — NBCS 2026 Part D Sec 5A, Table 27 (PDF p. 2269)
Clear entrance width1 000mmcode — NBCS 2026 Part D Sec 5A, Table 27 (PDF p. 2269)
Lift well width (clear plumb)2 500mmcode — NBCS 2026 Part D Sec 5A, Table 27 (PDF p. 2269)
Lift well depth (clear plumb)2 900mmcode — NBCS 2026 Part D Sec 5A, Table 27 (PDF p. 2269)
Counterweight positionsidecode — NBCS 2026 Part D Sec 5A, Table 27 (PDF p. 2269)
Car clear inside height2 200mmtypical — typical — confirm with the lift maker
Clear entrance height2 100mmtypical — typical — confirm with the lift maker
Pit depth1 800mmcode — NBCS 2026 Part D Sec 5A, Table 29 (PDF p. 2271) and Table 30 (PDF p. 2272)
Overhead (top landing floor to the well ceiling)4 800mmcode — NBCS 2026 Part D Sec 5A, Table 29 (PDF p. 2271) and Table 30 (PDF p. 2272)
CH + 2600 mm, CH = 2200 mm
Machineryhoisting machine inside the well, control system inside / adjacent to the top landing door — no machine roomcode — NBCS 2026 Part D Sec 5A, cl. 9.1 (PDF p. 2319)
Structural (raw) landing opening width1 200mmtypical — typical — confirm with the lift maker
Structural (raw) landing opening height2 250mmtypical — typical — confirm with the lift maker
Hoisting beam / hook at the well head (safe working load)50kNtypical — typical — confirm with the lift maker
Guide-rail fixingsguide-rail brackets at every floor and not more than about 2.5 m apart — a concrete band / insert channel or steel tie at each fixing level; divider beams between cars of a common well at every bracket leveltypical — typical — confirm with the lift maker
Landing opening clear height (min)2 000mmcode — NBCS 2026 Part D Sec 5A, cl. 6.1.1, 6.1.2 (PDF p. 2275–2277)
Pit floor design loadunder the buffers: 4 × the static load of the car (or counterweight) masscode — NBCS 2026 Part D Sec 5A, cl. 6.1.1, 6.1.2 (PDF p. 2275–2277)
Separator beam allowance between cars (min)150mmcode — NBCS 2026 Part D Sec 5A, cl. 5.10.2, 5.10.3.1 (PDF p. 2243)
Common well width (4 cars side by side)10 450mmcalculated
4 × 2500 + 3 × 150
Lift lobby depth (facing arrangement), minimum4 800mmcode — NBCS 2026 Part D Sec 5A, cl. 5.2 (PDF p. 2237–2238)
2 to 2.5 × car depth 2400 mm

Lift well plan

4LIFT WELL PLAN — 7 LIFT(S), FACING ARRANGEMENTTRUE SIZE — 1 DRAWING UNIT = 1 m (INSERT AT THE DRAWING SCALE)CAR 11 500 × 2 4001 000 CLEARWELL 2 500CAR 21 500 × 2 400CAR 31 500 × 2 400CAR 41 500 × 2 400COMMON WELL 10 450 (4 × 2 500 + 3 × 150 BEAM)WELL2 900LOBBY4 800 MINOPPOSITE ROW OF LIFTS / LOBBY EDGE (MINIMUM DEPTH)Counterweight: at the side

Lift well vertical section

5LIFT WELL VERTICAL SECTIONTRUE SIZE — 1 UNIT = 1 m (TRAVEL SHORTENED AT THE BREAK)MAIN LOBBY FFLLANDING +3.90 mLANDING +50.70 mTOP LANDING FFLCARBUFFERMACHINEPIT 1 800OVERHEAD 4 800FLOOR 3 900WELL 2 500NOTES1.Travel 54.60 m — 14 landingsabove the main lobby at 3.9 mfloor to floor.2.Pit depth 1 800 mm (code);overhead 4 800 mm from the toplanding floor to the underside ofthe well roof (code); car height 2200 mm.3.No machine room: machine in thewell head, controller cabinet atthe top landing.4.Hoisting beam / hook at the wellhead: 50 kN (typical).5.Guide-rail fixings at every floor(concrete band / insert channels);pit to be dry, with a ladder, light,socket and stop switch.6.Planning sizes only — the liftmaker's general arrangementdrawing governs before thestructure is frozen.Ref: NBCS 2026 Part D Section 5A(recommended dimensions); liftmaker's general arrangementdrawing governs

7. Code checks

CheckProvidedRequirementResultBasis
Fireman's liftbuilding height 58.5 mrequired: at least 1 — at least one fireman's lift per building; one per wing; one per bank of lifts; one per zone where no fireman's lift serves every floor (cl. 7.1.1 k)confirmcode — NBCS 2026 Part D Sec 5A, cl. 7.1.1, 7.1.2 (PDF p. 2294–2296)
Fireman's lift rated load1632 kg≥ 544 kg (8 persons)OKcode — NBCS 2026 Part D Sec 5A, cl. 7.1.1, 7.1.2 (PDF p. 2294–2296)
Fireman's lift car floor area3.60 m²≥ 1.43 m²OKcode — NBCS 2026 Part D Sec 5A, cl. 7.1.1, 7.1.2 (PDF p. 2294–2296)
Fireman's lift door (power operated)1000 mm≥ 800 mmOKcode — NBCS 2026 Part D Sec 5A, cl. 7.1.1, 7.1.2 (PDF p. 2294–2296)
Fireman's lift speed — top floor within 1 min1.6 m/s — 36 s over 54.6 m≥ 1 m/s and the top floor within 60 s → at least 1.00 m/s (next standard speed 1 m/s)OKcode — NBCS 2026 Part D Sec 5A, cl. 7.1.1, 7.1.2 (PDF p. 2294–2296)
Back-up supply to the fireman's liftto confirmautomatic change-over to an alternate supply; feeders in 2 h fire-rated enclosures up to the machine room / controllerconfirmcode — NBCS 2026 Part D Sec 5A, cl. 7.1.1, 7.1.2 (PDF p. 2294–2296)
Lift well enclosure and doorsto confirm on the drawingswell walls 2 h fire rating; vent at the top ≥ 0.2 m² per lift; landing doors 1 h (integrity)confirmcode — NBCS 2026 Part D Sec 5A, cl. 7.1.1, 7.1.2 (PDF p. 2294–2296)
Lift lobby / hoistway pressurisationlobby providedlobby 25–30 Pa; hoistway 50 Pa where no lift lobby is provided in air-conditioned buildings or where a funnel / flue effect may be createdconfirmcode — NBCS 2026 Part D (air conditioning, heating and mechanical ventilation) cl. 19.3.1.1, 19.3.2, 19.3.3 (PDF p. 2119–2120); NBCS 2026 Part F Fire and Life Safety, Table 5 (PDF p. 2783)
Emergency power for liftsto confirmfireman's lifts (including all lifts) on normal + standby generator supply with changeoverconfirmcode — NBCS 2026 Part F Fire and Life Safety, cl. 3.5.5.2 (PDF p. 2757)
Automatic rescue deviceto confirmbattery operated automatic rescue device (ARD) on all liftsconfirmcode — NBCS 2026 Part D Sec 5A, cl. 8.4.5 (PDF p. 2317)
Accessibility liftcar 1500 × 2400 mm, door 1000 mmall lifts open to the public: car size, door width, controls, handrails and communication per the accessibility good practice referred to — sizes are not given in this Section
typical size used here: 13-person car 2 000 × 1 100 mm with a 900 mm door (Table 14 row) — confirm with the accessibility standard referred to
confirmcode — NBCS 2026 Part D Sec 5A, cl. 9.4 (PDF p. 2319)

8. Electrical

ItemValueUnitBasis
Motor rating (each lift)15.1kWcalculated
kW = Q·v·(1 − balance)·g / (1000·η) — balance 50 %, efficiency 85 % (typical for VVVF gearless (PM machine))
Rated current (each lift)23.3Acalculated
3-phase 415 V, power factor 0.9
Starting / acceleration current41.9Atypical — typical — confirm with the lift maker
1.8 × rated current for VVVF gearless (PM machine)
Group diversity (7 lifts)0.65typical — typical — confirm with the lift maker
Group demand68.6kWcalculated
7 × 15.1 kW × 0.65
Group demand current106Acalculated
Auxiliaries (car light / fan, doors, well and machinery-space lighting)8.45kWtypical — typical — confirm with the lift maker
Generator load, all lifts running85.6kVAcalculated
Generator load with one lift starting104.8kVAtypical — typical — confirm with the lift maker
the largest lift accelerating while the others run
Heat released per lift (machine room / well head)1 530Wtypical — typical — confirm with the lift maker
heat released ≈ motor kW × (1 − efficiency) × duty 0.5 + 400 W per controller
Heat released, group10 711Wtypical — typical — confirm with the lift maker

Group diversity

Lifts in the groupDiversityDemand kWDemand A
1115.123.3
20.927.141.9
30.8538.459.4
40.848.274.5
50.7556.587.3
60.763.397.8
70.6568.6106
80.672.3111.8

typical — confirm with the lift maker

Lighting, sockets and circuits

WhereWhatBasis
Machine roomlighting at least 200 lux around the controller and machine, switch near the entrance; at least one plug socket per lift; room kept between 5 °C and 40 °Ccode — NBCS 2026 Part D Sec 5A, cl. 6.1.3 (PDF p. 2278–2281)
Lift well and pitlighting at least 50 lux 1 m above the car roof and the pit floor and 20 lux elsewhere; landings 50 lux at the doorscode — NBCS 2026 Part D Sec 5A, cl. 6.1.1, 6.1.2 (PDF p. 2275–2277)
Circuitscar lighting and ventilation; socket outlet on the car roof; lighting of machinery spaces; socket outlets in the machinery and pulley spaces and in the pit; lighting of the lift well including the pit; automatic rescue device — car light / well light supply independent of the power mains, separate switchgear for each liftcode — NBCS 2026 Part D Sec 5A, cl. 6.2.1, 6.2.2 (PDF p. 2282–2284)

Notes

References