Generated 28 Nov 2026 17:16 · NBCS 2026
7 lift(s) of 1,632 kg (24 persons) at 1.6 m/s — morning up-peak: interval 27.9 s, handling capacity 12.6 % in 5 minutes; average waiting time 24 s. Both targets are met.
| Item | Value | Basis |
|---|---|---|
| Building type | Office (multi-tenant) | |
| Code regime | NBCS 2026 | |
| Floors served above the main lobby | 14 | |
| Floor to floor / travel | 3.9 m / 54.6 m | |
| Population (design) | 1,636 persons | 14 floors × 1100 m² ÷ 8 m²/person (nbcs); occupancy at the peak 85 % |
| Target handling capacity (5 min) | 12.5 % (range 10–15 %) | code — NBCS 2026 Part D Sec 5A, cl. 4.2.1–4.2.9, Tables 1–5 (PDF p. 2225–2229) |
| Target interval | 35 s | code — NBCS 2026 Part D Sec 5A, cl. 4.2.1–4.2.9, Tables 1–5 (PDF p. 2225–2229) |
| Target average waiting time | 35 s | code — NBCS 2026 Part D Sec 5A, cl. 4.2.1–4.2.9, Tables 1–5 (PDF p. 2225–2229) |
| Item | Value |
|---|---|
| Lifts in the group | 7 |
| Rated load | 1,632 kg — 24 persons |
| Rated speed | 1.6 m/s — not less than 1 m/s for 14 floors; travel ÷ speed ≤ 35 s (NBCS 2026 Part D Sec 5A, cl. 4.5.1, Table 11 (PDF p. 2235); nominal travel time ≤ 35 s — NBCS 2026 Part D Sec 5A, cl. 4.2.1–4.2.9, Tables 1–5 (PDF p. 2225–2229)) |
| Average car load | 19.2 persons (80 % of the rated persons) |
| Door times (open / close) | 2 / 3 s (typical) — Centre opening, 2 panel |
| Single-floor flight / stop time | 4.04 s / T − tv = 7.10 s (acceleration 1 m/s², start delay 0.5 s) |
| Passenger transfer time | 1.2 s each way |
| Governing pattern | Morning up-peak |
| Pattern | Stops S | Reversal floor H | RTT s | Interval s | HC persons / 5 min | HC % of population | Check | Equation |
|---|---|---|---|---|---|---|---|---|
| Morning up-peak ◄ | 10.63 | 13.70 | 195.4 | 27.9 | 206 | 12.6 | OK | RTT = 2·H·tv + (S + 1)(T − tv) + 2·P·tp |
| Evening / morning down-peak | 10.63 | 13.70 | 125.0 | 17.9 | 322 | 19.7 | ≥ target | RTT = N·tv + (0.5·S + 1)(T − tv) + 2·P·tp |
| Mid-day (lunch) two-way | 10.63 | 13.70 | 309.8 | 44.3 | 260 | 15.9 | ≥ target | RTT = 2·H·tv + 2·S·(T − tv) + 4·P·tp |
◄ governing pattern for this building type. Mid-day split: incoming 45 % / outgoing 45 % / inter-floor 10 %.
| Measure | Value | How | Check |
|---|---|---|---|
| Average waiting time (governing pattern) | 23.7 s | AWT = [0.4 + (1.8·P/CC − 0.77)²] × INT (car loads 50–80 %) — factor 0.85 at P/CC = 0.80 | OK |
| Average transit time (up-peak) | 77.5 s | ATT = 0.5·H·tv + 0.5·S·(T − tv) + P·tp | |
| Average time to destination | 101.1 s | time to destination = AWT + ATT | |
| Nominal travel time | 34.1 s | travel ÷ rated speed | |
| Inter-floor waiting time | 14.0 s | AWT = INT_up-peak × (0.22 + 1.78 × A_interfloor / HC_up-peak) — inter-floor demand 2 % of the population in 5 min | OK |
code — average waiting time ≈ 75–85 % of the interval at 80 % car load — NBCS 2026 Part D Sec 5A, cl. 4.2.1–4.2.9, Tables 1–5 (PDF p. 2225–2229)
| Measure | Value | Grade | Basis |
|---|---|---|---|
| Interval | 27.9 s | Very good | code — NBCS 2026 Part D Sec 5A, cl. 4.2.1–4.2.9, Tables 1–5 (PDF p. 2225–2229) Table 3 |
| Average waiting time | 23.7 s | Premium class | code — NBCS 2026 Part D Sec 5A, cl. 4.2.1–4.2.9, Tables 1–5 (PDF p. 2225–2229) Table 4 |
| Nominal travel time | 34.1 s | Good | code — NBCS 2026 Part D Sec 5A, cl. 4.2.1–4.2.9, Tables 1–5 (PDF p. 2225–2229) Table 5 |
| Conventional | Destination control | |
|---|---|---|
| Probable stops S | 10.63 | 5.20 |
| Round trip time, s | 195.4 | 156.8 |
| Interval, s | 27.9 | 22.4 |
| 5-min handling capacity, persons | 206 | 257 |
| 5-min handling capacity, % of population | 12.6 | 15.7 |
destination grouping model: the stops of one trip are taken on N/√L floors (passengers for the same floors share a car); the reversal floor is unchanged — typical — confirm with the lift maker. Up-peak capacity gain about 25 %.
discrete-event simulation: Poisson arrivals with a 50 → 100 → 50 % ramp, directional collective control, trapezoidal motion, door / transfer times, capacity limit. Demand 12.5 % of the population in 5 minutes at the level part, 120 minutes, seed 1.
passenger generation for a simulation should be for 120 min and cover a minimum of 3 intervals of 5 min (cl. 4.2.1 b) — NBCS 2026 Part D Sec 5A, cl. 4.2.1–4.2.9, Tables 1–5 (PDF p. 2225–2229)
| Control | Pattern | Passengers | AWT s | 90th percentile wait s | Longest wait s | Waits over 60 s % | Transit s | Time to destination s | Lobby interval s | Car load at the lobby % | Not served at the end |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Conventional (collective) | Morning up-peak | 4,818 | 44.1 | 69.5 | 91 | 23.2 | 101.1 | 145.2 | 33.6 | 87 | 0 |
| Destination dispatch | Morning up-peak | 4,818 | 54.7 | 94.1 | 137 | 42.8 | 79.5 | 134.2 | 32.2 | 81 | 0 |
Calculated (analytic) interval 27.9 s and AWT 23.7 s for comparison.
| Item | Value | Unit | Basis |
|---|---|---|---|
| Rated load | 1 632 | kg | given 24 persons at 68 kg |
| Rated speed | 1.6 | m/s | given |
| Car inside width | 1 500 | mm | code — NBCS 2026 Part D Sec 5A, Table 27 (PDF p. 2269) |
| Car inside depth | 2 400 | mm | code — NBCS 2026 Part D Sec 5A, Table 27 (PDF p. 2269) |
| Clear entrance width | 1 000 | mm | code — NBCS 2026 Part D Sec 5A, Table 27 (PDF p. 2269) |
| Lift well width (clear plumb) | 2 500 | mm | code — NBCS 2026 Part D Sec 5A, Table 27 (PDF p. 2269) |
| Lift well depth (clear plumb) | 2 900 | mm | code — NBCS 2026 Part D Sec 5A, Table 27 (PDF p. 2269) |
| Counterweight position | side | code — NBCS 2026 Part D Sec 5A, Table 27 (PDF p. 2269) | |
| Car clear inside height | 2 200 | mm | typical — typical — confirm with the lift maker |
| Clear entrance height | 2 100 | mm | typical — typical — confirm with the lift maker |
| Pit depth | 1 800 | mm | code — NBCS 2026 Part D Sec 5A, Table 29 (PDF p. 2271) and Table 30 (PDF p. 2272) |
| Overhead (top landing floor to the well ceiling) | 4 800 | mm | code — NBCS 2026 Part D Sec 5A, Table 29 (PDF p. 2271) and Table 30 (PDF p. 2272) CH + 2600 mm, CH = 2200 mm |
| Machinery | hoisting machine inside the well, control system inside / adjacent to the top landing door — no machine room | code — NBCS 2026 Part D Sec 5A, cl. 9.1 (PDF p. 2319) | |
| Structural (raw) landing opening width | 1 200 | mm | typical — typical — confirm with the lift maker |
| Structural (raw) landing opening height | 2 250 | mm | typical — typical — confirm with the lift maker |
| Hoisting beam / hook at the well head (safe working load) | 50 | kN | typical — typical — confirm with the lift maker |
| Guide-rail fixings | guide-rail brackets at every floor and not more than about 2.5 m apart — a concrete band / insert channel or steel tie at each fixing level; divider beams between cars of a common well at every bracket level | typical — typical — confirm with the lift maker | |
| Landing opening clear height (min) | 2 000 | mm | code — NBCS 2026 Part D Sec 5A, cl. 6.1.1, 6.1.2 (PDF p. 2275–2277) |
| Pit floor design load | under the buffers: 4 × the static load of the car (or counterweight) mass | code — NBCS 2026 Part D Sec 5A, cl. 6.1.1, 6.1.2 (PDF p. 2275–2277) | |
| Separator beam allowance between cars (min) | 150 | mm | code — NBCS 2026 Part D Sec 5A, cl. 5.10.2, 5.10.3.1 (PDF p. 2243) |
| Common well width (4 cars side by side) | 10 450 | mm | calculated 4 × 2500 + 3 × 150 |
| Lift lobby depth (facing arrangement), minimum | 4 800 | mm | code — NBCS 2026 Part D Sec 5A, cl. 5.2 (PDF p. 2237–2238) 2 to 2.5 × car depth 2400 mm |
| Check | Provided | Requirement | Result | Basis |
|---|---|---|---|---|
| Fireman's lift | building height 58.5 m | required: at least 1 — at least one fireman's lift per building; one per wing; one per bank of lifts; one per zone where no fireman's lift serves every floor (cl. 7.1.1 k) | confirm | code — NBCS 2026 Part D Sec 5A, cl. 7.1.1, 7.1.2 (PDF p. 2294–2296) |
| Fireman's lift rated load | 1632 kg | ≥ 544 kg (8 persons) | OK | code — NBCS 2026 Part D Sec 5A, cl. 7.1.1, 7.1.2 (PDF p. 2294–2296) |
| Fireman's lift car floor area | 3.60 m² | ≥ 1.43 m² | OK | code — NBCS 2026 Part D Sec 5A, cl. 7.1.1, 7.1.2 (PDF p. 2294–2296) |
| Fireman's lift door (power operated) | 1000 mm | ≥ 800 mm | OK | code — NBCS 2026 Part D Sec 5A, cl. 7.1.1, 7.1.2 (PDF p. 2294–2296) |
| Fireman's lift speed — top floor within 1 min | 1.6 m/s — 36 s over 54.6 m | ≥ 1 m/s and the top floor within 60 s → at least 1.00 m/s (next standard speed 1 m/s) | OK | code — NBCS 2026 Part D Sec 5A, cl. 7.1.1, 7.1.2 (PDF p. 2294–2296) |
| Back-up supply to the fireman's lift | to confirm | automatic change-over to an alternate supply; feeders in 2 h fire-rated enclosures up to the machine room / controller | confirm | code — NBCS 2026 Part D Sec 5A, cl. 7.1.1, 7.1.2 (PDF p. 2294–2296) |
| Lift well enclosure and doors | to confirm on the drawings | well walls 2 h fire rating; vent at the top ≥ 0.2 m² per lift; landing doors 1 h (integrity) | confirm | code — NBCS 2026 Part D Sec 5A, cl. 7.1.1, 7.1.2 (PDF p. 2294–2296) |
| Lift lobby / hoistway pressurisation | lobby provided | lobby 25–30 Pa; hoistway 50 Pa where no lift lobby is provided in air-conditioned buildings or where a funnel / flue effect may be created | confirm | code — NBCS 2026 Part D (air conditioning, heating and mechanical ventilation) cl. 19.3.1.1, 19.3.2, 19.3.3 (PDF p. 2119–2120); NBCS 2026 Part F Fire and Life Safety, Table 5 (PDF p. 2783) |
| Emergency power for lifts | to confirm | fireman's lifts (including all lifts) on normal + standby generator supply with changeover | confirm | code — NBCS 2026 Part F Fire and Life Safety, cl. 3.5.5.2 (PDF p. 2757) |
| Automatic rescue device | to confirm | battery operated automatic rescue device (ARD) on all lifts | confirm | code — NBCS 2026 Part D Sec 5A, cl. 8.4.5 (PDF p. 2317) |
| Accessibility lift | car 1500 × 2400 mm, door 1000 mm | all lifts open to the public: car size, door width, controls, handrails and communication per the accessibility good practice referred to — sizes are not given in this Section typical size used here: 13-person car 2 000 × 1 100 mm with a 900 mm door (Table 14 row) — confirm with the accessibility standard referred to | confirm | code — NBCS 2026 Part D Sec 5A, cl. 9.4 (PDF p. 2319) |
| Item | Value | Unit | Basis |
|---|---|---|---|
| Motor rating (each lift) | 15.1 | kW | calculated kW = Q·v·(1 − balance)·g / (1000·η) — balance 50 %, efficiency 85 % (typical for VVVF gearless (PM machine)) |
| Rated current (each lift) | 23.3 | A | calculated 3-phase 415 V, power factor 0.9 |
| Starting / acceleration current | 41.9 | A | typical — typical — confirm with the lift maker 1.8 × rated current for VVVF gearless (PM machine) |
| Group diversity (7 lifts) | 0.65 | typical — typical — confirm with the lift maker | |
| Group demand | 68.6 | kW | calculated 7 × 15.1 kW × 0.65 |
| Group demand current | 106 | A | calculated |
| Auxiliaries (car light / fan, doors, well and machinery-space lighting) | 8.45 | kW | typical — typical — confirm with the lift maker |
| Generator load, all lifts running | 85.6 | kVA | calculated |
| Generator load with one lift starting | 104.8 | kVA | typical — typical — confirm with the lift maker the largest lift accelerating while the others run |
| Heat released per lift (machine room / well head) | 1 530 | W | typical — typical — confirm with the lift maker heat released ≈ motor kW × (1 − efficiency) × duty 0.5 + 400 W per controller |
| Heat released, group | 10 711 | W | typical — typical — confirm with the lift maker |
| Lifts in the group | Diversity | Demand kW | Demand A |
|---|---|---|---|
| 1 | 1 | 15.1 | 23.3 |
| 2 | 0.9 | 27.1 | 41.9 |
| 3 | 0.85 | 38.4 | 59.4 |
| 4 | 0.8 | 48.2 | 74.5 |
| 5 | 0.75 | 56.5 | 87.3 |
| 6 | 0.7 | 63.3 | 97.8 |
| 7 | 0.65 | 68.6 | 106 |
| 8 | 0.6 | 72.3 | 111.8 |
typical — confirm with the lift maker
| Where | What | Basis |
|---|---|---|
| Machine room | lighting at least 200 lux around the controller and machine, switch near the entrance; at least one plug socket per lift; room kept between 5 °C and 40 °C | code — NBCS 2026 Part D Sec 5A, cl. 6.1.3 (PDF p. 2278–2281) |
| Lift well and pit | lighting at least 50 lux 1 m above the car roof and the pit floor and 20 lux elsewhere; landings 50 lux at the doors | code — NBCS 2026 Part D Sec 5A, cl. 6.1.1, 6.1.2 (PDF p. 2275–2277) |
| Circuits | car lighting and ventilation; socket outlet on the car roof; lighting of machinery spaces; socket outlets in the machinery and pulley spaces and in the pit; lighting of the lift well including the pit; automatic rescue device — car light / well light supply independent of the power mains, separate switchgear for each lift | code — NBCS 2026 Part D Sec 5A, cl. 6.2.1, 6.2.2 (PDF p. 2282–2284) |