| Group | Input | Value | Unit |
|---|---|---|---|
| Building | Building type | Office (single tenant) | |
| Building | Floors served above the main lobby | 12 | |
| Building | Interfloor height | 3.6 | m |
| Building | Population from | Net area per floor ÷ density | |
| Building | Net usable area per floor | 1200 | m² |
| Building | Occupancy density (0 = typical for the type) | 0 | m²/person |
| Building | Occupancy at the peak (0 = typical) | 0 | % |
| Building | Express travel to the first served floor (high zone) | 0 | m |
| Lifts | Rated load (0 = select) | Select automatically | |
| Lifts | Rated speed (0 = by travel) | By travel height (typical) | |
| Lifts | Number of lifts (0 = select) | 0 | |
| Lifts | Average car load at up-peak | 80 | % |
| Lifts | Acceleration | 1.0 | m/s² |
| Lifts | Door opening time | 2.0 | s |
| Lifts | Door closing time | 3.0 | s |
| Lifts | Start delay | 0.5 | s |
| Lifts | Passenger transfer time (each way) | 1.2 | s |
| Targets and load | Target 5-minute handling capacity (0 = typical for the type) | 0 | % |
| Targets and load | Target interval (0 = typical for the type) | 0 | s |
| Targets and load | Counterweight balance | 50 | % |
| Targets and load | Drive + machine efficiency | 80 | % |
| Targets and load | Supply power factor | 0.9 | |
| Patterns, sizes and code checks | Code regime | India — NBCS 2026 | |
| Patterns, sizes and code checks | Traffic pattern to check | By building type | |
| Patterns, sizes and code checks | Lunch split in / out / inter-floor | 45,45,10 | |
| Patterns, sizes and code checks | Lift class (sizes) | By building type | |
| Patterns, sizes and code checks | Drive | By speed (MRL up to 2 m/s) |
| Item | Value | Unit | Note / basis |
|---|---|---|---|
| Population at the peak U | 1152.0 | persons | 1,200 m² ÷ 10 m²/person = 120.0 persons per floor × 12 floors × 80 % occupancy |
| Rated load / persons | 1275 kg / 17 | persons = Q / 75 kg (EN 81-20 convention) | |
| Average passengers P | 13.6 | 80 % of 17 | |
| Rated speed | 2.0 | m/s | travel 43.2 m — chosen by travel (typical) |
| Probable stops S | 8.33 | ||
| Highest reversal floor H | 11.59 | ||
| Interfloor flight tv | 1.8 | s | |
| Time lost per stop ts | 7.49 | s | single-floor flight − tv + doors + start delay |
| Round trip time RTT | 144.24 | s | |
| Number of lifts L | 5 | ||
| Interval INT = RTT / L | 28.85 | s | target ≤ 30 s |
| 5-min handling capacity | 141.44 | persons | |
| %POP | 12.28 | % | target ≥ 12 % |
| Item | Value | Unit | Note / basis |
|---|---|---|---|
| Motor power per lift (typical) | 15.63 | kW | Q·v·(1 − 0.5)·g / (1000·0.8) |
| Supply per lift | 17.37 | kVA | at pf 0.9 |
| Group running load | 58.63 | kW | 5 × 15.6 kW × diversity 0.75 (typical) |
| Feeder design current per lift (typical) | 36.25 | A | × 1.5 for acceleration current, 415 V 3-phase (typical); confirm with the maker |
| Starting / acceleration current (typical) | 46.4 | A | 1.8 × rated current, VVVF gearless (PM machine) |
| Heat released per lift (typical) | 2067.7 | W | to the machine room / well head |
| Item | Value | Unit | Note / basis |
|---|---|---|---|
| Morning up-peak — interval | 28.85 | s | RTT 144.2 s; handling capacity 12.3 % in 5 min; RTT = 2·H·tv + (S + 1)(T − tv) + 2·P·tp |
| Evening / morning down-peak — interval | 18.59 | s | RTT 92.9 s; handling capacity 19.1 % in 5 min; RTT = N·tv + (0.5·S + 1)(T − tv) + 2·P·tp |
| Mid-day (lunch) two-way — interval | 46.35 | s | RTT 231.8 s; handling capacity 15.3 % in 5 min; RTT = 2·H·tv + 2·S·(T − tv) + 4·P·tp |
| Inter-floor waiting time | 14.71 | s | AWT = INT_up-peak × (0.22 + 1.78 × A_interfloor / HC_up-peak) |
| Item | Value | Unit | Note / basis |
|---|---|---|---|
| Average waiting time | 21.58 | s | AWT = [0.4 + (1.8·P/CC − 0.77)²] × INT (car loads 50–80 %) — target ≤ 35 s |
| Average transit time | 57.94 | s | ATT = 0.5·H·tv + 0.5·S·(T − tv) + P·tp |
| Time to destination | 79.52 | s | time to destination = AWT + ATT |
| Nominal travel time | 21.6 | s | travel ÷ rated speed |
| Grade — interval | Very good | code: NBCS 2026 Part D Sec 5A, cl. 4.2.1–4.2.9, Tables 1–5 (PDF p. 2225–2229) Table 3 | |
| Grade — average waiting time | Premium class | code: NBCS 2026 Part D Sec 5A, cl. 4.2.1–4.2.9, Tables 1–5 (PDF p. 2225–2229) Table 4 | |
| Grade — nominal travel time | Excellent | code: NBCS 2026 Part D Sec 5A, cl. 4.2.1–4.2.9, Tables 1–5 (PDF p. 2225–2229) Table 5 | |
| Destination control — interval | 23.93 | s | handling capacity 14.8 %; destination grouping model: the stops of one trip are taken on N/√L floors (passengers for the same floors share a car); the reversal floor is unchanged (typical) |
| Item | Value | Unit | Note / basis |
|---|---|---|---|
| Rated load | 1360 | kg | calculated |
| Rated speed | 2.0 | m/s | given |
| Car inside width | 1700 | mm | code: NBCS 2026 Part D Sec 5A, Table 27 (PDF p. 2269) |
| Car inside depth | 1800 | mm | code: NBCS 2026 Part D Sec 5A, Table 27 (PDF p. 2269) |
| Clear entrance width | 1000 | mm | code: NBCS 2026 Part D Sec 5A, Table 27 (PDF p. 2269) |
| Lift well width (clear plumb) | 2550 | mm | code: NBCS 2026 Part D Sec 5A, Table 27 (PDF p. 2269) |
| Lift well depth (clear plumb) | 2350 | mm | code: NBCS 2026 Part D Sec 5A, Table 27 (PDF p. 2269) |
| Counterweight position | side | code: NBCS 2026 Part D Sec 5A, Table 27 (PDF p. 2269) | |
| Car clear inside height | 2200 | mm | typical: typical — confirm with the lift maker |
| Clear entrance height | 2100 | mm | typical: typical — confirm with the lift maker |
| Pit depth | 2200 | mm | code: NBCS 2026 Part D Sec 5A, Table 29 (PDF p. 2271) and Table 30 (PDF p. 2272) |
| Overhead (top landing floor to the well ceiling) | 4900 | mm | code: NBCS 2026 Part D Sec 5A, Table 29 (PDF p. 2271) and Table 30 (PDF p. 2272) |
| Machinery | hoisting machine inside the well, control system inside / adjacent to the top landing door — no machine room | code: NBCS 2026 Part D Sec 5A, cl. 9.1 (PDF p. 2319) | |
| Structural (raw) landing opening width | 1200 | mm | typical: typical — confirm with the lift maker |
| Structural (raw) landing opening height | 2250 | mm | typical: typical — confirm with the lift maker |
| Hoisting beam / hook at the well head (safe working load) | 30 | kN | typical: typical — confirm with the lift maker |
| Guide-rail fixings | guide-rail brackets at every floor and not more than about 2.5 m apart — a concrete band / insert channel or steel tie at each fixing level; divider beams between cars of a common well at every bracket level | typical: typical — confirm with the lift maker | |
| Landing opening clear height (min) | 2000 | mm | code: NBCS 2026 Part D Sec 5A, cl. 6.1.1, 6.1.2 (PDF p. 2275–2277) |
| Pit floor design load | under the buffers: 4 × the static load of the car (or counterweight) mass | code: NBCS 2026 Part D Sec 5A, cl. 6.1.1, 6.1.2 (PDF p. 2275–2277) | |
| Separator beam allowance between cars (min) | 150 | mm | code: NBCS 2026 Part D Sec 5A, cl. 5.10.2, 5.10.3.1 (PDF p. 2243) |
| Common well width (3 cars side by side) | 7950 | mm | calculated |
| Lift lobby depth (facing arrangement), minimum | 3600 | mm | code: NBCS 2026 Part D Sec 5A, cl. 5.2 (PDF p. 2237–2238) |
| Lifts | Load kg | Persons | RTT s | Interval s | 5-min HC % | Meets |
|---|---|---|---|---|---|---|
| 1 | 1000 | 13 | 127.0 | 127.0 | 2.1 | — |
| 1 | 1275 | 17 | 144.2 | 144.2 | 2.5 | — |
| 1 | 1600 | 21 | 159.1 | 159.1 | 2.8 | — |
| 1 | 1800 | 24 | 169.0 | 169.0 | 3.0 | — |
| 1 | 2000 | 26 | 175.2 | 175.2 | 3.1 | — |
| 1 | 2500 | 33 | 194.6 | 194.6 | 3.5 | — |
| 2 | 1000 | 13 | 127.0 | 63.5 | 4.3 | — |
| 2 | 1275 | 17 | 144.2 | 72.1 | 4.9 | — |
| 2 | 1600 | 21 | 159.1 | 79.5 | 5.5 | — |
| 2 | 1800 | 24 | 169.0 | 84.5 | 5.9 | — |
| 2 | 2000 | 26 | 175.2 | 87.6 | 6.2 | — |
| 2 | 2500 | 33 | 194.6 | 97.3 | 7.1 | — |
| 3 | 1000 | 13 | 127.0 | 42.3 | 6.4 | — |
| 3 | 1275 | 17 | 144.2 | 48.1 | 7.4 | — |
| 3 | 1600 | 21 | 159.1 | 53.0 | 8.3 | — |
| 3 | 1800 | 24 | 169.0 | 56.3 | 8.9 | — |
| 3 | 2000 | 26 | 175.2 | 58.4 | 9.3 | — |
| 3 | 2500 | 33 | 194.6 | 64.9 | 10.6 | — |
| 4 | 1000 | 13 | 127.0 | 31.7 | 8.5 | — |
| 4 | 1275 | 17 | 144.2 | 36.1 | 9.8 | — |
| 4 | 1600 | 21 | 159.1 | 39.8 | 11.0 | — |
| 4 | 1800 | 24 | 169.0 | 42.2 | 11.8 | — |
| 4 | 2000 | 26 | 175.2 | 43.8 | 12.4 | — |
| 4 | 2500 | 33 | 194.6 | 48.6 | 14.1 | — |
| 5 | 1000 | 13 | 127.0 | 25.4 | 10.7 | — |
| 5 | 1275 | 17 | 144.2 | 28.8 | 12.3 | yes |
| 5 | 1600 | 21 | 159.1 | 31.8 | 13.8 | — |
| 5 | 1800 | 24 | 169.0 | 33.8 | 14.8 | — |
| 5 | 2000 | 26 | 175.2 | 35.0 | 15.5 | — |
| 5 | 2500 | 33 | 194.6 | 38.9 | 17.7 | — |
| 6 | 1000 | 13 | 127.0 | 21.2 | 12.8 | yes |
| 6 | 1275 | 17 | 144.2 | 24.0 | 14.7 | yes |
| 6 | 1600 | 21 | 159.1 | 26.5 | 16.5 | yes |
| 6 | 1800 | 24 | 169.0 | 28.2 | 17.8 | yes |
| 6 | 2000 | 26 | 175.2 | 29.2 | 18.6 | yes |
| 6 | 2500 | 33 | 194.6 | 32.4 | 21.2 | — |
| 7 | 1000 | 13 | 127.0 | 18.1 | 14.9 | yes |
| 7 | 1275 | 17 | 144.2 | 20.6 | 17.2 | yes |
| 7 | 1600 | 21 | 159.1 | 22.7 | 19.3 | yes |
| 7 | 1800 | 24 | 169.0 | 24.1 | 20.7 | yes |
| Check | Result | Note |
|---|---|---|
| Interval 28.8 s ≤ 30 s | PASS | target typical for the building type unless entered |
| 5-minute handling capacity 12.3 % ≥ 12 % | PASS | up-peak, target typical unless entered |
| Fireman's lift rated load: 1360 kg | PASS | ≥ 544 kg (8 persons) — code: NBCS 2026 Part D Sec 5A, cl. 7.1.1, 7.1.2 (PDF p. 2294–2296) |
| Fireman's lift car floor area: 3.06 m² | PASS | ≥ 1.43 m² — code: NBCS 2026 Part D Sec 5A, cl. 7.1.1, 7.1.2 (PDF p. 2294–2296) |
| Fireman's lift door (power operated): 1000 mm | PASS | ≥ 800 mm — code: NBCS 2026 Part D Sec 5A, cl. 7.1.1, 7.1.2 (PDF p. 2294–2296) |
| Fireman's lift speed — top floor within 1 min: 2 m/s — 24 s over 43.2 m | PASS | ≥ 1 m/s and the top floor within 60 s → at least 1.00 m/s (next standard speed 1 m/s) — code: NBCS 2026 Part D Sec 5A, cl. 7.1.1, 7.1.2 (PDF p. 2294–2296) |
Results are design aids computed by designlink calc (calc.designlink.in) and must be reviewed by a qualified engineer before issue. Ground levels marked "assumed" have no survey level within reach — verify.