Lightning protection (IEC 62305)
Sample project — Tower A · Electrical
Generated 28 Nov 2026 16:09 Risk R1 per IEC 62305-2 (collection areas, dangerous events, probabilities, losses) agains… Project code SAMPLE
Surrounded by objects of same height or smaller (0.5)
Structure
Use of the structure
Residential / apartments
Structure
Persons in the structure (nz)
400
Structure
Construction
RCC frame (rebar can serve as natural down conductor)
Structure
Roof
Flat RCC with parapet
Lightning density
Place (NBCS 2026 / NBC 2016 cl. 11.8 thunderstorm days → Ng = 0.1 Td)
Delhi — Td 30
Risk factors (IEC 62305-2 Annex B/C)
Fire risk rf
Ordinary — 400–800 MJ/m² (0.01)
Risk factors (IEC 62305-2 Annex B/C)
Fire provisions rp
Extinguishers, hydrants, manual alarm, fire brigade < 10 min (0.5)
Risk factors (IEC 62305-2 Annex B/C)
Floor surface (touch/step) rt
Marble, ceramic tiles (10⁻³)
Risk factors (IEC 62305-2 Annex B/C)
Touch-voltage measures PTA
None (1)
Risk factors (IEC 62305-2 Annex B/C)
Environment of incoming lines CE
Urban (0.1)
Risk factors (IEC 62305-2 Annex B/C)
Power line
Buried cable
Risk factors (IEC 62305-2 Annex B/C)
Power line length (from last pole / transformer)
500
m
Risk factors (IEC 62305-2 Annex B/C)
HV/LV transformer at the structure (CT = 0.2)
True
Risk factors (IEC 62305-2 Annex B/C)
Telecom / data line
Buried
Risk factors (IEC 62305-2 Annex B/C)
Telecom line length
500
m
Risk factors (IEC 62305-2 Annex B/C)
Coordinated SPD protection on lines (PEB)
Auto — SPD level to match the LPS class
Risk factors (IEC 62305-2 Annex B/C)
Tolerable risk RT
1e-05
/yr
Risk factors (IEC 62305-2 Annex B/C)
Tolerable frequency of damage FT (internal systems, IEC 62305-2 : 2024)
0.1
/yr
LPS design
Code edition
NBCS 2026 (SP 7:2026) Part D Sec 2 — IEC 62305 : 2024
LPS design
Class of LPS
Auto — lowest class that brings R1 ≤ RT
LPS design
Air-termination method
Mesh on the roof + rods at corners / protrusions
LPS design
Air-termination rod height
1.0
m
LPS design
Conductor material
Hot-dip galvanised steel strip / rod
LPS design
Soil resistivity ρ
100
Ω·m
LPS design
Target earth resistance
10
Ω
2. Results
Dangerous events (IEC 62305-2 Annex A)
Item
Value
Unit
Note / basis
Ground flash density Ng
3.0
/km²·yr
Delhi — Td 30 (NBCS 11.8), Ng = 0.1·Td
Collection area of the structure Ad
51525.13
m²
L·W + 2·3H·(L+W) + π(3H)²
Location factor Cd
0.5
Flashes to the structure ND
7.729e-02
/yr
Flashes near the structure NM
2.611e+00
/yr
Am within 500 m
Power line (buried, 500 m): NL / NI
6.00e-04 / 6.00e-02
/yr
AL = 20000 m², AI = 2000000 m²
Telecom line (buried, 500 m): NL / NI
3.00e-03 / 3.00e-01
/yr
AL = 20000 m², AI = 2000000 m²
Loss factors (Annex C)
Item
Value
Unit
Note / basis
Loss by fire LF (type of structure)
0.01
Panic / evacuation factor hz
5
Fire risk rf
0.01
Fire provisions rp
0.5
Floor surface rt
0.001
LA = rt·LT (touch/step)
1.00e-05
LB = rp·rf·hz·LF (physical damage)
2.50e-04
Risk components with LPS class IV, SPD III (Annex B)
Item
Value
Unit
Note / basis
PB (LPS)
0.2
PEB (SPD on lines)
0.05
RA — injury by touch/step near the structure
1.55e-07
/yr
RB — physical damage, flash to structure
3.86e-06
/yr
RU — injury, flash to line
1.80e-09
/yr
RV — physical damage, flash to line
4.50e-08
/yr
R1 total
4.07e-06
/yr
Tolerable RT
1e-05
/yr
Frequency of damage F = FC + FM + FW + FZ (indicative)
3.21e-02
/yr
FC 3.9e-03 · FM 2.1e-02 · FW 1.8e-04 · FZ 7.2e-03; FT 0.1
Air termination — class IV
Item
Value
Unit
Note / basis
Rolling sphere radius
60
m
Mesh size
20 × 20
m
Mesh conductors along L / along W
3 / 4
nos
including the perimeter conductor on the parapet
Mesh conductor length
280.0
m
Rod height
1.0
m
Protective angle at 1 m
79.0
°
Rod protected radius at roof level
5.14
m
Max rod spacing (rolling sphere)
21.82
m
Air-termination rods
4
nos
at the four corners + one per protrusion
Protrusion 4 m: rod 5.0 m, α = 73.0°, protected radius
16.35
m
Down conductors
Item
Value
Unit
Note / basis
Perimeter
170.0
m
Typical spacing (NBCS Table 4)
20
m
Number of down conductors
10
nos
one at each corner, each facade split ≤ 20 m (largest gap 20.0 m)
Natural down conductors
RCC rebars / steel columns — electrically continuous, tied at every floor, test joints at 0.5 m AFL
Conductor
GI strip 25 × 3 mm (75 mm²) / 8 mm dia rod — Table 7 min. 50 mm²
Separation distance s in air (kc = 0.44, km = 1)
0.528
m
to unbonded metal on the roof / facade
Separation distance through concrete / brick (km = 0.5)
1.06
m
Earth termination — Type B ring
Item
Value
Unit
Note / basis
Soil resistivity
100.0
Ω·m
Minimum vertical electrode length (NBCS Table 5)
2.5
m
Ring 1 m from the walls, 0.5 m deep
62 × 27
m
length 178 m
Mean radius re
23.08
m
Extra vertical electrode length per down conductor
0.0
m
Ring resistance
3.3
Ω
3 m rod resistance (each)
31.13
Ω
Combined with 10 rods at the down conductors
1.6
Ω
Electrode material
GI strip 25 × 6 mm or 16 mm dia rod (Table 8: steel tape 90 mm² / rod 14 mm)
Bonding
ring bonded to the building earth mat / power earth, main equipotential bar at each down conductor test joint (IEC 62305-3 §6); all earthing interconnected (NBCS 8.2.20)
6. Tolerable risk: R1 ≤ RT = 1e-05 → without LPS 2.10e-05; with class IV + SPD III: 4.07e-06 PASS
7. Frequency of damage (indicative): F ≤ FT = 0.1 /yr → 3.9e-03 + 2.1e-02 + 1.8e-04 + 7.2e-03 = 3.21e-02 PASS(IEC 62305-2 : 2024)
Class IV — mesh, down conductors and separation distance
the class chosen above applied to this roof
Given: Class IV (NBCS Tables 3, 4) sphere r = 60 m, mesh 20 m, DC spacing 20 m, ki 0.04
1. Sphere sag between mesh conductors: d = r − √(r² − (m/2)²) = 60 − √(60² − 10²) = 839 mm
2. Down conductors (a DC at every corner): n = 2·⌈L / s⌉ + 2·⌈W / s⌉ = 2·⌈60 / 20⌉ + 2·⌈25 / 20⌉ = 2·3 + 2·2 = 10 nos(same rule as the LPS layout and CAD tools)
3. Separation distance: s = ki · kc / km · l = 0.04 · 0.44 / 1 · 30 = 0.53 m
Earth termination — Type B ring + rods
ρ = 100 Ω·m
1. Ring mean radius: re = √(Aring / π) = √(62 · 27 / π) = 23.08 m
2. Minimum electrode length (NBCS Table 5, 11.6.3.2): re ≥ 2.5 m (class IV, ρ 100 Ω·m) → 23.1 m PASS
Single-zone simplified R1 with the IEC 62305-2 Annex B/C probabilities and losses (2010 values, unchanged in principle in the 2024 edition); for mixed-use towers, zones with different floor / fire / panic factors reduce R1 — run the full multi-zone assessment for hospitals, explosive areas and heritage buildings.
Frequency of damage F (IEC 62305-2 : 2024, internal systems) is indicative: F = ND·PC + NM·PM + ΣNL·PW + ΣNI·PZ with unshielded wiring (Uw 2.5 kV) and the SPD probability; compare with the owner's tolerable FT.
Ng = 0.1 × Td with Td from the NBCS 2026 cl. 11.8 table (Delhi: 30 days); IEC 62305-2 : 2024 works with the ground strike-point density NSG — enter a measured lightning-location-network value under Custom where available.
RCC rebars as natural down conductors need ≥ 50 % of bars electrically continuous (welded / clamped laps), overall resistance ≤ 0.2 Ω (NBCS 11.5) and documented test joints — IEC 62305-3 §5.3.5 / E.4.3.
IEC 62305-2 : 2024 risk (R1) and frequency of damage — NBCS 11.2 (b), 11.4: no height threshold; IS 2309 withdrawn.
6. Standards and references
IEC 62305-1..4:2010 / IS/IEC 62305 — Protection against lightning: SPD type 1/2 selection, risk assessment (future)
IEC 61643-11:2011 — Surge protective devices connected to low-voltage power systems: SPD ratings (Iimp, In, Up)
IS 3043:2018 — Code of practice for earthing: Earth bus, strip sizing, earthing of panels (future earthing tool)
CEA (Measures relating to Safety and Electric Supply) Regulations, 2023 — Central Electricity Authority safety regulations: Statutory safety requirements for installations
NBCS 2026 (SP 7:2026) Part D Sec 2 — National Building Construction Standards — Electrical and allied installations: Load assessment and diversity, circuits, cables (4-core), earthing, lightning protection, standby supply for fire & life-safety loads
Prepared by
Checked by
Approved by
Results are design aids computed by designlink calc (calc.designlink.in) and must be reviewed by a qualified engineer before issue. Ground levels marked "assumed" have no survey level within reach — verify.