Line voltage regulation & technical losses

Sample project — Tower A · Electrical
Generated 28 Nov 2026 17:16
Voltage drop / regulation and I²R losses of an 11 kV / 33 kV / LT overhead line or cable w…
Project code SAMPLE
Current
154.4 A
Voltage drop
7.244 %
Peak loss
122.2 kW
Energy loss
3.177 % of energy sent

1. Inputs

GroupInputValueUnit
LineLine voltage11kV
LineLength8km
LineConductorRabbit 6/1 × 3.35
LineReactance0.38Ω/km
LineConductor temperature65°C
LoadPeak load2500kW
LoadPower factor0.85
LoadLoadUniformly spread along the line
LoadAnnual load factor0.5
LoadAllowed voltage drop9%
LoadEnergy cost6.0₹/kWh

2. Results

Line data

ItemValueUnitNote / basis
ConductorRabbit 6/1 × 3.35
R at 20 °C0.5426Ω/kmIS 398-2 values, typical — use the maker's
R at 65 °C0.641Ω/km
X0.38Ω/km

Results

ItemValueUnitNote / basis
Load current154.37A
Voltage drop796.82V
Voltage drop7.24%
Regulation (on receiving-end voltage)7.81%
Peak power loss122.2kW4.89 % of the load
Loss load factor0.3250.3·LF + 0.7·LF² (typical)
Annual energy loss347913.57kWh
Annual loss cost2087481.43₹

3. Checks

CheckResultNote
Voltage drop 7.24 % ≤ 9 %PASS

4. Worked example

I = 2500 / (√3 × 11 × 0.85) = 154.4 A; R65 = 0.5426 × (1 + 0.00403 × 45) = 0.6410 Ω/km
ΔV = √3 × 154.4 × (0.6410 × 0.85 + 0.38 × 0.527) × 8 km × ½ (uniform load) = 797 V = 7.24 %
Loss = 3 × 154.4² × 0.6410 × 8 × ⅓ = 122.2 kW

5. Notes

6. Standards and references

Prepared by
Checked by
Approved by

Results are design aids computed by designlink calc (calc.designlink.in) and must be reviewed by a qualified engineer before issue. Ground levels marked "assumed" have no survey level within reach — verify.