Lighting design — illuminance & uniformity

Sample project — Tower A · Indian regime · 4 rooms · 39 luminaires
Generated 28 Nov 2026 16:03
Photometric point-by-point + radiosity
Project code SAMPLE
Rooms
4
Luminaires
39
Emergency (E)
16
Area
350.4 m²
Connected load
1.23 kW
LPD
3.51 W/m²
Rooms failing
3
One or more luminaires use the generic (synthetic cosⁿ) distribution. Upload the manufacturer's IES / LDT file and re-run before submission.

1. Design basis

ItemValueSource
Code regimeIndian — NBCS 2026 (SP 7:2026) Part D Sec 1 Table 6, IS 3646-1:2025, SP 72:2025; emergency lighting NBCS 2026 Part F 3.5.6.1; ECSBC 2024 Table 7.4 (ECSBC)project
Code editionNBCS 2026 (SP 7:2026, in force from 30 Apr 2026) — Ēm = middle value of the Table 6 range (cl. 4.1.4.3), Uo, Ra and RUGL per ref no.project
Utility (stores, plant, electrical, stairs)MF 0.8 · reflectance ceiling 30 % / walls 20 % / floor 10 % · mounting 3.0 m · plane per room typedesign-basis profile
Enclosed (offices, toilets, lobbies, passages)MF 0.85 · reflectance ceiling 50 % / walls 30 % / floor 20 % · mounting 3.0 m · plane per room typedesign-basis profile
Parking & drivewayMF 0.8 · reflectance ceiling 30 % / walls 20 % / floor 10 % · mounting 2.5 m · plane per room typedesign-basis profile
Outdoor (no reflectance)MF 0.8 · reflectance ceiling 0 % / walls 0 % / floor 10 % · mounting 6.0 m · plane per room typedesign-basis profile
Uniformity targetUo ≥ 0.7 for all areas (standard's value where higher); parking, driveway and corridors: the standard's Uoproject / PMC
Calculation gridEN 12464-1 §4.4 grid at cell centres, wall zone 0.0 mEN 12464-1:2021
MethodDirect illuminance point-by-point from the luminaire's photometric file (I(C,γ)·cos θ / d²), interreflected component by radiosity between ceiling, walls and floor; all values × maintenance factorCIE 52 / IES LM-63 / EULUMDAT
Emergency lightingenabled — escape routes 10 lx on the centre line at floor level and ≥ 5 lx over 50 % of the width (routes ≤ 2 m wide), open areas 5 lx, assembly floors during performances 2 lx; duration ≥ 90 min, on within 5 s (NBCS 2026 Part F 3.5.6.1 f)); battery packs not in lieu of a DG-backed supply (g), ratio not checked; luminaires marked E stay onNBCS 2026 Part F 3.5.6.1 d), f)
Lighting power densityECSBC 2024 Table 7.4 (ECSBC) space-function limits — the same table as the energy-code toolenergy code

2. Luminaire list

ManufacturerModelDescriptionWlmlm/WQtyof which ERooms
Generic (designlink)PANEL-600-36LED panel 600×600, 36 W generic36.04,000111.12041
Generic (designlink)DL-15LED downlight 15 W generic15.01,500100.0951
Generic (designlink)PARK-36LED car-park luminaire 36 W generic36.04,300119.4661
Generic (designlink)BATTEN-40LED batten 1200 mm, 40 W generic40.04,800120.0411
Total3916

3. Results — all rooms

FloorRoomTypeL × Wm²E reqUo reqMFρ c/w/fHmPlaneLuminairesĒEminEmaxUoUGR / limitW/m²CheckEmergency
GFOpen officeOpen-plan office12 × 896.05000.70.8550/30/202.90.7520 (5×4)546.1430.2629.10.78825.1 / 197.5CHECK4 E · 24.2 lx PASS
GFCorridorCorridor / passage24 × 2.150.41000.40.8550/30/202.90.09 (9×1)107.670.9124.00.65925.7 / 282.68PASS5 E · 38.9 lx PASS
GFElectrical roomElectrical / LV / HT / DG room6 × 424.02000.70.830/20/103.00.04 (2×2)245.3172.2299.90.70231.7 / 256.67CHECK1 E · 14.0 lx PASS
B1Car park drivewayCovered car park — driveway / traffic lane30 × 6180.0750.40.830/20/102.50.06 (6×1)82.933.1156.80.434.2 / 251.2CHECK6 E · 33.1 lx PASS

3.1 Ē achieved vs required

Ē achieved vs required (lx)meetsshortrequired0100200300400500GF · Open office546.1 / 500GF · Corridor107.6 / 100GF · Electrical room245.3 / 200B1 · Car park driveway82.9 / 75

3.2 Glare — UGR per room

FloorRoomTypeUGR calc.RUGL limitRa ≥Luminaires in viewCheck
GFOpen officeOpen-plan office25.1≤ 198020CHECK
GFCorridorCorridor / passage25.7≤ 28709PASS
GFElectrical roomElectrical / LV / HT / DG room31.7≤ 25804CHECK
B1Car park drivewayCovered car park — driveway / traffic lane34.2≤ 25706CHECK
UGR calculated by the CIE 117 formula (observer 0.5 m from the short wall, eye 1.2 m, looking along the room) — an estimate; the manufacturer's tabular UGR governs for submission. Ra is a luminaire property: confirm from the data sheet.

4. Floors

FloorRoomsArea m²LuminairesELoad WLPD W/m²Failing
GF3170.433101015.05.962
B11180.066216.01.21

5. Room sheets

5.1 GF · Open office — Open-plan office

Ē
546.1 lx
Required
500 lx
Emin / Emax
430.2 / 629.1
Uo
0.788 (≥ 0.7)
g2
0.684
Luminaires
20 · 720 W
UF
0.771
UGR (calc.)
25.1 (≤ 19)
500500500500550600600600430476509511511509476430470527563567567563527470472536571578578571536472525584625629629625584525482549585593593585549482513576616622622616576513513576616622622616576513482549585593593585549482525584625629629625584525472536571578578571536472470527563567567563527470430476509511511509476430L1EL2L3L4L5L6L7L8L9L10EL11EL12L13L14L15L16L17L18L19L20E12 m8 m430 … 629 lx
Design basis
Room12 × 8 × 2.9 m (ceiling 2.9 m) · 96.0 m²
Room type / regimeOpen-plan office — NBCS 2026 Part D Sec 1 Table 6 (ref no. 26.2)
Required illuminance500 lx (NBCS 2026 Part D Sec 1 Table 6 (ref no. 26.2) — middle of 300-500-750 lx (cl. 4.1.4.3))
UniformityUo ≥ 0.7 (max(standard 0.6, project 0.7))
Colour rendering / glareRa ≥ 80 · RUGL ≤ 19
Maintenance factor0.85 (profile · Enclosed (offices, toilets, lobbies, passages))
Reflectancesceiling 50 % · walls 30 % · floor 20 %
Mounting height2.9 m (profile · Enclosed (offices, toilets, lobbies, passages))
Calculation plane0.75 m (room type (Open-plan office)) · wall zone 0.0 m · grid 12 × 8
LuminaireGeneric (designlink) PANEL-600-36 — LED panel 600×600, 36 W · 4000 lm · 36.0 W
Layout20 luminaires, 5 × 4 grid, rotation 0°, wall clearance 0.35 × spacing
Room index / UFK = 2.23 · UF = Ē·A / (Φ·MF) = 0.771
Direct / indirect475.1 + 71.0 lx
UGR (calculated)25.1 — observer 0.5 m from the short wall, mid-width, eye 1.2 m, looking along the length; 20 luminaires in view, Lb 26.0 cd/m². CIE 117 formula with Guth position index; Lb from the indirect illuminance — estimate
CheckResult
Ē 546.1 lx ≥ 500 lx requiredPASS
Uo 0.788 ≥ 0.7PASS
spacing / height 1.12 (limit 1.5)PASS
UGR 25.1 (calculated) > 19 limitCHECK
LPD 7.5 W/m² ≤ 10.0 (ECSBC 2024 Table 7.4 (ECSBC))PASS
Grid values (lx)
y \ x (m)0.501.502.503.504.505.506.507.508.509.5010.5011.50
7.50430470472525482513513482525472470430
6.50476527536584549576576549584536527476
5.50509563571625585616616585625571563509
4.50511567578629593622622593629578567511
3.50511567578629593622622593629578567511
2.50509563571625585616616585625571563509
1.50476527536584549576576549584536527476
0.50430470472525482513513482525472470430
Grid 12 × 8 points, spacing 1.00 × 1.00 m (EN 12464-1 §4.4: p = 0.2·5^log₁₀d)
lumen-method start: N = E·A / (Φ·UF·MF) = 500·96.0 / (4000·0.55·0.85) → 26 → pass 1: 18 luminaires → Ē 492.5 lx, Uo 0.792 → pass 2: 19 luminaires → Ē 580.9 lx, Uo 0.232 → uniformity search → 20: Uo 0.788 · chosen 20

Emergency lighting — Open (anti-panic) area

NBCS 2026 Part F 3.5.6.1 d) — open (anti-panic) area: 5 lx minimum at floor level; ≥ 90 min, on within 5 s (f)
E luminaires
4 of 20
Emin
24.2 lx (≥ 5)
Ē
83.0 lx
Emax/Emin
7.3
Check
PASS
Emergency scene — only E luminaires on (floor level)5050100100150150L1EL2L3L4L5L6L7L8L9L10EL11EL12L13L14L15L16L17L18L19L20E12 m8 m24 … 177 lx
E-luminaires 4 of 20: Emin 24.2 lx ≥ 5 lx; Emax/Emin 7.3 (ratio not checked) · E luminaires: L1, L10, L11, L20

5.2 GF · Corridor — Corridor / passage

Ē
107.6 lx
Required
100 lx
Emin / Emax
70.9 / 124.0
Uo
0.659 (≥ 0.4)
g2
0.572
Luminaires
9 · 135 W
UF
0.473
UGR (calc.)
25.7 (≤ 28)
90901001001101201201201201201201207178838378719110210810810291941051101101059410111211811811210110211412012011410210011111711711110010511712412411710510211411911911410210211412012011410210511812412411810510111211811811210110411612212211610410411612212211610410111211811811210110511812412411810510211412012011410210211411911911410210511712412411710510011111711711110010211412012011410210111211811811210194105110110105949110210810810291717883837871L1EL2L3EL4L5EL6L7EL8L9E24 m2.1 m71 … 124 lx
Design basis
Room24 × 2.1 × 2.9 m (ceiling 2.9 m) · 50.4 m²
Room type / regimeCorridor / passage — NBCS 2026 Part D Sec 1 Table 6 (ref no. 1.1)
Required illuminance100 lx (NBCS 2026 Part D Sec 1 Table 6 (ref no. 1.1) — middle of 75-100-150 lx (cl. 4.1.4.3))
UniformityUo ≥ 0.4 (max(standard 0.4, project 0.7))
Colour rendering / glareRa ≥ 70 · RUGL ≤ 28
Maintenance factor0.85 (profile · Enclosed (offices, toilets, lobbies, passages))
Reflectancesceiling 50 % · walls 30 % · floor 20 %
Mounting height2.9 m (profile · Enclosed (offices, toilets, lobbies, passages))
Calculation plane0 m (room type (Corridor / passage)) · wall zone 0.0 m · grid 24 × 6
LuminaireGeneric (designlink) DL-15 — LED downlight 15 W · 1500 lm · 15.0 W
Layout9 luminaires, 9 × 1 grid, rotation 0°, wall clearance 0.5 × spacing
Room index / UFK = 0.67 · UF = Ē·A / (Φ·MF) = 0.473
Direct / indirect91.5 + 16.1 lx
UGR (calculated)25.7 — observer 0.5 m from the short wall, mid-width, eye 1.2 m, looking along the length; 9 luminaires in view, Lb 5.9 cd/m². CIE 117 formula with Guth position index; Lb from the indirect illuminance — estimate
CheckResult
Ē 107.6 lx ≥ 100 lx requiredPASS
Uo 0.659 ≥ 0.4PASS
spacing / height 0.92 (limit 1.5)PASS
UGR 25.7 (calculated) ≤ 28 limitPASS
LPD 2.68 W/m² ≤ 7.1 (ECSBC 2024 Table 7.4 (ECSBC))PASS
Grid values (lx)
y \ x (m)0.502.504.506.508.5010.5012.5014.5016.5018.5020.5022.50
1.92719410210510210110410510210010191
1.5778105114117114112116118114111112102
1.2283110120124120118122124119117118108
0.8883110120124120118122124119117118108
0.5278105114117114112116118114111112102
0.17719410210510210110410510210010191
Grid 24 × 6 points, spacing 1.00 × 0.35 m (EN 12464-1 §4.4: p = 0.2·5^log₁₀d), shown every 2 × 1
lumen-method start: N = E·A / (Φ·UF·MF) = 100·50.4 / (1500·0.55·0.85) → 8 → pass 1: 9 luminaires → Ē 107.6 lx, Uo 0.659

Emergency lighting — Escape route

NBCS 2026 Part F 3.5.6.1 d) — escape route: 10 lx minimum on the centre line at floor level, 50 % of the width ≥ 5 lx (routes ≤ 2 m wide); ≥ 90 min, on within 5 s (f)
E luminaires
5 of 9
Centre line Emin
38.9 lx (≥ 10)
Emin (area)
34.7 lx
Emax/Emin
2.5
Check
PASS
Emergency scene — only E luminaires on (floor level)404040404040404050505050505050506060606060606060707070707070708080808080L1EL2L3EL4L5EL6L7EL8L9E24 m2.1 m35 … 85 lx
E-luminaires 5 of 9: centre line Emin 38.9 lx ≥ 10 lx; route 2.1 m wide (> 2 m) — centre line only; Emax/Emin not checked (no NBCS rule) · E luminaires: L1, L3, L5, L7, L9

5.3 GF · Electrical room — Electrical / LV / HT / DG room

Ē
245.3 lx
Required
200 lx
Emin / Emax
172.2 / 299.9
Uo
0.702 (≥ 0.7)
g2
0.574
Luminaires
4 · 160 W
UF
0.383
UGR (calc.)
31.7 (≤ 25)
225225250275172200216216200172206244261261244206229270289289270229238279299299279238237280300300280237238279299299279238229270289289270229206244261261244206172200216216200172L1EL2L3L46 m4 m172 … 300 lx
Design basis
Room6 × 4 × 3.5 m (ceiling 3.5 m) · 24.0 m²
Room type / regimeElectrical / LV / HT / DG room — NBCS 2026 Part D Sec 1 Table 6 (ref no. 3.1)
Required illuminance200 lx (NBCS 2026 Part D Sec 1 Table 6 (ref no. 3.1) — middle of 150-200-300 lx (cl. 4.1.4.3))
UniformityUo ≥ 0.7 (max(standard 0.4, project 0.7))
Colour rendering / glareRa ≥ 80 · RUGL ≤ 25
Maintenance factor0.8 (profile · Utility (stores, plant, electrical, stairs))
Reflectancesceiling 30 % · walls 20 % · floor 10 %
Mounting height3 m (profile · Utility (stores, plant, electrical, stairs))
Calculation plane0 m (room type (Electrical / LV / HT / DG room)) · wall zone 0.0 m · grid 9 × 6
LuminaireGeneric (designlink) BATTEN-40 — LED batten 1200 mm, 40 W · 4800 lm · 40.0 W
Layout4 luminaires, 2 × 2 grid, rotation 0°, wall clearance 0.5 × spacing
Room index / UFK = 0.8 · UF = Ē·A / (Φ·MF) = 0.383
Direct / indirect219.3 + 26.1 lx
UGR (calculated)31.7 — observer 0.5 m from the short wall, mid-width, eye 1.2 m, looking along the length; 4 luminaires in view, Lb 9.5 cd/m². CIE 117 formula with Guth position index; Lb from the indirect illuminance — estimate
CheckResult
Ē 245.3 lx ≥ 200 lx requiredPASS
Uo 0.702 ≥ 0.7PASS
spacing / height 1.00 (limit 1.5)PASS
UGR 31.7 (calculated) > 25 limitCHECK
LPD 6.67 W/m² ≤ 7.1 (ECSBC 2024 Table 7.4 (ECSBC))PASS
Grid values (lx)
y \ x (m)0.331.001.672.333.003.674.345.005.67
3.67172206229238237238229206172
3.00200244270279280279270244200
2.33216261289299300299289261216
1.67216261289299300299289261216
1.00200244270279280279270244200
0.33172206229238237238229206172
Grid 9 × 6 points, spacing 0.67 × 0.67 m (EN 12464-1 §4.4: p = 0.2·5^log₁₀d)
lumen-method start: N = E·A / (Φ·UF·MF) = 200·24.0 / (4800·0.45·0.8) → 3 → pass 1: 4 luminaires → Ē 245.3 lx, Uo 0.702

Emergency lighting — Open (anti-panic) area

NBCS 2026 Part F 3.5.6.1 d) — open (anti-panic) area: 5 lx minimum at floor level; ≥ 90 min, on within 5 s (f)
E luminaires
1 of 4
Emin
14.0 lx (≥ 5)
Ē
61.3 lx
Emax/Emin
9.3
Check
PASS
Emergency scene — only E luminaires on (floor level)20406080100120L1EL2L3L46 m4 m14 … 131 lx
E-luminaires 1 of 4: Emin 14.0 lx ≥ 5 lx; Emax/Emin 9.3 (ratio not checked) · E luminaires: L1

5.4 B1 · Car park driveway — Covered car park — driveway / traffic lane

Ē
82.9 lx
Required
75 lx
Emin / Emax
33.1 / 156.8
Uo
0.4 (≥ 0.4)
g2
0.211
Luminaires
6 · 216 W
UF
0.723
UGR (calc.)
34.2 (≤ 25)
75100100100100100100125125125125125125150150150150334964644933487911411479485710015015010057548712212287544868868668484869878769485790126126905762106156156106625790126126905750708888705050708888705057911261269157631061571571066358911261269158507088887050507088887050589112612691586310615715710663579112612691575070888870505070888870505790126126905762106156156106625790126126905748698787694848688686684854871221228754571001501501005748791141147948334964644933L1EL2EL3EL4EL5EL6E30 m6 m33 … 157 lx
Design basis
Room30 × 6 × 3 m (ceiling 3 m) · 180.0 m²
Room type / regimeCovered car park — driveway / traffic lane — NBCS 2026 Part D Sec 1 Table 6 (ref no. 34.3)
Required illuminance75 lx (NBCS 2026 Part D Sec 1 Table 6 (ref no. 34.3) — middle of 50-75-100 lx (cl. 4.1.4.3))
UniformityUo ≥ 0.4 (NBCS 2026 Part D Sec 1 Table 6 (ref no. 34.3))
Colour rendering / glareRa ≥ 70 · RUGL ≤ 25
Maintenance factor0.8 (profile · Parking & driveway)
Reflectancesceiling 30 % · walls 20 % · floor 10 %
Mounting height2.5 m (profile · Parking & driveway)
Calculation plane0 m (room type (Covered car park — driveway / traffic lane)) · wall zone 0.0 m · grid 30 × 6
LuminaireGeneric (designlink) PARK-36 — LED car-park luminaire 36 W · 4300 lm · 36.0 W
Layout6 luminaires, 6 × 1 grid, rotation 90°, wall clearance 0.5 × spacing
Room index / UFK = 2.0 · UF = Ē·A / (Φ·MF) = 0.723
Direct / indirect78.2 + 4.7 lx
UGR (calculated)34.2 — observer 0.5 m from the short wall, mid-width, eye 1.2 m, looking along the length; 6 luminaires in view, Lb 1.7 cd/m². CIE 117 formula with Guth position index; Lb from the indirect illuminance — estimate
CheckResult
Ē 82.9 lx ≥ 75 lx requiredPASS
Uo 0.4 ≥ 0.4PASS
spacing / height 2.40 (limit 1.5)PASS
UGR 34.2 (calculated) > 25 limitCHECK
LPD 1.2 W/m² ≤ 3.0 (ECSBC 2024 Table 7.4 (ECSBC))PASS
Grid values (lx)
y \ x (m)0.503.506.509.5012.5015.5018.5021.5024.5027.50
5.5033545750635057574857
4.504987907010670919069100
3.5064122126881578812612687150
2.5064122126881578812612687150
1.504987907010670919069100
0.5033545750635057574857
Grid 30 × 6 points, spacing 1.00 × 1.00 m (EN 12464-1 §4.4: p = 0.2·5^log₁₀d), shown every 3 × 1
lumen-method start: N = E·A / (Φ·UF·MF) = 75·180.0 / (4300·0.45·0.8) → 9 → pass 1: 6 luminaires → Ē 82.9 lx, Uo 0.4

Emergency lighting — Open (anti-panic) area

NBCS 2026 Part F 3.5.6.1 d) — open (anti-panic) area: 5 lx minimum at floor level; ≥ 90 min, on within 5 s (f)
E luminaires
6 of 6
Emin
33.1 lx (≥ 5)
Ē
82.9 lx
Emax/Emin
4.7
Check
PASS
Emergency scene — only E luminaires on (floor level)75100100100100100100125125125125125125150150150150L1EL2EL3EL4EL5EL6E30 m6 m33 … 157 lx
E-luminaires 6 of 6: Emin 33.1 lx ≥ 5 lx; Emax/Emin 4.7 (ratio not checked) · E luminaires: L1, L2, L3, L4, L5, L6

6. Worked examples — from this project

Worked from this project’s own rooms — every number is the engine’s result for that room (see the room sheet above); the lumen method only seeds the count, the point-by-point calculation decides it.

B1 · Car park driveway — Covered car park — driveway / traffic lane
largest room of the project
Given: Room 30 × 6 m, ceiling 3 m · Luminaire Generic (designlink) PARK-36 — Φ 4300 lm, 36.0 W · Basis Ereq 75 lx · Uo ≥ 0.4 · MF 0.8 · ρ 30/20/10 % · Hm 2.5 m · plane 0 m
Ereq from NBCS 2026 Part D Sec 1 Table 6 (ref no. 34.3) — middle of 50-75-100 lx (cl. 4.1.4.3)
1. Area: A = L × W = 30 × 6 = 180 m²
2. Room index: K = A / (h · (L + W)), h = Hm − plane = 180 / (2.5 · (30 + 6)) = 2
3. Lumen-method start: N0 = ⌈E · A / (Φ · UF0 · MF)⌉ = 75 · 180 / (4300 · 0.45 · 0.8) = 9 nos (UF0 0.45 assumed for an open / high space)
4. Point-by-point iteration: Ni+1 = ⌈Ni · Ereq / Ēi⌉, then step down while Ē ≥ Ereq = pass 1: 6 luminaires → Ē 82.9 lx, Uo 0.4 = 6 (6 × 1) nos
5. Average illuminance: Ē = (Ēdirect + Ēinter-reflected) × MF = 78.2 + 4.7 = 82.9 lx (direct I(C,γ)·cosθ/d² from the photometric file, inter-reflection by radiosity; both already × MF)
6. Illuminance: Ē ≥ Ereq → 82.9 ≥ 75 lx PASS
7. Utilisation factor (back-calculated): UF = Ē · A / (N · Φ · MF) = 82.9 · 180 / (6 · 4300 · 0.8) = 0.723
8. Uniformity: Uo = Emin / Ē ≥ 0.4 → 33.1 / 82.9 = 0.4 PASS (180 grid points)
9. Spacing / height: max(L/nx, W/ny) / h ≤ 1.5 → max(5.00, 6.00) / 2.5 = 2.4 PASS (accepted when Uo is met)
10. Glare: UGR ≤ RUGL 25 → UGR 34.2 (CIE 117 estimate) CHECK (limit from NBCS 2026 Part D Sec 1 Table 6)
11. Lighting power density: LPD = N · P / A = 6 · 36.0 / 180 = 1.2 W/m²
12. LPD limit: LPD ≤ 3 W/m² → 1.2 ≤ 3 PASS (ECSBC 2024 Table 7.4 (ECSBC), Covered car park — driveway / traffic lane)
13. Emergency (E luminaires only): Emin ≥ 5 lx → 6 of 6 on → Emin 33.1 lx, ratio 4.7 PASS
GF · Electrical room — Electrical / LV / HT / DG room
of the other rooms, the one with the smallest uniformity margin
Given: Room 6 × 4 m, ceiling 3.5 m · Luminaire Generic (designlink) BATTEN-40 — Φ 4800 lm, 40.0 W · Basis Ereq 200 lx · Uo ≥ 0.7 · MF 0.8 · ρ 30/20/10 % · Hm 3 m · plane 0 m
Ereq from NBCS 2026 Part D Sec 1 Table 6 (ref no. 3.1) — middle of 150-200-300 lx (cl. 4.1.4.3)
1. Area: A = L × W = 6 × 4 = 24 m²
2. Room index: K = A / (h · (L + W)), h = Hm − plane = 24 / (3 · (6 + 4)) = 0.8
3. Lumen-method start: N0 = ⌈E · A / (Φ · UF0 · MF)⌉ = 200 · 24 / (4800 · 0.45 · 0.8) = 3 nos (UF0 0.45 assumed for an open / high space)
4. Point-by-point iteration: Ni+1 = ⌈Ni · Ereq / Ēi⌉, then step down while Ē ≥ Ereq = pass 1: 4 luminaires → Ē 245.3 lx, Uo 0.702 = 4 (2 × 2) nos
5. Average illuminance: Ē = (Ēdirect + Ēinter-reflected) × MF = 219.3 + 26.1 = 245.3 lx (direct I(C,γ)·cosθ/d² from the photometric file, inter-reflection by radiosity; both already × MF)
6. Illuminance: Ē ≥ Ereq → 245.3 ≥ 200 lx PASS
7. Utilisation factor (back-calculated): UF = Ē · A / (N · Φ · MF) = 245.3 · 24 / (4 · 4800 · 0.8) = 0.383
8. Uniformity: Uo = Emin / Ē ≥ 0.7 → 172.2 / 245.3 = 0.702 PASS (54 grid points)
9. Spacing / height: max(L/nx, W/ny) / h ≤ 1.5 → max(3.00, 2.00) / 3 = 1.0 PASS
10. Glare: UGR ≤ RUGL 25 → UGR 31.7 (CIE 117 estimate) CHECK (limit from NBCS 2026 Part D Sec 1 Table 6)
11. Lighting power density: LPD = N · P / A = 4 · 40.0 / 24 = 6.67 W/m²
12. LPD limit: LPD ≤ 7.1 W/m² → 6.67 ≤ 7.1 PASS (ECSBC 2024 Table 7.4 (ECSBC), Electrical / LV / HT / DG room)
13. Emergency (E luminaires only): Emin ≥ 5 lx → 1 of 4 on → Emin 14.0 lx, ratio 9.3 PASS

7. Luminaire data sheets

7.1 Generic (designlink) PANEL-600-36

Luminaire data sheet
Manufacturer / modelGeneric (designlink) PANEL-600-36
DescriptionLED panel 600×600, 36 W
Lamp / sourceLED 4000 lm, 36.0 W
Luminous flux4,000 lm (absolute photometry (integrated))
Power / efficacy36.0 W · 111.1 lm/W
Distributionaxial symmetry · beam (50 %) 110.0° · downward light output ratio 1.0
Luminous dimensions600 × 600 × 30 mm
FilePANEL-600-36.ies (IES) · generic synthetic distribution — replace before submission · library id 2
Used in this project20 nos (4 on emergency) in 1 room(s)
8917926835730°30°60°60°90°90°cd / klm · C0–C180 solid · C90–C270 dashed · γ from nadir
Intensity table (cd/klm)
γ0°10°20°30°40°50°60°70°80°90°
C035735033129925620615094400
C9035735033129925620615094400

7.2 Generic (designlink) DL-15

Luminaire data sheet
Manufacturer / modelGeneric (designlink) DL-15
DescriptionLED downlight 15 W
Lamp / sourceLED 1500 lm, 15.0 W
Luminous flux1,500 lm (absolute photometry (integrated))
Power / efficacy15.0 W · 100.0 lm/W
Distributionaxial symmetry · beam (50 %) 90.0° · downward light output ratio 1.0
Luminous dimensions150 × 150 × 50 mm
FileDL-15.ies (IES) · generic synthetic distribution — replace before submission · library id 5
Used in this project9 nos (5 on emergency) in 1 room(s)
11923835747630°30°60°60°90°90°cd / klm · C0–C180 solid · C90–C270 dashed · γ from nadir
Intensity table (cd/klm)
γ0°10°20°30°40°50°60°70°80°90°
C047646242035728019711956140
C9047646242035728019711956140

7.3 Generic (designlink) PARK-36

Luminaire data sheet
Manufacturer / modelGeneric (designlink) PARK-36
DescriptionLED car-park luminaire 36 W
Lamp / sourceLED 4300 lm, 36.0 W
Luminous flux4,300 lm (absolute photometry (integrated))
Power / efficacy36.0 W · 119.4 lm/W
Distributionquadrant symmetry · beam (50 %) 126.0° · downward light output ratio 1.0
Luminous dimensions1200 × 100 × 60 mm
FilePARK-36.ies (IES) · generic synthetic distribution — replace before submission · library id 18
Used in this project6 nos (6 on emergency) in 1 room(s)
6913820727730°30°60°60°90°90°cd / klm · C0–C180 solid · C90–C270 dashed · γ from nadir
Intensity table (cd/klm)
γ0°10°20°30°40°50°60°70°80°90°
C0277273262243218186148106580
C902772742672542372141851481000

7.4 Generic (designlink) BATTEN-40

Luminaire data sheet
Manufacturer / modelGeneric (designlink) BATTEN-40
DescriptionLED batten 1200 mm, 40 W
Lamp / sourceLED 4800 lm, 40.0 W
Luminous flux4,800 lm (absolute photometry (integrated))
Power / efficacy40.0 W · 120.0 lm/W
Distributionquadrant symmetry · beam (50 %) 120.0° · downward light output ratio 1.0
Luminous dimensions1200 × 60 × 50 mm
FileBATTEN-40.ies (IES) · generic synthetic distribution — replace before submission · library id 9
Used in this project4 nos (1 on emergency) in 1 room(s)
7214521729030°30°60°60°90°90°cd / klm · C0–C180 solid · C90–C270 dashed · γ from nadir
Intensity table (cd/klm)
γ0°10°20°30°40°50°60°70°80°90°
C029028527225122218614599500
C90290287278264244217185144930

8. Standards applied

StandardUsed for
NBCS 2026 Part D Sec 1 Table 6Illuminance and lighting performance parameters — Ēm (middle of the range, cl. 4.1.4.3), Uo, Ra, RUGL per ref no.
IS 3646 (Part 1):2025Interior illumination — general requirements for working interiors
SP 72:2025National Lighting Code of India
NBCS 2026 Part F 3.5.6Escape lighting — 10 lx centre line, 5 lx over 50 % of the width, 2 lx in auditoria during performances; on within 5 s, ≥ 90 min
ECSBC 2024 cl. 7.3.3, Tables 7.4–7.6Lighting power density — space-function method (ECSBC 2024 Table 7.4 (ECSBC))
IS 1944Outdoor lighting (NBCS D1 4.6 gives no lux table)
IES LM-63Photometric data file format (IES)
EULUMDATPhotometric data file format (LDT)
CIE 52 / CIE 40Calculation of illuminance — point-by-point and interreflection
Prepared by
Checked by
Approved by

Results are design aids computed by designlink calc (calc.designlink.in) and must be reviewed by a qualified engineer before issue. Ground levels marked "assumed" have no survey level within reach — verify.