SAMPLELighting design (lux) — this is what your report looks like, generated from demo inputs.Generate yours →2 free designs every day for every signed-in account · 1 design free on sign-in · ₹99 + GST per design (report + Excel + DXF) · free for DesignLink companies
Report ready — use Print → Save as PDF (A4 landscape).
calc.designlink.in
Lighting design — illuminance & uniformity
Sample project — Tower A · Indian regime · 4 rooms · 39 luminaires
One or more luminaires use the generic (synthetic cosⁿ) distribution. Upload the manufacturer's IES / LDT file and re-run before submission.
1. Design basis
Item
Value
Source
Code regime
Indian — NBCS 2026 (SP 7:2026) Part D Sec 1 Table 6, IS 3646-1:2025, SP 72:2025; emergency lighting NBCS 2026 Part F 3.5.6.1; ECSBC 2024 Table 7.4 (ECSBC)
project
Code edition
NBCS 2026 (SP 7:2026, in force from 30 Apr 2026) — Ēm = middle value of the Table 6 range (cl. 4.1.4.3), Uo, Ra and RUGL per ref no.
project
Utility (stores, plant, electrical, stairs)
MF 0.8 · reflectance ceiling 30 % / walls 20 % / floor 10 % · mounting 3.0 m · plane per room type
design-basis profile
Enclosed (offices, toilets, lobbies, passages)
MF 0.85 · reflectance ceiling 50 % / walls 30 % / floor 20 % · mounting 3.0 m · plane per room type
design-basis profile
Parking & driveway
MF 0.8 · reflectance ceiling 30 % / walls 20 % / floor 10 % · mounting 2.5 m · plane per room type
design-basis profile
Outdoor (no reflectance)
MF 0.8 · reflectance ceiling 0 % / walls 0 % / floor 10 % · mounting 6.0 m · plane per room type
design-basis profile
Uniformity target
Uo ≥ 0.7 for all areas (standard's value where higher); parking, driveway and corridors: the standard's Uo
project / PMC
Calculation grid
EN 12464-1 §4.4 grid at cell centres, wall zone 0.0 m
EN 12464-1:2021
Method
Direct illuminance point-by-point from the luminaire's photometric file (I(C,γ)·cos θ / d²), interreflected component by radiosity between ceiling, walls and floor; all values × maintenance factor
CIE 52 / IES LM-63 / EULUMDAT
Emergency lighting
enabled — escape routes 10 lx on the centre line at floor level and ≥ 5 lx over 50 % of the width (routes ≤ 2 m wide), open areas 5 lx, assembly floors during performances 2 lx; duration ≥ 90 min, on within 5 s (NBCS 2026 Part F 3.5.6.1 f)); battery packs not in lieu of a DG-backed supply (g), ratio not checked; luminaires marked E stay on
NBCS 2026 Part F 3.5.6.1 d), f)
Lighting power density
ECSBC 2024 Table 7.4 (ECSBC) space-function limits — the same table as the energy-code tool
energy code
2. Luminaire list
Manufacturer
Model
Description
W
lm
lm/W
Qty
of which E
Rooms
Generic (designlink)
PANEL-600-36
LED panel 600×600, 36 W generic
36.0
4,000
111.1
20
4
1
Generic (designlink)
DL-15
LED downlight 15 W generic
15.0
1,500
100.0
9
5
1
Generic (designlink)
PARK-36
LED car-park luminaire 36 W generic
36.0
4,300
119.4
6
6
1
Generic (designlink)
BATTEN-40
LED batten 1200 mm, 40 W generic
40.0
4,800
120.0
4
1
1
Total
39
16
3. Results — all rooms
Floor
Room
Type
L × W
m²
E req
Uo req
MF
ρ c/w/f
Hm
Plane
Luminaires
Ē
Emin
Emax
Uo
UGR / limit
W/m²
Check
Emergency
GF
Open office
Open-plan office
12 × 8
96.0
500
0.7
0.85
50/30/20
2.9
0.75
20 (5×4)
546.1
430.2
629.1
0.788
25.1 / 19
7.5
CHECK
4 E · 24.2 lx PASS
GF
Corridor
Corridor / passage
24 × 2.1
50.4
100
0.4
0.85
50/30/20
2.9
0.0
9 (9×1)
107.6
70.9
124.0
0.659
25.7 / 28
2.68
PASS
5 E · 38.9 lx PASS
GF
Electrical room
Electrical / LV / HT / DG room
6 × 4
24.0
200
0.7
0.8
30/20/10
3.0
0.0
4 (2×2)
245.3
172.2
299.9
0.702
31.7 / 25
6.67
CHECK
1 E · 14.0 lx PASS
B1
Car park driveway
Covered car park — driveway / traffic lane
30 × 6
180.0
75
0.4
0.8
30/20/10
2.5
0.0
6 (6×1)
82.9
33.1
156.8
0.4
34.2 / 25
1.2
CHECK
6 E · 33.1 lx PASS
3.1 Ē achieved vs required
3.2 Glare — UGR per room
Floor
Room
Type
UGR calc.
RUGL limit
Ra ≥
Luminaires in view
Check
GF
Open office
Open-plan office
25.1
≤ 19
80
20
CHECK
GF
Corridor
Corridor / passage
25.7
≤ 28
70
9
PASS
GF
Electrical room
Electrical / LV / HT / DG room
31.7
≤ 25
80
4
CHECK
B1
Car park driveway
Covered car park — driveway / traffic lane
34.2
≤ 25
70
6
CHECK
UGR calculated by the CIE 117 formula (observer 0.5 m from the short wall, eye 1.2 m, looking along the room) — an estimate; the manufacturer's tabular UGR governs for submission. Ra is a luminaire property: confirm from the data sheet.
4. Floors
Floor
Rooms
Area m²
Luminaires
E
Load W
LPD W/m²
Failing
GF
3
170.4
33
10
1015.0
5.96
2
B1
1
180.0
6
6
216.0
1.2
1
5. Room sheets
5.1 GF · Open office — Open-plan office
Ē
546.1 lx
Required
500 lx
Emin / Emax
430.2 / 629.1
Uo
0.788 (≥ 0.7)
g2
0.684
Luminaires
20 · 720 W
UF
0.771
UGR (calc.)
25.1 (≤ 19)
Design basis
Room
12 × 8 × 2.9 m (ceiling 2.9 m) · 96.0 m²
Room type / regime
Open-plan office — NBCS 2026 Part D Sec 1 Table 6 (ref no. 26.2)
Required illuminance
500 lx (NBCS 2026 Part D Sec 1 Table 6 (ref no. 26.2) — middle of 300-500-750 lx (cl. 4.1.4.3))
25.1 — observer 0.5 m from the short wall, mid-width, eye 1.2 m, looking along the length; 20 luminaires in view, Lb 26.0 cd/m². CIE 117 formula with Guth position index; Lb from the indirect illuminance — estimate
25.7 — observer 0.5 m from the short wall, mid-width, eye 1.2 m, looking along the length; 9 luminaires in view, Lb 5.9 cd/m². CIE 117 formula with Guth position index; Lb from the indirect illuminance — estimate
NBCS 2026 Part F 3.5.6.1 d) — escape route: 10 lx minimum on the centre line at floor level, 50 % of the width ≥ 5 lx (routes ≤ 2 m wide); ≥ 90 min, on within 5 s (f)
E luminaires
5 of 9
Centre line Emin
38.9 lx (≥ 10)
Emin (area)
34.7 lx
Emax/Emin
2.5
Check
PASS
E-luminaires 5 of 9: centre line Emin 38.9 lx ≥ 10 lx; route 2.1 m wide (> 2 m) — centre line only; Emax/Emin not checked (no NBCS rule) · E luminaires: L1, L3, L5, L7, L9
31.7 — observer 0.5 m from the short wall, mid-width, eye 1.2 m, looking along the length; 4 luminaires in view, Lb 9.5 cd/m². CIE 117 formula with Guth position index; Lb from the indirect illuminance — estimate
34.2 — observer 0.5 m from the short wall, mid-width, eye 1.2 m, looking along the length; 6 luminaires in view, Lb 1.7 cd/m². CIE 117 formula with Guth position index; Lb from the indirect illuminance — estimate
Check
Result
Ē 82.9 lx ≥ 75 lx required
PASS
Uo 0.4 ≥ 0.4
PASS
spacing / height 2.40 (limit 1.5)
PASS
UGR 34.2 (calculated) > 25 limit
CHECK
LPD 1.2 W/m² ≤ 3.0 (ECSBC 2024 Table 7.4 (ECSBC))
PASS
Grid values (lx)
y \ x (m)
0.50
3.50
6.50
9.50
12.50
15.50
18.50
21.50
24.50
27.50
5.50
33
54
57
50
63
50
57
57
48
57
4.50
49
87
90
70
106
70
91
90
69
100
3.50
64
122
126
88
157
88
126
126
87
150
2.50
64
122
126
88
157
88
126
126
87
150
1.50
49
87
90
70
106
70
91
90
69
100
0.50
33
54
57
50
63
50
57
57
48
57
Grid 30 × 6 points, spacing 1.00 × 1.00 m (EN 12464-1 §4.4: p = 0.2·5^log₁₀d), shown every 3 × 1
NBCS 2026 Part F 3.5.6.1 d) — open (anti-panic) area: 5 lx minimum at floor level; ≥ 90 min, on within 5 s (f)
E luminaires
6 of 6
Emin
33.1 lx (≥ 5)
Ē
82.9 lx
Emax/Emin
4.7
Check
PASS
E-luminaires 6 of 6: Emin 33.1 lx ≥ 5 lx; Emax/Emin 4.7 (ratio not checked) · E luminaires: L1, L2, L3, L4, L5, L6
6. Worked examples — from this project
Worked from this project’s own rooms — every number is the engine’s result for that room (see the room sheet above); the lumen method only seeds the count, the point-by-point calculation decides it.
B1 · Car park driveway — Covered car park — driveway / traffic lane
largest room of the project
Given: Room 30 × 6 m, ceiling 3 m · Luminaire Generic (designlink) PARK-36 — Φ 4300 lm, 36.0 W · Basis Ereq 75 lx · Uo ≥ 0.4 · MF 0.8 · ρ 30/20/10 % · Hm 2.5 m · plane 0 m
Ereq from NBCS 2026 Part D Sec 1 Table 6 (ref no. 34.3) — middle of 50-75-100 lx (cl. 4.1.4.3)
1. Area: A = L × W = 30 × 6 = 180 m²
2. Room index: K = A / (h · (L + W)), h = Hm − plane = 180 / (2.5 · (30 + 6)) = 2
3. Lumen-method start: N0 = ⌈E · A / (Φ · UF0 · MF)⌉ = 75 · 180 / (4300 · 0.45 · 0.8) = 9 nos(UF0 0.45 assumed for an open / high space)
4. Point-by-point iteration: Ni+1 = ⌈Ni · Ereq / Ēi⌉, then step down while Ē ≥ Ereq = pass 1: 6 luminaires → Ē 82.9 lx, Uo 0.4 = 6 (6 × 1) nos
5. Average illuminance: Ē = (Ēdirect + Ēinter-reflected) × MF = 78.2 + 4.7 = 82.9 lx(direct I(C,γ)·cosθ/d² from the photometric file, inter-reflection by radiosity; both already × MF)
BATTEN-40.ies (IES) · generic synthetic distribution — replace before submission · library id 9
Used in this project
4 nos (1 on emergency) in 1 room(s)
Intensity table (cd/klm)
γ
0°
10°
20°
30°
40°
50°
60°
70°
80°
90°
C0
290
285
272
251
222
186
145
99
50
0
C90
290
287
278
264
244
217
185
144
93
0
8. Standards applied
Standard
Used for
NBCS 2026 Part D Sec 1 Table 6
Illuminance and lighting performance parameters — Ēm (middle of the range, cl. 4.1.4.3), Uo, Ra, RUGL per ref no.
IS 3646 (Part 1):2025
Interior illumination — general requirements for working interiors
SP 72:2025
National Lighting Code of India
NBCS 2026 Part F 3.5.6
Escape lighting — 10 lx centre line, 5 lx over 50 % of the width, 2 lx in auditoria during performances; on within 5 s, ≥ 90 min
ECSBC 2024 cl. 7.3.3, Tables 7.4–7.6
Lighting power density — space-function method (ECSBC 2024 Table 7.4 (ECSBC))
IS 1944
Outdoor lighting (NBCS D1 4.6 gives no lux table)
IES LM-63
Photometric data file format (IES)
EULUMDAT
Photometric data file format (LDT)
CIE 52 / CIE 40
Calculation of illuminance — point-by-point and interreflection
Prepared by
Checked by
Approved by
Results are design aids computed by designlink calc (calc.designlink.in) and must be reviewed by a qualified engineer before issue. Ground levels marked "assumed" have no survey level within reach — verify.