calc.designlink.inVoltage dip on motor starting
Sample project — Tower A · Electrical
Generated 28 Nov 2026 17:16
Voltage at the transformer LV bus and at the motor while a large motor starts — source fau…
Project code SAMPLE
1. Inputs
| Group | Input | Value | Unit |
|---|
| Supply | Transformer | 1000 | kVA |
| Supply | Transformer impedance | 5.0 | % |
| Supply | Transformer X/R | 6 | |
| Supply | Source fault level at the HV side | 250 | MVA |
| Supply | LV voltage | 415 | V |
| Motor | Motor | 160 | kW |
| Motor | Full-load pf | 0.87 | |
| Motor | Efficiency | 0.95 | |
| Motor | Locked-rotor current | 6.5 | × FLC |
| Motor | Starting power factor | 0.3 | |
| Motor | Starter | Direct-on-line | |
| Motor | Cable resistance transformer → motor (0 = none) | 8 | mΩ |
| Motor | Cable reactance | 4 | mΩ |
| Motor | Allowed dip at the LV bus | 10 | % |
| Motor | Allowed dip at the motor | 15 | % |
2. Results
Impedances (Ω, per phase at LV)
| Item | Value | Unit | Note / basis |
|---|
| Source | 0.6889 | mΩ | |
| Transformer | 8.61 | mΩ | R 1.42 + jX 8.49 |
| Cable | 8.94 | mΩ | |
| Motor at start | 136.87 | mΩ | pf 0.3 |
Motor start
| Item | Value | Unit | Note / basis |
|---|
| Full-load current | 269.32 | A | |
| Starter | Direct-on-line | | |
| Starting current | 1750.58 | A | 6.50 × FLC |
| Voltage at the LV bus | 94.01 | % | |
| Voltage at the motor | 89.84 | % | |
3. Checks
| Check | Result | Note |
|---|
| LV bus dip 6.0 % ≤ 10 % | PASS | |
| Motor terminal dip 10.2 % ≤ 15 % | PASS | torque falls with V²: check the load torque at the reduced voltage |
4. Worked example
I start = 6.50 × 269.3 = 1751 A → Zm = 240 / 1751 = 136.9 mΩ at pf 0.3
V motor = |Zm / (Zs + Zt + Zc + Zm)| = 89.8 % → dip 10.2 %
5. Notes
- Constant-impedance motor model at standstill (conservative for the first cycles); other running loads on the bus add to the dip.
- If the dip is too high: star-delta / auto-transformer / soft starter, a larger or lower-%Z transformer, or start the motor before the other large loads.
6. Standards and references
- IEC 60076 (series) — Power transformers: Impedance, ratings and losses used for the fault study source model
- IEC 60034-1 — Rotating electrical machines — rating and performance: Alternators and motors
- IEEE Std 3002.7-2018 — Recommended practice for conducting motor-starting studies in industrial and commercial power systems: Voltage dip on motor starting