calc.designlink.inMotor protection & DOL / star-delta starter
Sample project — Tower A · Electrical
Generated 28 Nov 2026 17:16
Motor full-load current, DOL and star-delta starter parts (contactors, overload relay rang…
Project code SAMPLE
1. Inputs
| Group | Input | Value | Unit |
|---|
| Motor | Motor output | 37 | kW |
| Motor | Line voltage | 415 | V |
| Motor | Power factor at full load | 0.86 | |
| Motor | Efficiency at full load | 0.93 | |
| Motor | Nameplate FLC (0 = calculate) | 0 | A |
| Motor | Locked-rotor current | 7.0 | × FLC |
| Motor | Starting time (DOL) | 6 | s |
| Motor | Service factor ≥ 1.15 or temperature rise ≤ 40 K (NEC 430.32) | False | |
| Starter and protection | Starter | Star-delta | |
| Starter and protection | Overload trip class | Class 10 | |
| Starter and protection | Short-circuit protection basis | IEC — MPCB / motor MCCB (magnetic ≈ 13 × In, typical) | |
2. Results
Motor currents
| Item | Value | Unit | Note / basis |
|---|
| Full-load current | 64.36 | A | P / (√3 · V · pf · η) |
| Locked-rotor current (DOL) | 450.52 | A | |
| Starting line current | 150.17 | A | star start = DOL / 3 |
Starter parts
| Item | Value | Unit | Note / basis |
|---|
| Line (main) contactor, AC-3 | 38 | A | ≥ FLC/√3 = 37.2 A |
| Delta contactor, AC-3 | 38 | A | ≥ FLC/√3 = 37.2 A |
| Star contactor, AC-3 | 25 | A | ≥ FLC/3 = 21.5 A |
| Overload relay setting (in the winding circuit) | 37.16 | A | set at FLC/√3 = 0.58 × FLC |
| Star → delta changeover | timer, typically at 80–90 % speed | | |
Short-circuit protection
| Item | Value | Unit | Note / basis |
|---|
| MPCB / motor-protection MCCB rating | 40 | A | thermal range covering the overload setting |
| Magnetic trip (≈ 13 × In, typical) | 520 | A | |
Cables
| Item | Value | Unit | Note / basis |
|---|
| Cable current (each of the two cables to the motor) | 46.45 | A | ≥ 125 % of the conductor current (NEC 430.22; typical in IEC practice) |
| NEC 430.32 overload maximum | 74.01 | A | 125 % with SF ≥ 1.15 / ≤ 40 K rise, else 115 % |
3. Checks
| Check | Result | Note |
|---|
| Starting 3 s within the class 10 trip time at 7.2 × setting (10 s max) | PASS | IEC 60947-4-1 trip classes; long run-up (fans, crushers) needs class 20 / 30 |
| Magnetic trip 520 A above the starting inrush allowance 300 A | PASS | ≈ 2 × locked-rotor current for the asymmetric first peak (typical) |
4. Worked example
FLC = 37 × 1000 / (√3 × 415 × 0.86 × 0.93) = 64.4 A
Star-delta: winding current = FLC / √3 = 64.4 / 1.732 = 37.2 A; star start current = 7 × 64.4 / 3 = 150 A
5. Notes
- Contactor ratings are typical AC-3 frame sizes; take the maker's coordination table (type 2 coordination, IEC 60947-4-1) for the MPCB / contactor / overload set.
- Star-delta needs six terminals and two cables to the motor; the overload relay sits in the winding circuit and is set at 58 % of FLC.
6. Standards and references
- IS/IEC 60947-4-1 — Contactors and motor-starters — electromechanical: AC-3 utilisation, starter ratings and overload relays for motor feeders
- IEC 60034-1 — Rotating electrical machines — rating and performance: Alternators and motors
- NFPA 70 (NEC 2023) — National Electrical Code: Wiring methods, articles 250, 450, 520, 620, 640, 700, 760, 800
- IS 8828 / IEC 60898-1 — Circuit-breakers for overcurrent protection for household and similar installations (MCB): MCBs
Prepared by
Checked by
Approved by
Results are design aids computed by designlink calc (calc.designlink.in) and must be reviewed by a qualified engineer before issue. Ground levels marked "assumed" have no survey level within reach — verify.