Motor protection & DOL / star-delta starter

Sample project — Tower A · Electrical
Generated 28 Nov 2026 17:16
Motor full-load current, DOL and star-delta starter parts (contactors, overload relay rang…
Project code SAMPLE
FLC
64.4 A
Starting current
150.2 A
Overload set
37.2 A
Main contactor
38 A

1. Inputs

GroupInputValueUnit
MotorMotor output37kW
MotorLine voltage415V
MotorPower factor at full load0.86
MotorEfficiency at full load0.93
MotorNameplate FLC (0 = calculate)0A
MotorLocked-rotor current7.0× FLC
MotorStarting time (DOL)6s
MotorService factor ≥ 1.15 or temperature rise ≤ 40 K (NEC 430.32)False
Starter and protectionStarterStar-delta
Starter and protectionOverload trip classClass 10
Starter and protectionShort-circuit protection basisIEC — MPCB / motor MCCB (magnetic ≈ 13 × In, typical)

2. Results

Motor currents

ItemValueUnitNote / basis
Full-load current64.36AP / (√3 · V · pf · η)
Locked-rotor current (DOL)450.52A
Starting line current150.17Astar start = DOL / 3

Starter parts

ItemValueUnitNote / basis
Line (main) contactor, AC-338A≥ FLC/√3 = 37.2 A
Delta contactor, AC-338A≥ FLC/√3 = 37.2 A
Star contactor, AC-325A≥ FLC/3 = 21.5 A
Overload relay setting (in the winding circuit)37.16Aset at FLC/√3 = 0.58 × FLC
Star → delta changeovertimer, typically at 80–90 % speed

Short-circuit protection

ItemValueUnitNote / basis
MPCB / motor-protection MCCB rating40Athermal range covering the overload setting
Magnetic trip (≈ 13 × In, typical)520A

Cables

ItemValueUnitNote / basis
Cable current (each of the two cables to the motor)46.45A≥ 125 % of the conductor current (NEC 430.22; typical in IEC practice)
NEC 430.32 overload maximum74.01A125 % with SF ≥ 1.15 / ≤ 40 K rise, else 115 %

3. Checks

CheckResultNote
Starting 3 s within the class 10 trip time at 7.2 × setting (10 s max)PASSIEC 60947-4-1 trip classes; long run-up (fans, crushers) needs class 20 / 30
Magnetic trip 520 A above the starting inrush allowance 300 APASS≈ 2 × locked-rotor current for the asymmetric first peak (typical)

4. Worked example

FLC = 37 × 1000 / (√3 × 415 × 0.86 × 0.93) = 64.4 A
Star-delta: winding current = FLC / √3 = 64.4 / 1.732 = 37.2 A; star start current = 7 × 64.4 / 3 = 150 A

5. Notes

6. Standards and references