calc.designlink.inNEC breaker sizing — branch, feeder, transformer
Sample project — Tower A · Electrical
Generated 28 Nov 2026 17:16
NEC overcurrent device and conductor ampacity for branch circuits and feeders (continuous …
Project code SAMPLE
Conductor ampacity ≥
50.0 A
1. Inputs
| Group | Input | Value | Unit |
|---|
| Circuit | What to size | Branch circuit / feeder | |
| Circuit | Continuous load (3 h or more) | 32 | A |
| Circuit | Non-continuous load | 10 | A |
| Circuit | Device and assembly listed for 100 % continuous operation | False | |
2. Results
NEC 210.20 / 215.3 and 210.19 / 215.2
| Item | Value | Unit | Note / basis |
|---|
| Continuous load × 125 % | 40.0 | A | 100 % where listed for continuous operation |
| Non-continuous load | 10.0 | A | |
| Device rating ≥ | 50.0 | A | → standard 50 A (240.6(A)) |
| Conductor ampacity ≥ | 50.0 | A | before ambient / grouping adjustment |
3. Checks
| Check | Result | Note |
|---|
| 50 A ≥ 50.0 A | PASS | |
| Conductor protected by the device (240.4) — choose a conductor with ampacity ≥ the device or use 240.4(B) | PASS | check after the correction factors |
4. Worked example
OCPD ≥ 1.25 × 32 + 10 = 50.0 A → 50 A
5. Notes
- Small conductors: 14 AWG ≤ 15 A, 12 AWG ≤ 20 A, 10 AWG ≤ 30 A copper (240.4(D)).
6. Standards and references
- NFPA 70 (NEC 2023) — National Electrical Code: Wiring methods, articles 250, 450, 520, 620, 640, 700, 760, 800
Prepared by
Checked by
Approved by
Results are design aids computed by designlink calc (calc.designlink.in) and must be reviewed by a qualified engineer before issue. Ground levels marked "assumed" have no survey level within reach — verify.