SAMPLE NEC breaker sizing — branch, feeder, transformer — this is what your report looks like, generated from demo inputs. Generate yours → 2 free designs every day for every signed-in account · 1 design free on sign-in · ₹99 + GST per design (report + Excel + DXF) · free for DesignLink companies
Report ready — use Print → Save as PDF (A4 landscape).
Design Linkcalc.designlink.in

NEC breaker sizing — branch, feeder, transformer

Sample project — Tower A · Electrical
Generated 28 Nov 2026 17:16
NEC overcurrent device and conductor ampacity for branch circuits and feeders (continuous …
Project code SAMPLE
Minimum device
50.0 A
Standard device
50 A
Conductor ampacity ≥
50.0 A

1. Inputs

GroupInputValueUnit
CircuitWhat to sizeBranch circuit / feeder
CircuitContinuous load (3 h or more)32A
CircuitNon-continuous load10A
CircuitDevice and assembly listed for 100 % continuous operationFalse

2. Results

NEC 210.20 / 215.3 and 210.19 / 215.2

ItemValueUnitNote / basis
Continuous load × 125 %40.0A100 % where listed for continuous operation
Non-continuous load10.0A
Device rating ≥50.0A→ standard 50 A (240.6(A))
Conductor ampacity ≥50.0Abefore ambient / grouping adjustment

3. Checks

CheckResultNote
50 A ≥ 50.0 APASS
Conductor protected by the device (240.4) — choose a conductor with ampacity ≥ the device or use 240.4(B)PASScheck after the correction factors

4. Worked example

OCPD ≥ 1.25 × 32 + 10 = 50.0 A → 50 A

5. Notes

6. Standards and references

Prepared by
Checked by
Approved by

Results are design aids computed by designlink calc (calc.designlink.in) and must be reviewed by a qualified engineer before issue. Ground levels marked "assumed" have no survey level within reach — verify.