Neutral earthing resistor & earthing transformer

Sample project — Tower A · Electrical
Generated 28 Nov 2026 17:16
Resistance earthing of a transformer / generator neutral: resistor value for the earth-fau…
Project code SAMPLE
Resistance
21.2 Ω
Current
300.0 A
Energy
19.1 MJ

1. Inputs

GroupInputValueUnit
SystemSystem line voltage11kV
SystemEarth-fault current limit300A
SystemTime rating10 s
SystemSystem charging current 3·Ic0 (0 = not known)0A
SystemNeutral sourceStar neutral of a transformer / generator
SystemAllowed resistor temperature rise760K

2. Results

Neutral earthing resistor

ItemValueUnitNote / basis
Phase voltage6350.85V
Resistance R = Vph / I21.17Ω
Power during the fault I²R1905.26kW
Energy over 10 s19.05MJ

3. Checks

CheckResultNote
Earth-fault relays pick up well below the limitPASSe.g. 10–20 % of 300 A (typical)

4. Worked example

R = 11 kV / √3 / 300 A = 6351 / 300 = 21.17 Ω; E = I²Rt = 300² × 21.17 × 10 = 19.05 MJ

5. Notes