calc.designlink.inNeutral earthing resistor & earthing transformer
Sample project — Tower A · Electrical
Generated 28 Nov 2026 17:16
Resistance earthing of a transformer / generator neutral: resistor value for the earth-fau…
Project code SAMPLE
1. Inputs
| Group | Input | Value | Unit |
|---|
| System | System line voltage | 11 | kV |
| System | Earth-fault current limit | 300 | A |
| System | Time rating | 10 s | |
| System | System charging current 3·Ic0 (0 = not known) | 0 | A |
| System | Neutral source | Star neutral of a transformer / generator | |
| System | Allowed resistor temperature rise | 760 | K |
2. Results
Neutral earthing resistor
| Item | Value | Unit | Note / basis |
|---|
| Phase voltage | 6350.85 | V | |
| Resistance R = Vph / I | 21.17 | Ω | |
| Power during the fault I²R | 1905.26 | kW | |
| Energy over 10 s | 19.05 | MJ | |
3. Checks
| Check | Result | Note |
|---|
| Earth-fault relays pick up well below the limit | PASS | e.g. 10–20 % of 300 A (typical) |
4. Worked example
R = 11 kV / √3 / 300 A = 6351 / 300 = 21.17 Ω; E = I²Rt = 300² × 21.17 × 10 = 19.05 MJ
5. Notes
- Specify the NER by voltage (Vph), current, time rating and allowed temperature rise; stainless-steel grid resistors in a ventilated enclosure with a neutral CT for the earth-fault relay.
- Low-resistance earthing limits damage at the fault and still trips quickly; high-resistance earthing keeps a process running on the first fault but needs an earth-fault alarm and quick location.
6. Standards and references
- IEC 60909-0:2016 — Short-circuit currents in three-phase a.c. systems — Calculation of currents: Impedance method, voltage factor c (1.05 / 1.10 max, 0.95 min), peak factor κ = 1.02 + 0.98·e^(−3R/X), Ik" = c·Un/(√3·Zk)
- IEEE Std 142-2007 (Green Book) — Recommended practice for grounding of industrial and commercial power systems: Resistance earthing of the system neutral
- IEEE Std 32 — Requirements, terminology and test procedures for neutral grounding devices: Neutral earthing resistor time ratings and temperature rise
Prepared by
Checked by
Approved by
Results are design aids computed by designlink calc (calc.designlink.in) and must be reviewed by a qualified engineer before issue. Ground levels marked "assumed" have no survey level within reach — verify.