PA / voice-alarm coverage

Sample project — Tower A · Sample project — Tower A · 32 speakers · 44 W
Generated 28 Nov 2026 16:09
SPL & STI · NFPA 72 / EN 54-16 / IEC 60268-16
Project code SAMPLE
Floors
1
Speakers
32
Load
44 W
Zones
1
Amplifiers
60 W
STI min
0.36
Checks
all pass · 2 to confirm

1. Design basis

ItemValueBasis
CodeNBCS 2026 (SP 7:2026) Part F cl. 4.9 (c), 3.5.5.2 (g), 3.5.11 (a), Tables 7A–7J col. (10) · IS 2189:2026 · IS 15908 / EN 54-16 & -24 · IEC 60268-16regime
Target level≥ ambient + 15 dB(A), never below 65 dB(A), at 1.5 mdesign criterion — NFPA 72 18.4.3 (+15 dB) / BS 5839-1 & -8 (65 dB(A)); NBCS 2026 sets no SPL value
IntelligibilitySTI ≥ 0.5 (rooms above 60 dB(A) ambient: alarm tone, STI not required)IEC 60268-16 / NFPA 72 Annex D
Uniformity±6 dBproject
SpeakerCeiling 6" 6 W (EN 54-24) (horns in plant rooms, projectors in car parks / warehouses, pendants above 5.5 m)catalogue
PlacementMinimum overlap (±3–4 dB, speech) — spacing 2·(h − 1.5)·tan(θ/2)·k on a grid aligned with the roomcoverage rule
AcousticsRT60 by Sabine from the room volume and finish absorption; direct + reverberant SPL; STI by the Houtgast–Steeneken modulation-transfer approximationstatistical acoustics
Amplifiers / cable100 V line, 20 % headroom, loss ≤ 10 % on 1.5 mm²project
Atriano openings between floors — evaluated floor by floorIEC 60268-16 late-energy principle

2. Checks

CheckResult
Minimum SPL ≥ ambient + 15 dB(A) and ≥ 65 dB(A) in every room (design criterion — NFPA 72 18.4.3 / BS 5839-1 & -8 practice; NBCS 2026 sets no SPL value)PASS
Uniformity within ±6 dB at the listening planePASS
STI ≥ 0.50 in every room (IEC 60268-16 / EN 54-16 voice alarm)PASS
Amplifiers sized with 20 % headroom per zonePASS
100 V line loss ≤ 10 % on every zone cablePASS
PA / voice evacuation applicability — occupancy not set — PA / VE applicability by Tables 7A–7J col. (10) not assessedCONFIRM
Pre-recorded messages in English, Hindi and the vernacular language — enter the local language (NBCS 2026 Part F cl. 4.9 (c))CONFIRM
Zoned per floor and integrated with the FA panel: fire zone and the floors above / below alerted (NBCS 2026 Part F cl. 4.9 (c))PASS
PA on emergency supply — Normal + standby DG with changeover, amplifier battery back-up (NBCS 2026 Part F cl. 3.5.5.2 (g))PASS
PA cabling — Fire-survival cable in metal (MS / GI) conduit; metal conduit or armoured, segregated from power cables (NBCS 2026 Part F cl. 3.5.5.2)PASS
Main PA rack with the main FA panel in the fire command centre (NBCS 2026 Part F cl. 3.5.11 (a))PASS

3. Ground — 32 speakers · 44.2 W

Office 181.1–84.4 dB · STI 0.69 · 6 spkMeeting room80.2–84.1 dB · STI 0.73 · 6 spkCorridor86.2–87.6 dB · STI 0.57 · 7 spkOpen office81.9–85.0 dB · STI 0.7 · 10 spkPlant room111.8–113.1 dB · STI 0.36 (n/a) · 3 spkLift shaftSPK-GR-001 0.75 WSPK-GR-001SPK-GR-002 0.75 WSPK-GR-002SPK-GR-003 0.75 WSPK-GR-003SPK-GR-004 0.75 WSPK-GR-004SPK-GR-005 0.75 WSPK-GR-005SPK-GR-006 0.75 WSPK-GR-006SPK-GR-007 0.75 WSPK-GR-007SPK-GR-008 0.75 WSPK-GR-008SPK-GR-009 0.75 WSPK-GR-009SPK-GR-010 0.75 WSPK-GR-010SPK-GR-011 0.75 WSPK-GR-011SPK-GR-012 0.75 WSPK-GR-012SPK-GR-013 0.75 WSPK-GR-013SPK-GR-014 0.75 WSPK-GR-014SPK-GR-015 0.75 WSPK-GR-015SPK-GR-016 0.75 WSPK-GR-016SPK-GR-017 0.75 WSPK-GR-017SPK-GR-018 0.75 WSPK-GR-018SPK-GR-019 0.75 WSPK-GR-019SPK-GR-020 0.75 WSPK-GR-020SPK-GR-021 0.75 WSPK-GR-021SPK-GR-022 0.75 WSPK-GR-022SPK-GR-023 0.75 WSPK-GR-023SPK-GR-024 0.75 WSPK-GR-024SPK-GR-025 0.75 WSPK-GR-025SPK-GR-026 0.75 WSPK-GR-026SPK-GR-027 0.75 WSPK-GR-027SPK-GR-028 0.75 WSPK-GR-028SPK-GR-029 0.75 WSPK-GR-029SPK-GR-030 7.5 WSPK-GR-030SPK-GR-031 7.5 WSPK-GR-031SPK-GR-032 7.5 WSPK-GR-03255 dB95 dBSPL dB(A) at the listening plane

Rooms

RoomAreaHAmbientRT60TargetSPL min / mean / max±dBS/NSTISpeakersWOK
Office 196.03.2480.6265.081.1 / 82.5 / 84.41.734.50.6964.5PASS
Meeting room96.03.2420.5265.080.2 / 82.0 / 84.11.940.00.7364.5PASS
Corridor65.03.2501.0765.086.2 / 86.8 / 87.60.736.80.5775.25PASS
Open office130.03.2480.6165.081.9 / 83.3 / 85.01.635.30.7107.5PASS
Plant room55.06.0802.9995.0111.8 / 112.1 / 113.10.732.10.36 n/a322.5PASS

Zones & amplifiers

ZoneRoomsSpeakersLoad WAmplifierCableLossOK
GroundR1, R2, C1, R3, R43244.21 × 60 W184 m · 1.5 mm²1.9 %PASS

4. Intelligibility and riser

STI per room (IEC 60268-16) — design minimum 0.50.00.20.40.60.81.0Ground · Office 10.69Ground · Meeting room0.73Ground · Corridor0.57Ground · Open office0.70Ground · Plant room0.36 (alarm tone)
PA zone / amplifier riser (100 V line)GroundZone Ground32 spk · 44.2 W1×60PA rack — VA controller, amplifiers, battery · in the FCCFA panel interface (zone of fire + floors above / below)Supply: Normal + standby DG with changeover, amplifier battery back-up · cable 1.5 mm² fire-survival in metal conduit / armoured

5. Voice evacuation — NBCS 2026 Part F

ItemProjectNBCS 2026
Applicabilityoccupancy not set — PA / VE applicability by Tables 7A–7J col. (10) not assessedTables 7A–7J col. (10)
MessagesEnglish, Hindi + local language (to be confirmed) — pre-recorded, FA-triggeredcl. 4.9 (c)
SupplyNormal + standby DG with changeover, amplifier battery back-upcl. 3.5.5.2 (g)
CablingFire-survival cable in metal (MS / GI) conduitcl. 3.5.5.2
Rackfire command centrecl. 3.5.11 (a)

Alert matrix — fire floor and the floors above / below

Fire onFloors alertedZones
GroundGroundGround

6. Bill of quantities

ItemQtyUnit
Loudspeaker — Ceiling 6" 6 W (EN 54-24)29nos
Loudspeaker — Horn 30 W (plant / outdoor)3nos
100 V amplifier 60 W1nos
Fire-survival speaker cable 2C × 1.5 mm² — in metal conduit, segregated from power cables184m

7. Worked examples — from this project

Worked from this project’s own inputs and results — each value can be traced to the schedules above.

Ground — Corridor (65 m², h 3.2 m)
the room with the lowest STI in this project
Given: Room ambient 50 dB(A) (room-type table), mean absorption α = 0.1 · Speaker 7 × Ceiling 6" 6 W (EN 54-24), 88 dB at 1 W / 1 m, dispersion 120°
1. Target level: Lt = max(ambient + 15, 65) = max(50 + 15, 65) = 65 dB(A)
2. Speaker spacing: s = max(2·(h − hl)·tan(θ/2)·k, 2) = 2 × (3.2 − 1.5) × tan(60°) × 0.7071 = 4.16 m (Minimum overlap (±3–4 dB, speech); grid aligned with the room → 7 speakers)
3. Tap: first tap with 10·log P ≥ Lt + 3 − (Ls − 20·log(1.5·(z − hl))) = 65 + 3 − (88 − 20·log 2.55) = -11.9 dB → taps 0.75, 1.5, 3, 6 W = 0.75 W (10·log 0.75 = -1.2 dB)
4. Direct SPL under a speaker: Ld = Ls + 10·log P − 20·log d = 88 + 10·log 0.75 − 20·log 1.7 = 82.1 dB (on axis, no off-axis loss)
5. Room surface: S = 2·A + perimeter·h = 2 × 65.0 + 57.0 × 3.2 = 312.4 m²
6. Room constant: R = α·S / (1 − α) = 0.1 × 312.4 / 0.9 = 34.7 m²
7. Reverberant SPL (all speakers): Lr = Ls + 10·log P + 10·log(4/R) + 10·log N = 88 + 10·log 0.75 + 10·log(4 / 34.7) + 10·log 7 = 85.8 dB
SPL map: power sum of every speaker's direct (with off-axis loss) + reverberant field on a 0.5 m grid → min / mean / max 86.2 / 86.8 / 87.6 dB
8. Minimum level: Lmin ≥ Lt → 86.2 ≥ 65 dB(A) PASS
9. Uniformity: (Lmax − Lmin) / 2 ≤ 6 dB → (87.6 − 86.2) / 2 = 0.7 dB PASS
10. RT60 (Sabine): T = 0.161·V / (α·S) = 0.161 × 208.0 / (0.1 × 312.4) = 1.07 s (engine 1.07 s)
11. Effective S/N: S/N = Lmean − ambient = 86.8 − 50 = 36.8 dB
12. Modulation transfer: m(F) = 1/√(1 + (2πF·T/13.8)²) · 1/(1 + 10−S/N/10) = m(0.63 Hz) = 0.956 … m(12.5 Hz) = 0.162
13. STI: STI = (mean of clip(10·log(m/(1−m)), ±15) + 15) / 30 over 14 F = T 1.07 s, S/N 36.8 dB = 0.57 (engine 0.57)
14. Intelligibility: STI ≥ 0.5 → 0.57 PASS
Ground — zone Ground (32 speakers)
the zone with the largest 100 V load in this project
1. Zone load: W = Σ speaker taps = 4.5 + 4.5 + 5.25 + 7.5 + 22.5 (rooms) = 44.25 W
2. Amplifier: next size ≥ 1.2 × W = 1.2 × 44.25 = 53.1 W → sizes 60, 120, 240, 360, 500, 1000 W = 1 × 60 W
3. Amplifier capacity: n · Pamp ≥ 1.2 · W → 60 ≥ 53.1 W PASS
4. Cable length: L = 30 m riser + 1.3 × nearest-neighbour chain = 184 m
5. Loop resistance: R = ρCu · 2L / A = 0.0175 × 2 × 184 / 1.5 = 4.29 Ω
6. Line current: I = W / 100 V = 44.25 / 100 = 0.443 A
7. Line loss: ΔU % = I · R / 100 V × 100 = 0.443 × 4.29 = 1.9 % (engine 1.9 % (lengths rounded to 1 m))
8. 100 V line loss: ΔU ≤ 10 % → 1.9 % PASS

Predictive design on statistical room acoustics; STI at commissioning is measured per IEC 60268-16 in every acoustically distinguishable space.

8. Codes and standards

Indian code edition: NBCS 2026 (SP 7:2026) — National Building Construction Standards (replaced NBC 2016 on 30 Apr 2026). SPL / STI targets are design criteria (no NBCS value).

NBCS 2026 clausePDF pageGoverns
Part F Tables 7A–7J col. (10)2791–2819Public address and voice evacuation system — R / NR by occupancy, height, floor area
Part F cl. 4.12766Annunciation and voice-guided egress for high-occupancy areas
Part F cl. 4.9 (c)2789Pre-recorded messages in English, Hindi and the vernacular; FA-integrated alert of the fire zone and surrounding zones / floors
Part F cl. 3.5.5.2 (g)2757PA on normal + standby generator supply with changeover
Part F cl. 3.5.5.2 (last para)2758Fire alarm and PA cables in metal conduit or armoured, segregated from power cables
Part F cl. 3.5.11 (a)2765Fire command centre — main FA panel with the PA
Part D Sec 2 cl. 4.2.1 (jj)1674–1675PA (emergency voice evacuation) among the fire and life-safety loads on emergency power
StandardTitleUsed for
NFPA 72 (2022)National Fire Alarm and Signaling CodeDetection for releasing systems: cross-zoning, spacing, pre-discharge alarms, abort
EN 54 seriesFire detection and fire alarm systems — componentsDetectors, panels, sounders, voice alarm certification
IEC 60268 series (60268-16 STI)Sound-system equipment / objective rating of speech intelligibilityAudio performance and STI
BS 5839-8:2023Design, installation, commissioning and maintenance of voice alarm systemsVoice-alarm intelligibility
NBCS 2026 (SP 7:2026) Part FNational Building Construction Standards — Fire and life safetyMeans of egress (Tables 2–4, cl. 4.4.2), staircase / lobby / lift-well pressurisation (cl. 4.4.2.5, Table 5), emergency lighting (cl. 3.5.6), fire-fighting installations by occupancy (Tables 7A–7J), demand, pumps and duration (Tables 7K / 7M), mains (Table 8), hydrant pressure 3.5–7 bar (cl. 5.1.1 f), sprinklers (cl. 5.1.3), gaseous suppression (cl. 5.1.6 / 5.1.9)