Equipment pad, inertia base & vibration isolators
Sample project — Tower A · Structure & architecture
Generated 28 Nov 2026 16:09 Concrete pad or inertia base for pumps, chillers, DGs and AHUs: mass ratio, pad dimensions… Project code SAMPLE
Base
inertia base
Base mass
2419.2 kg
Pad
2.10 × 1.20 × 400 mm
Isolator
rubber (8 mm) × 4
Efficiency
94.4 %
Bearing
15.0 kN/m²
Impact allowance
20.0 %
1. Inputs
Group
Input
Value
Unit
Equipment
Equipment
Base-mounted pump
Equipment
Operating weight
1200
kg
Equipment
Lowest disturbing speed
1450
rpm
Equipment
Base length
1.8
m
Equipment
Base width
0.9
m
Equipment
Location
On a floor slab
Equipment
Slab allowable load
10
kN/m²
Base and isolation
Base type
Auto by equipment / location
Base and isolation
Inertia mass ratio (base : equipment)
0
Base and isolation
Target isolation efficiency
90
%
Base and isolation
Isolator
Auto by deflection
Base and isolation
Isolators
4
Base and isolation
Pad / base thickness
150
mm
Base and isolation
Impact allowance (bearing check)
Auto — NBCS C1 3.6.1: 20 % motor units, 50 % DG / reciprocating
2. Results
Base
Item
Value
Unit
Note / basis
Type
inertia
Mass ratio
2.0
base : equipment
Plan
2.10 × 1.20 m (equipment + 150 mm margin)
Thickness
400.0
mm
Base mass
2419.2
kg
Total supported mass
3619.2
kg
Isolation
Item
Value
Unit
Note / basis
Disturbing frequency
24.17
Hz
1450 rpm
Required frequency ratio r for 90 % efficiency
3.32
Natural frequency required
7.29
Hz
Static deflection required
4.68
mm
Isolator
rubber — 8 mm rated deflection
Frequency ratio achieved
4.34
fn = 5.57 Hz
Efficiency achieved
94.38
%
Load per isolator (static / with impact)
905 / 965
kg
4 isolators
Bearing
Item
Value
Unit
Note / basis
Impact allowance on the machine weight
20.0
%
NBCS 2026 Part C Sec 1 cl. 3.6.1 (c)/(d): light machinery, shaft or motor units — 20 %
Static pressure (machine + base)
14.09
kN/m²
Design pressure (machine × (1 + impact) + base)
15.02
kN/m²
(1,200 × 1.20 + 2,419) × 9.81 / 2.520 m²
Allowable
10.0
kN/m²
slab design load — confirm with the structural engineer
ASHRAE Applications ch. 49: inertia bases for pumps ≥ 1.5 × pump weight, for reciprocating compressors 3–5 ×; spring isolators need seismic restraint (see Seismic calculator).
Impact: NBCS 2026 (SP 7:2026) Part C Sec 1 cl. 3.6.1 — supporting structures and foundations for light machinery, shaft or motor units 20 %, for reciprocating machinery or power units 50 %; cl. 3.6.2.1 — not less than 20 %. Applied here to the machine weight; the base is dead load.
Pads on grade: M20 concrete, 150 mm minimum, 12 mm bars at 150 c/c both ways, 25 mm isolation joint to the floor; anchor bolts in sleeves. Base mass uses 2400 kg/m³ (reinforced ≈ 2500 kg/m³ — slightly conservative for isolation).
6. Standards and references
ASHRAE Handbook — HVAC Applications ch. 51 — Service water heating: Hot-water demand, storage and recovery
IS 1893 (Part 1):2016 — Criteria for earthquake resistant design of structures — cl. 7.13 non-structural elements: Design seismic force on MEP equipment Fp
IS 2974 (Parts 1–4) — Design and construction of machine foundations: Foundations for reciprocating and rotary machines, mass ratios
IS 456:2000 — Plain and reinforced concrete — code of practice: Pads, plinths, bearing on concrete
NBCS 2026 (SP 7:2026) Part C Sec 1 — National Building Construction Standards — Loads and load effects: Imposed loads, impact allowance (cl. 3.6), wind, seismic by IS 1893 (Part 1)