SAMPLESwimming pool — filtration, heating, plant room — this is what your report looks like, generated from demo inputs.Generate yours →2 free designs every day for every signed-in account · 1 design free on sign-in · ₹99 + GST per design (report + Excel + DXF) · free for DesignLink companies
Report ready — use Print → Save as PDF (A4 landscape).
calc.designlink.in
Swimming pool — filtration, heating, plant room
Sample project — Tower A · Plumbing / PHE
Generated 28 Nov 2026 16:09 Pool volume and bather load, turnover → circulation flow, sand filters and backwash, pump … Project code SAMPLE
Volume
500.0 m³
Circulation
83.3 m³/h
Filters
2 × Ø1600 mm
Pumps
3 × 5.5 kW
Heater
268.5 kW
Bathers (peak)
92
Plant room
13.5 × 6.5 m
1. Inputs
Group
Input
Value
Unit
Pool
Design basis
NBCS 2026 Part E Sec 1 cl. 4.19 — turnover table, user load by depth, displacement 60 / 45 L
Turnover, user load by depth and displacement per NBCS 2026 (SP 7:2026) Part E Sec 1 cl. 4.19.1.2–4.19.1.4; filtration rate and balance-tank method per PWTAG / IS 3328 practice; local health regulations may impose stricter limits.
Evaporation by the Carrier / Smith et al. (1993) correlation used in ASHRAE Applications (Natatoriums); activity factors 0.5 residential, 0.65 hotel, 0.8 competition, 1.0 kids / spa.
Pump head is an estimate — confirm with the filter's dirty-bed pressure drop, heat exchanger and UV data; use the water-network tool for long pipe runs.
Indoor pools: hall air 1 °C above water, 50–60 % RH, dehumidification 0.75 × evaporation — size the pool-hall AHU separately (heat-load tool).
6. Standards and references
CPHEEO Manual on Water Supply & Treatment (1999 / 2024) — Manual on Water Supply and Treatment: Per-capita demand, peak factors, distribution velocity and residual pressure
ASHRAE Handbook — HVAC Applications ch. 51 — Service water heating: Hot-water demand, storage and recovery
IS 1172:1993 — Basic requirements for water supply, drainage and sanitation: Per-capita water requirement for storage sizing
PWTAG Code of Practice (2020) / Swimming Pool Water (2017) — Pool Water Treatment Advisory Group — design and operation of swimming pool water treatment: Turnover periods, filtration rates, bather load, balance tank, disinfection residuals, secondary UV / ozone
IS 3328:1993 — Quality tolerances for water for swimming pools: Water quality limits, chlorine residual, pH, turnover and circulation guidance
NBCS 2026 (SP 7:2026) Part E Sec 1 — National Building Construction Standards — Water supply: Per-capita demand, storage, fixture units and probable flow, pressures and zoning
Prepared by
Checked by
Approved by
Results are design aids computed by designlink calc (calc.designlink.in) and must be reviewed by a qualified engineer before issue. Ground levels marked "assumed" have no survey level within reach — verify.