SAMPLE Swimming pool — filtration, heating, plant room — this is what your report looks like, generated from demo inputs. Generate yours → 2 free designs every day for every signed-in account · 1 design free on sign-in · ₹99 + GST per design (report + Excel + DXF) · free for DesignLink companies
Report ready — use Print → Save as PDF (A4 landscape).
Design Linkcalc.designlink.in

Swimming pool — filtration, heating, plant room

Sample project — Tower A · Plumbing / PHE
Generated 28 Nov 2026 16:09
Pool volume and bather load, turnover → circulation flow, sand filters and backwash, pump …
Project code SAMPLE
Volume
500.0 m³
Circulation
83.3 m³/h
Filters
2 × Ø1600 mm
Pumps
3 × 5.5 kW
Heater
268.5 kW
Bathers (peak)
92
Plant room
13.5 × 6.5 m

1. Inputs

GroupInputValueUnit
PoolDesign basisNBCS 2026 Part E Sec 1 cl. 4.19 — turnover table, user load by depth, displacement 60 / 45 L
PoolPool typeHotel / club leisure
PoolLength25m
PoolWidth12.5m
PoolDepth — shallow end1.2m
PoolDepth — deep end2.0m
PoolEdge typeDeck-level / overflow channel (balance tank)
PoolIndoor poolFalse
PoolTurnover period (blank = by type)h
PoolArea per bather (blank = by type)m²
Filtration and pumpsFiltration rate (blank = by type)m/h
Filtration and pumpsNumber of filters (0 = auto, ≥ 2 for public)0
Filtration and pumpsBackwash rate40m/h
Filtration and pumpsBackwash duration6min
Filtration and pumpsPump head (blank = estimate: static + filter + heater + pipes)m
Filtration and pumpsCirculation pipe run (plant room → pool, one way)30m
Filtration and pumpsPump + motor efficiency60%
Filtration and pumpsStandby pumpTrue
HeatingHeatingHeat pump
HeatingPool water temperature28°C
HeatingDesign ambient air (coldest month)15°C
HeatingRelative humidity60%
HeatingAir speed over water (indoor 0.15, outdoor 2–4)2.0m/s
HeatingFill / make-up water temperature18°C
HeatingInitial heat-up time48h
HeatingPool cover at night (evaporation × 0.3 for 12 h)False
HeatingHeat-pump COP at design4.5
Water treatmentSecondary disinfectionMedium-pressure UV (60 mJ/cm²)
Water treatmentFree chlorine residual1.5mg/L
Water treatmentHypochlorite strength12% available Cl
Water treatmentOperating hours per day12h
Plant roomPlant room sizeAuto — minimum that fits the equipment
Plant roomClear height3.5m

2. Results

Pool and circulation

ItemValueUnitNote / basis
Surface area312.5m²
Average depth1.6m
Volume500.0m³
Wetted perimeter75.0m
Peak bather load (3.4 m²/bather, by depth — NBCS cl. 4.19.1.3)92
Turnover period6.0hNBCS 2026 Part E Sec 1 cl. 4.19.1.2
Circulation flow Q = V / T83.33m³/h23.1 L/s
Edgedeck-level with overflow channel → balance tank

Filtration

ItemValueUnitNote / basis
Design filtration rate25m/h
Filter area required (total)3.33m²
Filters2 × Ø1600 mm2.01 m² each, bed 1.0 m sand 16/30 + support gravel
Actual rate20.72m/h
Backwash flow per filter80.42m³/h40 m/h × 2.01 m²
Backwash water per filter8.04m³6 min; one filter at a time, air scour recommended
Strainer / hair-and-lint basket3 nos on pump suction

Pumps and pipes

ItemValueUnitNote / basis
Pump head24.79mestimate: static 3 + dirty filter 12 + HX 3 + UV 2 + pipe friction + inlets 2
Duty pumps2 × 41.7 m³/hone per filter up to 120 m³/h
Standby1 × same (auto changeover)
Shaft + motor input per pump4.69kWη = 60 %
Motor rating5.5kWIE3, VFD recommended for night turndown
Main suction (≤ 1.5 m/s)Ø160 OD / 145 IDmm
Main return (≤ 2.0 m/s)Ø140 OD / 127 IDmm
Pool inlets11nos≈ 8 m³/h each, spaced ≤ 3 m on the long walls
Main drains2 nos, anti-entrapment grating, ≤ 0.5 m/s across the grille (VGB / EN 13451)

Balance tank

ItemValueUnitNote / basis
Volume26.49m³
Plan area at 2 m depth13.25m²
Fittingslevel probes (low / working / high), make-up float valve, overflow to drain, access hatch

Heat loss and heater (design: 28 °C water, 15 °C air, 60 % RH)

ItemValueUnitNote / basis
Saturation pressure at water / vapour pressure of air3.78 / 1.02kPa
Evaporation, unoccupied (activity factor 0.5)155.15kg/h
Evaporation, occupied (activity factor 0.80)248.24kg/h
Evaporation heat loss169.22kW
Convection54.03kW
Radiation to sky37.69kW
Conduction to ground2.81kW
Steady loss at design263.75kW
Make-up water reheat (average)4.8kW
Initial heat-up 18→28 °C in 48 h121.12kW
Heater duty268.55kWmax(steady + make-up, heat-up + ½ loss)
Heat-pump electrical input (COP 4.5)59.68kW

Water treatment

ItemValueUnitNote / basis
Free chlorine residual1.5mg/LpH 7.2–7.6; combined Cl ≤ 0.5 mg/L
Chlorine demand730.0g/day1 g/m³ baseline + 2.5 g per bather
Sodium hypochlorite 12 %6.08L/day
Acid (HCl 30 %) for pH3.65L/day
Dosing pumps (hypo + acid)2 × 2 L/hORP / pH controlled, 200 L day tanks, bunded
Secondary disinfectionMP-UV 2.1 kW on full flow, 60 mJ/cm²
Flocculant (PAC)0.35 L/h continuous, 0.1 mL/m³
Make-up water9.9m³/dayevaporation + backwash/7 + 30 L per bather dilution
Backwash disposalto drain via break tank / settlement; heat recovery on backwash optional

Plant-room equipment schedule

TagItemSizeQtykW
BTBalance tank26.5 m³, 4.5 × 3.0 × 2.0 m1
F-1Sand filterØ1600 mm1
F-2Sand filterØ1600 mm1
P-1Circulation pump + strainer42 m³/h1
P-2Circulation pump + strainer42 m³/h1
P-3Circulation pump + strainer42 m³/h1
HP-1Heat pump269 kW1
UV-1UV reactor83 m³/h1
DS-1Dosing skid (hypo + acid, 2 × 200 L tanks, bund)2 pumps + controller1
CPControl panel (pumps, VFD, heater, dosing, level)IP541

Pipe schedule (uPVC / ABS, solvent-welded)

ServiceFlow m³/hOD mmID mmVelocity m/s
Main suction (BT → pumps)83.31601451.4
Filtered return to pool83.31401271.83
Per-filter branch41.7110991.5
Backwash to drain80.41251132.23
BTF-1F-2P-1P-2P-3HP-1UV-1DS-1CPPlant room 13.5 × 6.5 m — BT balance tank · F filters · P pumps · HP/HX heater · UV · DS dosing · CP panelHeat-loss breakdown at design (kW)Steady loss + make-upEvaporation 169.2 kWConvection 54.0 kWRadiation 37.7 kWConduction 2.8 kWMake-up reheat 4.8 kW268.5 kWInitial heat-up121.1 kWHeater duty268.5 kWEvaporation 169.2 kW (63 %)Convection 54.0 kW (20 %)Radiation 37.7 kW (14 %)Conduction 2.8 kW (1 %)Make-up reheat 4.8 kW (2 %)Turnoveradopted 6 hNBCS limit 6 h (cl. 4.19.1.2)circulation 83.3 m³/h

3. Checks

CheckResultNote
Filtration rate 20.7 m/h ≤ 25 m/hPASS2 × Ø1600 mm vessels, 2.01 m² each
Turnover 6 h ≤ 6 h for a hotel / club leisure pool (NBCS 2026 cl. 4.19.1.2)PASSNBCS 2026: private outdoor 6 h, private indoor 10 h, public 6, competition 6, wading 1, spa public ½ / private 1
Suction velocity 1.40 m/s ≤ 1.5, return 1.83 m/s ≤ 2.0PASSmain suction Ø160 OD, return Ø140 OD uPVC
Filter vessel Ø1600 mm + 500 mm access fits under 3.5 m clear heightPASSvessel height ≈ 1.5 × dia + 300 legs — else more, smaller filters
Plant room 13.5 × 6.5 m (auto)PASS
Balance tank 26.5 m³ (13.2 m² × 2 m)PASSuser displacement 60 L deep / 45 L shallow (NBCS 2026 cl. 4.19.1.4 (f)) + channel/pipe drain-down + one backwash, ×1.2
User load 92 = Σ area / m² per user by depth (NBCS 2026 cl. 4.19.1.3)PASS≤ 1.5 m: 117 m² / 2.7; > 1.5 m: 195 m² / 4

4. Worked example

Worked from this project’s own inputs and results — each value can be traced to the schedules above.

Turnover, user load and circulation
NBCS 2026 Part E Sec 1 cl. 4.19.1
1. Pool volume: V = L × W × (d1 + d2) / 2 = 25 × 12.5 × (1.2 + 2) / 2 = 500 m³
2. Users (by depth): N = Σ Aband / aband = 117.2 / 2.7 + 195.3 / 4 = 92 users (cl. 4.19.1.3: ≤ 1 m 2.2, ≤ 1.5 m 2.7, > 1.5 m 4.0 m²)
3. Displacement: Vd = Nshallow × 45 + Ndeep × 60 = 5.53 m³ (cl. 4.19.1.4 (f))
4. Circulation flow: Q = V / T = 500 / 6 = 83.3 m³/h (T = 6 h; NBCS limit 6 h)
5. Turnover: T ≤ TNBCS → 6 ≤ 6 h PASS (cl. 4.19.1.2)
6. Filter area: Af = Q / filtration rate = 83.3 / 25 = 3.33 m² (2 × Ø1600 mm → 20.7 m/h)
Heat loss and heater
28 °C water, 15 °C air, outdoor
1. Evaporation (occupied): E = (95 + 0.425 v)(pw − pa) A / 1050 × activity = (95 + 0.425 × 394) × 0.814 × 3364 / 1050 × 0.4536 × 0.80 = 248.2 kg/h (Carrier / Smith; ASHRAE Applications)
2. Evaporation heat: Qe = E × 2454 / 3600 = 248.2 × 2454 / 3600 = 169.2 kW
3. Steady loss: Qloss = Qe + Qconv + Qrad + Qcond = 169.2 + 54.0 + 37.7 + 2.8 = 263.8 kW
4. Heater duty: max(Qloss + Qmake-up, Qheat-up + ½ Qloss) = max(263.8 + 4.8, 121.1 + 131.9) = 268.5 kW

5. Notes

6. Standards and references

Prepared by
Checked by
Approved by

Results are design aids computed by designlink calc (calc.designlink.in) and must be reviewed by a qualified engineer before issue. Ground levels marked "assumed" have no survey level within reach — verify.