Lift-well pressurisation
Sample project — Tower A · Fire
Generated 15 Oct 2026 18:22 Pressurised lift shaft: landing-door leakage (0.06 m² each, BS EN 12101-6, or gaps), shaft… Project code SAMPLE
Fan duty
42347 m³/h
Fan pressure
244 Pa
Motor
7.5 kW
Design ΔP
30 Pa
Governing case
doors closed
Relief damper
0.0 m²
1. Inputs
Group
Input
Value
Unit
Code & criteria
Code basis
India — NBC 2016 Part 4 targets + BS EN 12101-6 method
Code & criteria
Purpose (sets the open-door air speed)
Means of escape — 0.75 m/s
Code & criteria
Lift-well pressure difference, doors closed (0 = code: NBC 30 Pa · EN class · NFPA min)
0
Pa
Code & criteria
Air speed through the open door (0 = by purpose / class)
0
m/s
Code & criteria
Maximum door-opening force (0 = code: India 110 N · EN 100 N · NFPA 133 N)
0
N
Code & criteria
Door-closer force at the handle
40
N
Building
Floors served by the lift well
15
Building
Floor-to-floor height
3.3
m
Building
Outside design temperature — summer
45
°C
Building
Outside design temperature — winter
10
°C
Building
Inside (shaft) temperature
27
°C
Building
Supply injection at least every … floors (above 11 m)
3
Lift well
Lifts in the shaft (landing doors per floor)
2
Lift well
Landing door width
1.1
m
Lift well
Landing door height
2.1
m
Lift well
Door leakage from
BS EN 12101-6 Table A.2 values
Lift well
Shaft vent at the top left open (0 if closed by a damper on fire)
0
m²
Lift well
Include shaft wall leakage (ASHRAE ratios — BS practice leaves it to the unidentified allowance)
False
Lift well
Highest ΔP the landing doors operate at (lift maker)
50
Pa
Landing-doors-open case
Landing doors open at the same time (fire floor + access level)
2
Landing-doors-open case
ΔP across the other closed landing doors
10
Pa
Fan, ducts & air distribution
Allowance for unidentified leakage
25
%
Fan, ducts & air distribution
Duct leakage allowance on the fan
15
%
Fan, ducts & air distribution
Over-pressure control
Barometric pressure-relief damper(s)
Fan, ducts & air distribution
Standby fan (duty + standby)
True
Fan, ducts & air distribution
Duct run fan → farthest outlet (0 = shaft height + 10 m)
0
m
Fan, ducts & air distribution
Duct friction
1.0
Pa/m
Fan, ducts & air distribution
Fittings allowance on duct friction
50
%
Fan, ducts & air distribution
Intake louvre + dampers + grille losses
125
Pa
Fan, ducts & air distribution
Fan total efficiency
60
%
Fan, ducts & air distribution
Supply grille face velocity
3.0
m/s
Fan, ducts & air distribution
Riser duct velocity
8.0
m/s
2. Results
Criteria
Item
Value
Unit
Note / basis
Basis
NBC 2016 Part 4 — 25–30 Pa in lobbies / lift wells; open-door air speed by BS EN 12101-6
Design pressure difference, doors closed
30.0
Pa
Air speed through the open door
0.75
m/s
Maximum door-opening force
110.0
N
Pressure across the other closed doors with the door open
10.0
Pa
BS EN 12101-6
Shaft height
49.5
m
15 floors × 3.3 m
Landing doors
30
nos
Air quantities
Item
Value
Unit
Note / basis
Doors closed (with unidentified leakage)
10.23
m³/s
36,823 m³/h
Doors open — 2 landing door(s) 1.1 × 2.1 m
3.47
m³/s
0.75 m/s × 4.62 m²
Doors open — total
8.98
m³/s
32,317 m³/h
Design (larger)
10.23
m³/s
doors closed
Fan duty (with duct leakage)
11.76
m³/s
42,347 m³/h · 24,924 cfm
Fan, relief & distribution
Item
Value
Unit
Note / basis
Duct run
59.5
m
Duct friction incl. fittings
89.25
Pa
Fan total pressure
244.25
Pa
Shaft power
4.79
kW
Motor
7.5
kW
Fresh-air intake louvre (free area at 2.5 m/s)
4.71
m²
Pressure-relief damper free area
0.0
m²
Air release from the fire floor (vent / shaft / façade)
1.32
m²
at 10 Pa for the open-door air
Injection points
5
nos
L1, L4, L7, L10, L13
Air per injection point
8469.38
m³/h
Supply grille (gross, ≤ face velocity, 75 % free)
1400 × 750
mm
Riser duct
1500 × 1000
mm
≤ 8 m/s
Leakage paths (doors closed)
Path
Basis
Each m²
Total m²
Lift landing doors — 2 per floor × 15 floors
lift landing door
0.0600
1.8000
Pressure difference over the height (balanced injection)
Fan pressure = 60 m × duct friction × (1 + fittings) = 89 + fixed losses + 30 Pa = 244 Pa; shaft power = Q·p/η = 11.763 × 244 / η = 4.79 kW → motor 7.5 kW
Relief: leakage at 50 Pa = 13.205 m³/s; excess = 11.763 − 13.205 = 0.000 m³/s → A = Q / (0.83 √ΔP) = 0.000 m²
Stack: b = 3460 × |1/To − 1/Ts| = 0.652 Pa/m (summer), 0.692 Pa/m (winter); over 49.5 m with Asb ≈ Abo the shaft ΔP varies ± b·H/4 → 21 – 39 Pa
5. Notes
Leakage areas: BS EN 12101-6 Table A.2 (doors), A.3 (windows); wall leakage ratios from the ASHRAE Handbook of Smoke Control Engineering (NFPA 92 Annex). Verify the door schedule and construction with the architect.
Open-door condition: the required air speed through the open door(s), the other doors closed at the reduced pressure — BS EN 12101-6 Annex A method; the fire floor needs an air-release path (vent, shaft or façade opening) sized above.
The fan starts on fire alarm; the intake is taken from a smoke-free location at least 5 m from any smoke outlet; fans, controls and cables are on the fire-protected supply (NBC 2016 Part 4 / BS EN 12101-6).
Commissioning: measure the pressure difference with all doors closed and the air speed with the design doors open (BS EN 12101-13 acceptance test).
6. Standards and references
NBC 2016 Part 4 — National Building Code — Fire and life safety: Occupant load (Table 5), exit width (Table 22), travel distance (Table 21), stair widths
NFPA 101:2021 — Life Safety Code: Means of egress (international option)
NFPA 92 (2021) — Smoke control systems: Pressurisation and smoke-exhaust design and acceptance
EN 81-72:2020 — Firefighters lifts: Fire-fighter lift features
BS EN 12101-6:2005 — Smoke and heat control systems — Specification for pressure differential systems — Kits: System classes A–F, design pressure differences and open-door air speeds, door-opening force, leakage areas of doors / windows (Annex A), calculation method
BS EN 12101-13:2022 — Smoke and heat control systems — Pressure differential systems (PDS) — Design and calculation methods, installation, acceptance testing, routine testing and maintenance: Design and calculation of pressurised stairs, lobbies and lift wells; commissioning (pressure difference doors closed, air speed doors open)
ASHRAE Handbook of Smoke Control Engineering (2012) — Klote, Milke, Turnbull, Kashef, Ferreira — Handbook of Smoke Control Engineering: Flow through leakage paths, wall / floor leakage ratios, stack effect in pressurised stairwells and lift shafts, door-opening force
BS 9999:2017 — Fire safety in the design, management and use of buildings — Code of practice: Protected stairs, fire-fighting shafts and lobbies, when pressurisation is used in place of natural ventilation
Prepared by
Checked by
Approved by
Results are design aids computed by designlink calc (calc.designlink.in) and must be reviewed by a qualified engineer before issue. Ground levels marked "assumed" have no survey level within reach — verify.