Lift-well pressurisation

Sample project — Tower A · Fire
Generated 15 Oct 2026 18:22
Pressurised lift shaft: landing-door leakage (0.06 m² each, BS EN 12101-6, or gaps), shaft…
Project code SAMPLE
Fan duty
42347 m³/h
Fan pressure
244 Pa
Motor
7.5 kW
Design ΔP
30 Pa
Governing case
doors closed
Relief damper
0.0 m²

1. Inputs

GroupInputValueUnit
Code & criteriaCode basisIndia — NBC 2016 Part 4 targets + BS EN 12101-6 method
Code & criteriaPurpose (sets the open-door air speed)Means of escape — 0.75 m/s
Code & criteriaLift-well pressure difference, doors closed (0 = code: NBC 30 Pa · EN class · NFPA min)0Pa
Code & criteriaAir speed through the open door (0 = by purpose / class)0m/s
Code & criteriaMaximum door-opening force (0 = code: India 110 N · EN 100 N · NFPA 133 N)0N
Code & criteriaDoor-closer force at the handle40N
BuildingFloors served by the lift well15
BuildingFloor-to-floor height3.3m
BuildingOutside design temperature — summer45°C
BuildingOutside design temperature — winter10°C
BuildingInside (shaft) temperature27°C
BuildingSupply injection at least every … floors (above 11 m)3
Lift wellLifts in the shaft (landing doors per floor)2
Lift wellLanding door width1.1m
Lift wellLanding door height2.1m
Lift wellDoor leakage fromBS EN 12101-6 Table A.2 values
Lift wellShaft vent at the top left open (0 if closed by a damper on fire)0m²
Lift wellInclude shaft wall leakage (ASHRAE ratios — BS practice leaves it to the unidentified allowance)False
Lift wellHighest ΔP the landing doors operate at (lift maker)50Pa
Landing-doors-open caseLanding doors open at the same time (fire floor + access level)2
Landing-doors-open caseΔP across the other closed landing doors10Pa
Fan, ducts & air distributionAllowance for unidentified leakage25%
Fan, ducts & air distributionDuct leakage allowance on the fan15%
Fan, ducts & air distributionOver-pressure controlBarometric pressure-relief damper(s)
Fan, ducts & air distributionStandby fan (duty + standby)True
Fan, ducts & air distributionDuct run fan → farthest outlet (0 = shaft height + 10 m)0m
Fan, ducts & air distributionDuct friction1.0Pa/m
Fan, ducts & air distributionFittings allowance on duct friction50%
Fan, ducts & air distributionIntake louvre + dampers + grille losses125Pa
Fan, ducts & air distributionFan total efficiency60%
Fan, ducts & air distributionSupply grille face velocity3.0m/s
Fan, ducts & air distributionRiser duct velocity8.0m/s

2. Results

Criteria

ItemValueUnitNote / basis
BasisNBC 2016 Part 4 — 25–30 Pa in lobbies / lift wells; open-door air speed by BS EN 12101-6
Design pressure difference, doors closed30.0Pa
Air speed through the open door0.75m/s
Maximum door-opening force110.0N
Pressure across the other closed doors with the door open10.0PaBS EN 12101-6
Shaft height49.5m15 floors × 3.3 m
Landing doors30nos

Air quantities

ItemValueUnitNote / basis
Doors closed (with unidentified leakage)10.23m³/s36,823 m³/h
Doors open — 2 landing door(s) 1.1 × 2.1 m3.47m³/s0.75 m/s × 4.62 m²
Doors open — total8.98m³/s32,317 m³/h
Design (larger)10.23m³/sdoors closed
Fan duty (with duct leakage)11.76m³/s42,347 m³/h · 24,924 cfm

Fan, relief & distribution

ItemValueUnitNote / basis
Duct run59.5m
Duct friction incl. fittings89.25Pa
Fan total pressure244.25Pa
Shaft power4.79kW
Motor7.5kW
Fresh-air intake louvre (free area at 2.5 m/s)4.71m²
Pressure-relief damper free area0.0m²
Air release from the fire floor (vent / shaft / façade)1.32m²at 10 Pa for the open-door air
Injection points5nosL1, L4, L7, L10, L13
Air per injection point8469.38m³/h
Supply grille (gross, ≤ face velocity, 75 % free)1400 × 750mm
Riser duct1500 × 1000mm≤ 8 m/s

Leakage paths (doors closed)

PathBasisEach m²Total m²
Lift landing doors — 2 per floor × 15 floorslift landing door0.06001.8000

Pressure difference over the height (balanced injection)

Height mSummer PaWinter Pa
0.038.121.4
5.036.523.1
9.934.824.9
14.833.226.6
19.831.628.3
24.830.030.0
29.728.431.7
34.626.833.4
39.625.235.1
44.523.536.9
49.521.938.6

Bill of quantities

ItemQtyUnit
Pressurisation fan, 42,347 m³/h @ 244 Pa, 7.5 kW motor (duty + standby)2nos
Motorised / non-return damper at each fan outlet2nos
Fresh-air intake louvre with bird screen, ≥ 4.71 m² free area (2.5 m/s), away from smoke outlets1set
Riser duct 1500 × 1000 mm, GI sheet, 60 m (fire-rated where outside the protected shaft)297.5m²
Shaft injection grilles 1400 × 750 mm (fire-rated where through the shaft wall)5nos
Interface with the fire-alarm panel (start on alarm, status / fault to FACP), fire-survival cable to the fans1set
LIFT WELLL0L1L2L3L4L5L6L7L8L9L10L11L12L13L14FANFan 42,347 m³/h @ 244 Pa, 7.5 kW × 2No relief damper neededPressure difference over the height (Pa)01020304050min 27max (door force / limit) 50design 30summerwinter

3. Checks

CheckResultNote
Design ΔP 30 Pa ≤ landing-door operating limit (lift maker) (50 Pa)PASSdoor force at the design ΔP n/a
Stack effect: ΔP over the height 21 – 39 Pa within 27 – 50 PaCHECKoutside the band: pressure-sensing VFD, a damper at each injection point, or a lower-leakage shaft
Injection points: 5 (≤ every 3 floors above 11 m)PASSlevels L1, L4, L7, L10, L13

4. Worked example

Doors closed: Q = 0.83 × ΣA × ΔP^(1/2) = 0.83 × 1.8000 × 30^0.5 = 8.183 m³/s; × (1 + 25 % unidentified) = 10.229 m³/s
Doors open: v × A = 0.75 × 4.62 = 3.465 m³/s; other closed doors at 10 Pa: 0.83 × 1.6800 × 10^0.5 (+ walls) × 1.25 = 5.512 m³/s → 8.977 m³/s
Design = max(10.229, 8.977) = 10.229 m³/s (doors closed); fan = × 1.15 duct leakage = 11.763 m³/s = 42,347 m³/h
Fan pressure = 60 m × duct friction × (1 + fittings) = 89 + fixed losses + 30 Pa = 244 Pa; shaft power = Q·p/η = 11.763 × 244 / η = 4.79 kW → motor 7.5 kW
Relief: leakage at 50 Pa = 13.205 m³/s; excess = 11.763 − 13.205 = 0.000 m³/s → A = Q / (0.83 √ΔP) = 0.000 m²
Stack: b = 3460 × |1/To − 1/Ts| = 0.652 Pa/m (summer), 0.692 Pa/m (winter); over 49.5 m with Asb ≈ Abo the shaft ΔP varies ± b·H/4 → 21 – 39 Pa

5. Notes

6. Standards and references

Prepared by
Checked by
Approved by

Results are design aids computed by designlink calc (calc.designlink.in) and must be reviewed by a qualified engineer before issue. Ground levels marked "assumed" have no survey level within reach — verify.