Design Linkcalc.designlink.in

Lobby pressurisation (lift / stair)

Sample project — Tower A · Fire
Generated 15 Oct 2026 18:24
Pressurised lift / stair / fire-fighting lobbies: leakage to the floor, the stair and the …
Project code SAMPLE
Fan duty
46665 m³/h
Fan pressure
244 Pa
Motor
7.5 kW
Design ΔP
30 Pa
Governing case
doors open
Relief damper
0.2 m²

1. Inputs

GroupInputValueUnit
Code & criteriaCode basisIndia — NBC 2016 Part 4 targets + BS EN 12101-6 method
Code & criteriaPurpose (sets the open-door air speed)Means of escape — 0.75 m/s
Code & criteriaLobby pressure difference, doors closed (0 = code: NBC 30 Pa · EN class · NFPA min)0Pa
Code & criteriaAir speed through the open door (0 = by purpose / class)0m/s
Code & criteriaMaximum door-opening force (0 = code: India 110 N · EN 100 N · NFPA 133 N)0N
Code & criteriaDoor-closer force at the handle40N
BuildingFloors with a pressurised lobby15
BuildingFloor-to-floor height3.3m
LobbyLobbyLift + stair (fire-fighting) lobby
LobbyDoors lobby → floor (accommodation)1
LobbyLobby → floor doorSingle leaf — opens into the pressurised space (0.01 m²)
LobbyLobby → floor door width1.0m
LobbyLobby → floor door height2.1m
LobbyDoor leakage fromBS EN 12101-6 Table A.2 values
LobbyLobby → stair doorSingle leaf — opens out of it (0.02 m²)
LobbyLobby → stair door width1.0m
LobbyStair pressurised tooTrue
LobbyStair ΔP (to the floor)50Pa
LobbyLift landing doors into the lobby2
LobbyLift well pressurised tooFalse
LobbyInclude lobby wall leakage (ASHRAE ratios — BS practice leaves it to the unidentified allowance)False
Fire-floor door openLobby → floor doors open at the fire floor1
Fire-floor door openΔP across the lobby's other doors, door open10Pa
Fan, ducts & air distributionAllowance for unidentified leakage25%
Fan, ducts & air distributionDuct leakage allowance on the fan15%
Fan, ducts & air distributionOver-pressure controlBarometric pressure-relief damper(s)
Fan, ducts & air distributionStandby fan (duty + standby)True
Fan, ducts & air distributionDuct run fan → farthest outlet (0 = shaft height + 10 m)0m
Fan, ducts & air distributionDuct friction1.0Pa/m
Fan, ducts & air distributionFittings allowance on duct friction50%
Fan, ducts & air distributionIntake louvre + dampers + grille losses125Pa
Fan, ducts & air distributionFan total efficiency60%
Fan, ducts & air distributionSupply grille face velocity3.0m/s
Fan, ducts & air distributionRiser duct velocity8.0m/s

2. Results

Criteria

ItemValueUnitNote / basis
BasisNBC 2016 Part 4 — 25–30 Pa in lobbies / lift wells; open-door air speed by BS EN 12101-6
Design pressure difference, doors closed30.0Pa
Air speed through the open door0.75m/s
Maximum door-opening force110.0N
Pressure across the other closed doors with the door open10.0PaBS EN 12101-6
Lobbies15nosone per floor, 3.3 m floor to floor
Air per lobby, doors closed2392.21m³/hnet of inflow from a pressurised stair / shaft
Air to the fire-floor lobby, door open7087.33m³/h
Inflow from the stair / lift shaft per lobby267.25m³/h

Air quantities

ItemValueUnitNote / basis
Doors closed (with unidentified leakage)9.97m³/s35,883 m³/h
Doors open — 1 lobby door(s) 1 × 2.1 m at the fire floor1.58m³/s0.75 m/s × 2.10 m²
Doors open — total11.27m³/s40,578 m³/h
Design (larger)11.27m³/sdoors open
Fan duty (with duct leakage)12.96m³/s46,665 m³/h · 27,466 cfm

Fan, relief & distribution

ItemValueUnitNote / basis
Duct run59.5m
Duct friction incl. fittings89.25Pa
Fan total pressure244.25Pa
Shaft power5.28kW
Motor7.5kW
Fresh-air intake louvre (free area at 2.5 m/s)5.19m²
Pressure-relief damper free area0.1962m²
Air release from the fire floor (vent / shaft / façade)0.6001m²at 10 Pa for the open-door air
Injection points15nosL0, L1, L2, L3, L4, L5, L6, L7, L8, L9, L10, L11, L12, L13, L14
Air per injection point7087.33m³/h
Supply grille (gross, ≤ face velocity, 75 % free)1250 × 700mm
Riser duct1550 × 1050mm≤ 8 m/s

Leakage paths (doors closed)

PathBasisEach m²Total m²
Lobby → floor door(s) × 1single leaf, opening INTO the pressurised space0.01000.0100
Lobby ↔ stair door (air IN from the pressurised stair)ΔP 20 Pa0.0200−0.0200
Lift landing doors × 2 (shaft not pressurised)lift landing door0.06000.1200

Bill of quantities

ItemQtyUnit
Pressurisation fan, 46,665 m³/h @ 244 Pa, 7.5 kW motor (duty + standby)2nos
Motorised / non-return damper at each fan outlet2nos
Fresh-air intake louvre with bird screen, ≥ 5.19 m² free area (2.5 m/s), away from smoke outlets1set
Riser duct 1550 × 1050 mm, GI sheet, 60 m (fire-rated where outside the protected shaft)309.4m²
Lobby supply grilles 1250 × 700 mm with motorised damper (fire floor fully open)15nos
Interface with the fire-alarm panel (start on alarm, status / fault to FACP), fire-survival cable to the fans1set
Barometric pressure-relief damper per lobby, 0.20 m² free area, set to 35 Pa (relieves to the floor / a relief shaft)15nos
LOBBIESL0L1L2L3L4L5L6L7L8L9L10L11L12L13L14FANFan 46,665 m³/h @ 244 Pa, 7.5 kW × 2Relief damper 0.20 m²Pressure difference over the height (Pa)010203040506070min 27max (door force / limit) 62design 30summerwinter

3. Checks

CheckResultNote
Pressure hierarchy: stair 50 Pa > lobby 30 Pa > floor 0 PaPASSthe stair must stay above the lobby so smoke cannot pass into the stair
Lobby → stair door force at 20 Pa: 63 N ≤ 110 NPASS
Design ΔP 30 Pa ≤ door-opening force ≤ 110 N (62 Pa)PASSdoor force at the design ΔP 74 N

4. Worked example

Per lobby, doors closed: 0.83 × 0.0100 × 30^0.5 = 0.045 m³/s to the floor + 0.546 m³/s to the stair / lift shaft, × 1.25 unidentified − inflow 0.074 m³/s = 0.665 m³/s; × 15 lobbies = 9.968 m³/s
Fire floor, door open: v × A = 0.75 × 2.10 = 1.575 m³/s + the lobby's other doors at 10 Pa 0.394 m³/s = 1.969 m³/s; + 14 other lobbies × 0.665 = 11.272 m³/s
Design = max(9.968, 11.272) = 11.272 m³/s (doors open); fan = × 1.15 duct leakage = 12.963 m³/s = 46,665 m³/h
Fan pressure = 60 m × duct friction × (1 + fittings) = 89 + fixed losses + 30 Pa = 244 Pa; shaft power = Q·p/η = 12.963 × 244 / η = 5.28 kW → motor 7.5 kW
Door force: F = Fdc + W·A·ΔP / (2(W − d)) = 74 N at 30 Pa; limit 110 N → ΔP max = 2(W − d)(F − Fdc)/(W·A) = 62 Pa
Relief: leakage at 62 Pa = 0.985 m³/s; excess = 12.963 − 0.985 = 1.279 m³/s → A = Q / (0.83 √ΔP) = 0.196 m²

5. Notes

6. Standards and references

Prepared by
Checked by
Approved by

Results are design aids computed by designlink calc (calc.designlink.in) and must be reviewed by a qualified engineer before issue. Ground levels marked "assumed" have no survey level within reach — verify.