SAMPLEStaircase pressurisation — this is what your report looks like, generated from demo inputs.Generate yours →2 free designs every day for every signed-in account · 1 design free on sign-in · ₹99 + GST per design (report + Excel + DXF) · free for DesignLink companies
Report ready — use Print → Save as PDF (A4 landscape).
calc.designlink.in
Staircase pressurisation
Sample project — Tower A · Fire
Generated 15 Oct 2026 18:21 Pressurised escape stair: door leakage (BS EN 12101-6 table or gaps), doors-closed and doo… Project code SAMPLE
Fan duty
9101 m³/h
Fan pressure
264 Pa
Motor
1.5 kW
Design ΔP
50 Pa
Governing case
doors open
Relief damper
0.14 m²
1. Inputs
Group
Input
Value
Unit
Code & criteria
Code basis
India — NBC 2016 Part 4 targets + BS EN 12101-6 method
Code & criteria
Purpose (sets the open-door air speed)
Means of escape — 0.75 m/s
Code & criteria
Design pressure difference, doors closed (0 = code value: NBC 50 Pa · EN class · NFPA min)
0
Pa
Code & criteria
Air speed through the open door (0 = by purpose / class)
0
m/s
Code & criteria
Maximum door-opening force (0 = code: India 110 N · EN 100 N · NFPA 133 N)
0
N
Code & criteria
Door-closer force at the handle
40
N
Building
Floors served by the stair (incl. ground / basements)
15
Building
Floor-to-floor height
3.3
m
Building
Outside design temperature — summer
45
°C
Building
Outside design temperature — winter
10
°C
Building
Inside (shaft) temperature
27
°C
Building
Supply injection at least every … floors (above 11 m)
3
Stair doors & openings
Stair doors per floor
1
Stair doors & openings
Stair door
Single leaf — opens into the pressurised space (0.01 m²)
Stair doors & openings
Stair door width (clear, whole door)
1.0
m
Stair doors & openings
Stair door height
2.1
m
Stair doors & openings
Door leakage from
BS EN 12101-6 Table A.2 values
Stair doors & openings
Final exit doors at ground
1
Stair doors & openings
Final exit door
Double leaf (0.03 m²)
Stair doors & openings
Final exit door width
1.5
m
Stair doors & openings
Final exit door height
2.1
m
Stair doors & openings
Roof / other doors
1
Stair doors & openings
Roof door
Single leaf — opens out of it (0.02 m²)
Stair doors & openings
Windows in the stair
None
Stair doors & openings
Permanent vent at the stair head (0 if the AOV stays shut)
0
m²
Stair doors & openings
Include wall leakage (ASHRAE ratios — BS practice leaves it to the unidentified allowance)
False
Doors-open case
Stair doors open at the same time (fire floor)
1
Doors-open case
Final exit door open at the same time
False
Doors-open case
ΔP across the other closed doors, door open
10
Pa
Fan, ducts & air distribution
Allowance for unidentified leakage
25
%
Fan, ducts & air distribution
Duct leakage allowance on the fan
15
%
Fan, ducts & air distribution
Over-pressure control
Barometric pressure-relief damper(s)
Fan, ducts & air distribution
Standby fan (duty + standby)
True
Fan, ducts & air distribution
Duct run fan → farthest outlet (0 = shaft height + 10 m)
0
m
Fan, ducts & air distribution
Duct friction
1.0
Pa/m
Fan, ducts & air distribution
Fittings allowance on duct friction
50
%
Fan, ducts & air distribution
Intake louvre + dampers + grille losses
125
Pa
Fan, ducts & air distribution
Fan total efficiency
60
%
Fan, ducts & air distribution
Supply grille face velocity
3.0
m/s
Fan, ducts & air distribution
Riser duct velocity
8.0
m/s
2. Results
Criteria
Item
Value
Unit
Note / basis
Basis
NBC 2016 Part 4 — 50 Pa in staircases; open-door air speed by BS EN 12101-6
Design pressure difference, doors closed
50.0
Pa
Air speed through the open door
0.75
m/s
Maximum door-opening force
110.0
N
Pressure across the other closed doors with the door open
10.0
Pa
BS EN 12101-6
Stair height
49.5
m
15 floors × 3.3 m
Air quantities
Item
Value
Unit
Note / basis
Doors closed (with unidentified leakage)
1.47
m³/s
5,282 m³/h
Doors open — 1 stair door(s) 1 × 2.1 m
1.58
m³/s
0.75 m/s × 2.10 m²
Doors open — total
2.2
m³/s
7,914 m³/h
Design (larger)
2.2
m³/s
doors open
Fan duty (with duct leakage)
2.53
m³/s
9,101 m³/h · 5,357 cfm
Fan, relief & distribution
Item
Value
Unit
Note / basis
Duct run
59.5
m
Duct friction incl. fittings
89.25
Pa
Fan total pressure
264.25
Pa
Shaft power
1.11
kW
Motor
1.5
kW
Fresh-air intake louvre (free area at 2.5 m/s)
1.01
m²
Pressure-relief damper free area
0.1379
m²
Air release from the fire floor (vent / shaft / façade)
0.6001
m²
at 10 Pa for the open-door air
Injection points
5
nos
L1, L4, L7, L10, L13
Air per injection point
1820.25
m³/h
Supply grille (gross, ≤ face velocity, 75 % free)
500 × 450
mm
Riser duct
650 × 500
mm
≤ 8 m/s
Leakage paths (doors closed)
Path
Basis
Each m²
Total m²
Stair doors to the floors — 1 per floor × 15 floors
single leaf, opening INTO the pressurised space
0.0100
0.1500
Final exit door(s) × 1
double leaf
0.0300
0.0300
Roof / other door(s) × 1
single leaf, opening OUT of the pressurised space
0.0200
0.0200
Pressure difference over the height (balanced injection)
Fan pressure = 60 m × duct friction × (1 + fittings) = 89 + fixed losses + 50 Pa = 264 Pa; shaft power = Q·p/η = 2.528 × 264 / η = 1.11 kW → motor 1.5 kW
Door force: F = Fdc + W·A·ΔP / (2(W − d)) = 97 N at 50 Pa; limit 110 N → ΔP max = 2(W − d)(F − Fdc)/(W·A) = 62 Pa
Relief: leakage at 62 Pa = 1.629 m³/s; excess = 2.528 − 1.629 = 0.899 m³/s → A = Q / (0.83 √ΔP) = 0.138 m²
Stack: b = 3460 × |1/To − 1/Ts| = 0.652 Pa/m (summer), 0.692 Pa/m (winter); over 49.5 m with Asb ≈ Abo the shaft ΔP varies ± b·H/4 → 41 – 59 Pa
5. Notes
Leakage areas: BS EN 12101-6 Table A.2 (doors), A.3 (windows); wall leakage ratios from the ASHRAE Handbook of Smoke Control Engineering (NFPA 92 Annex). Verify the door schedule and construction with the architect.
Open-door condition: the required air speed through the open door(s), the other doors closed at the reduced pressure — BS EN 12101-6 Annex A method; the fire floor needs an air-release path (vent, shaft or façade opening) sized above.
The fan starts on fire alarm; the intake is taken from a smoke-free location at least 5 m from any smoke outlet; fans, controls and cables are on the fire-protected supply (NBC 2016 Part 4 / BS EN 12101-6).
Commissioning: measure the pressure difference with all doors closed and the air speed with the design doors open (BS EN 12101-13 acceptance test).
6. Standards and references
NBC 2016 Part 4 — National Building Code — Fire and life safety: Occupant load (Table 5), exit width (Table 22), travel distance (Table 21), stair widths
NFPA 101:2021 — Life Safety Code: Means of egress (international option)
NFPA 92 (2021) — Smoke control systems: Pressurisation and smoke-exhaust design and acceptance
BS EN 12101-6:2005 — Smoke and heat control systems — Specification for pressure differential systems — Kits: System classes A–F, design pressure differences and open-door air speeds, door-opening force, leakage areas of doors / windows (Annex A), calculation method
BS EN 12101-13:2022 — Smoke and heat control systems — Pressure differential systems (PDS) — Design and calculation methods, installation, acceptance testing, routine testing and maintenance: Design and calculation of pressurised stairs, lobbies and lift wells; commissioning (pressure difference doors closed, air speed doors open)
ASHRAE Handbook of Smoke Control Engineering (2012) — Klote, Milke, Turnbull, Kashef, Ferreira — Handbook of Smoke Control Engineering: Flow through leakage paths, wall / floor leakage ratios, stack effect in pressurised stairwells and lift shafts, door-opening force
BS 9999:2017 — Fire safety in the design, management and use of buildings — Code of practice: Protected stairs, fire-fighting shafts and lobbies, when pressurisation is used in place of natural ventilation
Prepared by
Checked by
Approved by
Results are design aids computed by designlink calc (calc.designlink.in) and must be reviewed by a qualified engineer before issue. Ground levels marked "assumed" have no survey level within reach — verify.