Psychrometric processes

Sample project — Tower A · HVAC
Generated 28 Nov 2026 16:09
State points and processes on the psychrometric chart: mixing of two air streams, sensible…
Project code SAMPLE
DB / WB
95.0 / 78.0 °F
Grains
117.4 gr/lb
Enthalpy
41.3 Btu/lb

1. Inputs

GroupInputValueUnit
ProcessProcessState point
ProcessAltitude0ft
ProcessCode edition (room-state check)NBCS 2026 Part D Sec 3 cl. 3.6 — 18–26 °C, RH 30–70 %
ProcessRoom-state check — NBCS 2026 D3 cl. 3.6 (18–26 °C, RH 30–70 %)Return / room stream (mixing, ERV)
ProcessAir flow (stream 1 / supply)10000cfm
Stream 1 / enteringDry bulb95°F
Stream 1 / enteringSecond propertyWet bulb °F
Stream 1 / enteringValue78

2. Results

States and process

ItemValueUnitNote / basis
Stream 1 — DB / WB / RH95.0 °F / 78.0 °F / 47 %35.0 °C / 25.6 °C
Stream 1 — humidity ratio117.39gr/lb16.77 g/kg
Stream 1 — enthalpy41.3Btu/lb78.2 kJ/kg
Stream 1 — dew point / specific volume71.8 °F / 14.360 ft³/lb
Psychrometric chart — State pointp = 14.696 psia (0 ft) · DB °F (bottom) / °C (top) · humidity ratio gr/lb (right)304050607080901001100510152025303540020406080100120140160Dry bulb °FW gr/lbWB 40WB 50WB 60WB 70WB 8010%20%30%40%50%60%70%80%90%NBCS D3 cl. 3.6: 18–26 °C, RH 30–70 %11: 95.0 °F (35.0 °C), 117.4 gr/lb

4. Worked example

Worked from this calculation’s own inputs — each value matches the results table above.

State point — from these inputs
site pressure 14.696 psia at 0 ft; constants × 1.0000
Given: State 95.0 °F DB, 78.0 °F WB (47 % RH)
1. Site pressure: p = 14.696 · (1 − 6.8754×10−6 · z)5.2559 = z = 0 ft = 14.696 psia
2. Saturation pressure: pws(T) — Hyland-Wexler = T = 95.0 °F = 0.8162 psia
3. Vapour pressure: pw = RH · pws = 0.473 × 0.8162 = 0.3859 psia
4. Humidity ratio: W = 0.622 · pw / (p − pw) = 0.622 × 0.3859 / (14.696 − 0.3859) = 0.01677 lb/lb (117.4 gr/lb)
5. Enthalpy: h = 0.240·T + W · (1061 + 0.444·T) = 0.240 × 95.0 + 0.01677 × (1061 + 0.444 × 95.0) = 41.3 Btu/lb

5. Notes

6. Standards and references

Prepared by
Checked by
Approved by

Results are design aids computed by designlink calc (calc.designlink.in) and must be reviewed by a qualified engineer before issue. Ground levels marked "assumed" have no survey level within reach — verify.