SAMPLERoof drainage — gutters, outlets, siphonic / RWPs — this is what your report looks like, generated from demo inputs.Generate yours →2 free designs every day for every signed-in account · 1 design free on sign-in · ₹99 + GST per design (report + Excel + DXF) · free for DesignLink companies
Report ready — use Print → Save as PDF (A4 landscape).
calc.designlink.in
Roof drainage — gutters, outlets, siphonic system
Sample project — Tower A · BS EN 12056-3 · BS 8490 / ASPE 45 · NBCS 2026 Part E Sec 2
Generated 28 Nov 2026 16:09 r = 150 mm/h · 12692 m² · 529 L/s Project code SAMPLE
Intensity
150 mm/h
Catchment
12692 m²
Design flow
528.8 L/s
Outlets / RWPs
26 nos
Gutters
3/3 OK
Emergency flow
793.3 L/s
Min. pressure
-7.9 m
1. Design basis
Item
Value
Basis
Design rainfall intensity r
150 mm/h
design value entered
Emergency intensity
225 mm/h
BS 8490 / EN 12056-3 §7 — overflow at the 100-yr storm or 1.5 × design
Kothyari & Garde (1992): i = C·T^0.20·R24^0.33 / t^0.71
Municipal / local minimum
100 mm/h
local bye-law / practice — NBCS 2026 E2 sets no fixed value: intensity from IMD / IRC data (4.5.11.2.3), RWPs for a very short time of concentration (4.5.11.2.5)
siphonic full-bore (BS 8490:2007, ASPE 45, EN 12056-3 Annex)
Emergency system
duplicate siphonic system for 100 % of the emergency flow
independent of the primary system (BS 8490 §6, EN 12056-3 §7); NBCS 2026 E2 4.5.11.6.10: flat roofs need an emergency drain (down take or spout), horizontal outlets 100 % / side gratings 50 % of flow; Fig. 11A overflow weir 50 mm above roof
Indian RWP table (NBCS 2026)
RA = 0.084 · d2.5 / I × 1.44 (PVC / HDPE)
NBCS 2026 Part E Sec 2 4.5.11.6.8, Table 25 and Note; walls + 50 % (one) / + 35 % (two) — Notes 1–2
Roof falls / strainers (flat roofs)
1:150–1:133 smooth, 1:100 stone / tiles, 1:75–1:66 gravel; strainer 1.5–2 × pipe area
NBCS 2026 Part E Sec 2 4.5.11.6.8
Figure 1 — IMD generalised IDF curves for the city (Kothyari–Garde) with the design intensity and the emergency intensity.
2. Roof drainage plan
3. Calculation per gutter run
Area-01 — RWDP-01: gutter run 88.3 m, roof depth 33.1 m, pitch 8°, eave 12 m
Rainwater flow
Plan area A_plan
2926.4 m²
Pitched addition = A_plan × (h/2)/B, h = B·tan 8° = 4.65 m
205.6 m²
Extended / other area
879.1 m²
Wall above roof × 0.5
0.0 m²
Effective catchment A_E
4011.1 m²
Q = C · r · A_E / 3600 = 1 × 150 × 4011.1 / 3600
167.1 L/s
Outlets n = 9 (spacing 9.8 m ≤ 20 m) → tributary per outlet A_E/n = 446 m²
18.6 L/s per outlet
Emergency Q_em = 1 × 225 × 4011.1 / 3600
250.7 L/s
Gutter capacity (BS EN 12056-3)
Gutter 700 (T) × 700 (S) × 325 (H) mm, box / rectangular, laid level
Freeboard 75 mm → design water depth W = H − freeboard
250 mm
Wetted section A_E = (T + S)/2 × W
175000 mm²
Q_SE = 3.48 × 10⁻⁵ × A_E^1.25
124.56 L/s
Depth factor F_D at W/T = 0.357 (Figure 5)
0.78
Shape factor F_S at S/T = 1.00 (Figure 6)
1.00
Q_N = Q_SE × F_D × F_S
97.16 L/s
Q_L = 0.9 × Q_N (factor of safety for non-half-round shapes, 5.1.4)
Area-06: velocities 2.1–5.0 m/s within 1–6; minimum pressure -7.1 m ≥ -8 m
PASS
top of downpipe governs; increase pipe sizes or reduce head if pressure fails
Emergency system: duplicate siphonic system for 225 mm/h (793 L/s total)
PASS
BS 8490 / EN 12056-3 §7: an independent overflow is mandatory for siphonic and box-gutter systems; NBCS 2026 E2 4.5.11.6.10: flat roofs need an emergency drain (down take or spout), horizontal outlets 100 %, side gratings 50 % of flow
6. Review checklist
#
Reviewer's item
This design
Typical comment on a submission
1
Intensity basis
150 mm/h (design value entered)
state the IDF / return period; 150 mm/h without a source is not substantiated
2
Catchment build-up
plan + pitch + extended + walls per EN §4.2, per outlet tributary
sheets that divide the whole roof by outlet count hide the pitch and wall additions
3
F_D / F_S / F_L values
interpolated from Figures 5–6 and Table 6 at the actual W/T, S/T, L/W (shown)
values read off the figure without stating the ratio cannot be checked
4
Long-gutter factor
L/W up to 362
L/W > 500 is outside Table 6 — add outlets rather than extrapolate
the supplier's calculation must show the same for every outlet path
8
Emergency system
100 % duplicate siphonic
mandatory and independent for siphonic / box gutters
7. Worked examples — from this project
Worked from this project’s own inputs and results — each value can be traced to the schedules above.
Area-02 (RWDP-02) — catchment, design flow and outlets
the largest flow of the 3 gutter run(s)
Given: Rainfall r = 150 mm/h (design value entered), emergency 225 mm/h, C = 1 · Roof gutter run L = 90.4 m, depth B = 70.3 m, pitch 8° · Outlets 13 (entered)
NBCS 2026 (SP 7:2026) Part E Sec 2 — National Building Construction Standards — Drainage and sanitation: Sanitary fixtures by occupancy (Tables 1–17), DFU, stacks, vents, building drains, rainwater pipes (Table 25)
ASPE 45-2018 — Siphonic Roof Drainage: Siphonic system design and installation, hydraulic balancing tolerance, materials
IS 1742:1983 — Code of practice for building drainage: Rainwater pipes: roof area per pipe size by rainfall intensity (with NBC 2016 Part 9)
Kothyari & Garde (1992), IMD data — Generalised rainfall intensity–duration–frequency relationship for India: i = C·T^0.20·R24^0.33/t^0.71 with zone constant C and 2-year 24-h rainfall
IS 2527:1984 — Code of practice for fixing rainwater gutters and downpipes for roof drainage: Gutter and downpipe fixing, falls, joints, outlets
Prepared by
Checked by
Approved by
Results are design aids computed by designlink calc (calc.designlink.in) and must be reviewed by a qualified engineer before issue. Ground levels marked "assumed" have no survey level within reach — verify.