SAMPLE Clean room · server room · DG room · transformer room — this is what your report looks like, generated from demo inputs. Generate yours → 2 free designs every day for every signed-in account · 1 design free on sign-in · ₹99 + GST per design (report + Excel + DXF) · free for DesignLink companies
Report ready — use Print → Save as PDF (A4 landscape).
Design Linkcalc.designlink.in

Clean room · server room · DG room · transformer room

Sample project — Tower A · HVAC
Generated 28 Nov 2026 16:09
Clean-room supply air and cooling by ISO class (ISO 14644-1), server-room cooling and airf…
Project code SAMPLE
Cooling
13.1 TR
Units
3 × 7.5 TR
Airflow
12442.3 m³/h
kW/m²
0.667

1. Inputs

GroupInputValueUnit
RoomRoom typeServer / data room
RoomFloor area60m²
RoomClear height3.5m
RoomRoom design temperature24°C
RoomEnvelope + lighting gain3000W
Clean roomOccupants6
Server roomIT load (UPS output)40kW
Server roomUPS / PDU losses in room6%
Server roomSupply–return ΔT11K
Server roomCooling redundancyN+1
Server roomUnit size (0 = auto)0TR

2. Results

Server room

ItemValueUnitNote / basis
IT load + UPS/PDU losses42.4kW
Envelope, lighting, people3.78kW
Total cooling (SHR ≈ 0.99)46.18kW13.1 TR
Airflow at ΔT 11 K12442.33m³/h7323 cfm · 59 ACH
Units3 × 7.5 TR (N+1: 2 duty)
Cooling density0.6667kW/m²
Fresh air (pressurisation)180.0m³/h≈ 0.2 ACH or 30 m³/h per person
Inside conditions18–27 °C, RH 8–60 % (NBCS 2026 Part D Sec 3 cl. 13.4.4; lower RH limit 50 / 35 % with corrosive gases)
Recommendedprecision AC with set-points towards 27 °C where the equipment allows, cold-aisle containment above 5 kW/rack
Server room — hot / cold aisle airflow (3 × 7.5 TR, N+1)raised-floor supply plenumCRACCRACrack row Arack row BCOLD AISLEHOT AISLEHOT AISLEIT 40 kW (0.67 kW/m²) · supply 12,442 m³/h at ΔT 11 K · inside 18–27 °C, RH 8–60 % (NBCS D3 13.4.4)

3. Checks

CheckResultNote
3 × 7.5 TR installed ≥ 13.1 TR with N+1PASS

4. Worked example

Worked from this project’s own inputs and results — each value can be traced to the schedules above.

Server room — 40 kW IT on 60 m²
this room's own inputs; inside conditions per NBCS 2026 Part D Sec 3 cl. 13.4.4
Given: Loads IT 40 kW, UPS/PDU loss 6 %, envelope 3 kW, 6 persons, ΔT 11 K, N+1
1. UPS / PDU loss: qu = IT·% = 40 × 6 % = 2.4 kW
2. Total cooling: q = IT + qu + env + 0.13·n = 40 + 2.40 + 3 + 0.13 × 6 = 46.18 kW / 3.517 = 13.13 TR
3. Airflow: Q = qs/(ρ·cp·ΔT) = 45,850/(1.2 × 1005 × 11) × 3600 = 12 442 m³/h (59 ACH)
4. Units: n = ⌈TR/unit⌉ + redundancy = ⌈13.13/7.5⌉ = 2, N+1 = 3 nos
5. Capacity: duty units × unit ≥ load → 2 × 7.5 = 15 ≥ 13.13 TR PASS
6. Inside conditions: NBCS D3 13.4.4 → 18–27 °C, RH 8–60 %; room set-point 24 °C PASS

5. Notes

6. Standards and references

Prepared by
Checked by
Approved by

Results are design aids computed by designlink calc (calc.designlink.in) and must be reviewed by a qualified engineer before issue. Ground levels marked "assumed" have no survey level within reach — verify.