Sanitary fixtures & car parking (NBCS 2026 / NBC 2016)
Sample project — Tower A · Structure & architecture
Generated 28 Nov 2026 16:09 Water closets, urinals, wash basins, baths, drinking water and cleaner's sinks per gender … Project code SAMPLE
Occupants
500
WC (M / F)
10 / 17
Urinals
9
Wash basins (M / F)
10 / 10
ECS
100
Parking area
3500.0 m²
Accessible toilets
1
Code
NBCS Table 1
1. Inputs
Group
Input
Value
Unit
Occupancy
Occupancy (NBCS 2026 Part E Sec 2 table)
Office buildings — Table 1
Occupancy
Code edition (offices)
NBCS 2026 (SP 7:2026) Part E Sec 2 Table 1
Occupancy
Floors served
1
Occupants
Floor area (built-up, for parking and the population)
5000
m²
Occupants
Main population (0 = from area where NBCS E1 4.1 gives a rate)
7. Drinking water fountain / water station: 1 per 100 persons or part (not inside toilets, 4.2.5.1 c; water stations allowed, j) = 5
8. Cleaner's sink: 1 per floor = 1
9. Accessible unisex toilets: 4.2.5.1 → good practice [E-2(2)]; tool: ≥ 1 per floor and 1 per 500 persons = 1
10. Parking: ECS = A / 100 × ratio = 5000 / 100 × 2 = 100 ECS(bye-law ratio (not in NBCS))
5. Notes
Ablution tap in each WC; toilet suite (WC + basin, optional shower) for executive / officer rooms and conference halls, pantry optional (Table 1 i).
Space for one janitor per toilet core (Note 2). Male / female taken as half / half unless entered (Note 3).
One fixture is the minimum for the number of persons or part thereof (4.2.5.1 a); drinking fountains not inside toilets (c); water stations / hand-wash points may replace fountains where food is eaten indoors (j).
Executives and meeting / conference rooms: individual toilets and pantry as the user requires (4.2.5.1 h). Emergency shower + eye-wash where skin contamination is possible (d).
Code basis: NBCS 2026 Part E Sec 2 Table 1 (cl. 4.2.5.1; PDF p2591). NBC 2016 Part 9 Sec 2 Table 1 is offered as the office option (same counts).
Parking ratios come from the state / municipal bye-law — enter that value; URDPFI figures are only a starting point.
6. Standards and references
NBCS 2026 (SP 7:2026) Part E Sec 1 — National Building Construction Standards — Water supply: Per-capita demand, storage, fixture units and probable flow, pressures and zoning
NBCS 2026 (SP 7:2026) Part E Sec 2 — National Building Construction Standards — Drainage and sanitation: Sanitary fixtures by occupancy (Tables 1–17), DFU, stacks, vents, building drains, rainwater pipes (Table 25)
NBC 2016 Part 9 Sec 1 — National Building Code — Plumbing services: water supply, drainage and sanitation: Sanitary fixture counts by occupancy; drainage fixture units, soil / waste / vent stacks and building drains
URDPFI Guidelines 2014 (MoHUA) — Urban and Regional Development Plans Formulation and Implementation: Parking norms (ECS per 100 m²) by land use
Prepared by
Checked by
Approved by
Results are design aids computed by designlink calc (calc.designlink.in) and must be reviewed by a qualified engineer before issue. Ground levels marked "assumed" have no survey level within reach — verify.