| Item | Value |
|---|---|
| System | SCADA |
| Template profile | detailed |
| Spare on hardwired points | 15 % per type, rounded up per system |
| Protocols | BACnet/IP · BACnet MS/TP · Modbus RTU (RS-485) |
| Code regime | Indian — NBCS 2026 (SP 7:2026), which replaced NBC 2016 on 30 Apr 2026 |
| Sr | System | Location | Qty | AI | DI | AO | DO | SI | Hardwired | Total incl. spare |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | HT breaker (33 kV / 11 kV) | Substation · GF · HT room | 4 | 0 | 12 | 0 | 0 | 80 | 12 | 94 |
| 2 | Power / distribution transformer | Substation · GF · Transformer bay | 2 | 4 | 12 | 0 | 0 | 0 | 16 | 19 |
| 3 | LT main ACB / bus coupler / capacitor source | Substation · GF · LT room | 6 | 0 | 24 | 0 | 12 | 120 | 36 | 162 |
| 4 | DG set with synchronising panel | Substation · GF · DG room | 2 | 6 | 6 | 0 | 0 | 60 | 12 | 74 |
| 5 | Multi-function meter — LT panel feeder | Substation · GF · LT room | 40 | 0 | 0 | 0 | 0 | 800 | 0 | 800 |
| 6 | SCADA PLC panel health monitoring | Substation · GF · SCADA room | 1 | 0 | 2 | 0 | 0 | 0 | 2 | 3 |
| TOTAL | 55 | 10 | 56 | 0 | 12 | 1060 | 78 | 1151 |
| Sr | Description | Qty | AI | DI | AO | DO | SI | Mon | Ctl | Alm | Remarks |
|---|---|---|---|---|---|---|---|---|---|---|---|
| ELECTRICAL | |||||||||||
| 1 | HT breaker (33 kV / 11 kV) Substation · GF · HT room | 4 | 80 | ||||||||
| i | Breaker ON / OFF Status | 4 | ● | Potential Free Contact to SCADA from HT / LT Panel | |||||||
| ii | Breaker Trip Status | 4 | ● | ● | Potential Free Contact to SCADA from HT / LT Panel | ||||||
| iii | Breaker Auto / Manual Status | 4 | ● | Potential Free Contact to SCADA from HT / LT Panel | |||||||
| iv | Protocol integration (soft points) | 80 | ● | Modbus/BACnet Integration — MFM at 20 registers per breaker | |||||||
| 2 | Power / distribution transformer Substation · GF · Transformer bay | 2 | |||||||||
| i | Transformer HV / LV Breaker ON / OFF Status | 2 | ● | A transformer has no ON/OFF of its own — this is its incomer and outgoing breaker status. Potential Free Contact to SCADA from HT / LT Panel | |||||||
| ii | Transformer Trip Status | 2 | ● | ● | Potential Free Contact to SCADA from HT / LT Panel | ||||||
| iii | Winding Temperature Alarm | 2 | ● | ● | Potential Free Contact to SCADA from HT / LT Panel | ||||||
| iv | Winding Temperature Trip | 2 | ● | ● | Potential Free Contact to SCADA from HT / LT Panel | ||||||
| v | Oil Temperature Alarm | 2 | ● | ● | Potential Free Contact to SCADA from HT / LT Panel | ||||||
| vi | Oil Temperature Trip | 2 | ● | ● | Potential Free Contact to SCADA from HT / LT Panel | ||||||
| vii | Winding Temperature Value | 2 | ● | 4-20 mA output from WTI. Previously only alarm and trip contacts — no trendable value. | |||||||
| viii | Oil Temperature Value | 2 | ● | 4-20 mA output from OTI. Previously only alarm and trip contacts — no trendable value. | |||||||
| 3 | LT main ACB / bus coupler / capacitor source Substation · GF · LT room | 6 | 120 | ||||||||
| i | Breaker ON / OFF Command | 12 | ● | Potential Free Contact from SCADA to LT Panel. 2 DO per breaker (close and open), subject to the local/remote selector being in Remote. Scope of remote switchin | |||||||
| ii | Breaker ON / OFF Status | 6 | ● | Potential Free Contact to SCADA from HT / LT Panel | |||||||
| iii | Breaker Trip Status | 6 | ● | ● | Potential Free Contact to SCADA from HT / LT Panel | ||||||
| iv | Breaker Auto / Manual Status | 6 | ● | Potential Free Contact to SCADA from HT / LT Panel | |||||||
| v | Breaker Spring Charged Status | 6 | ● | Potential Free Contact to SCADA from HT / LT Panel | |||||||
| vi | Protocol integration (soft points) | 120 | ● | Modbus/BACnet Integration — MFM at 20 registers per breaker | |||||||
| 4 | DG set with synchronising panel Substation · GF · DG room | 2 | 60 | ||||||||
| i | DG Internal and Outer Fuel Tank Low Level | 4 | ● | ● | Sensor & field wiring — flame proof level switch | ||||||
| ii | DG Fuel Tank Continuous Level Measurement | 4 | ● | Level switches alone give no available run time. 4-20 mA transmitter on day and bulk tanks. | |||||||
| iii | DG Battery Under Voltage Fault | 2 | ● | ● | Sensor & field wiring — DC voltage transducer | ||||||
| iv | DG Battery Voltage Value | 2 | ● | The DC voltage transducer is already provided; its analogue output was discarded and only a threshold contact was taken. | |||||||
| v | Protocol integration (soft points) | 60 | ● | Modbus/BACnet Integration — 30 parameters per set: start/stop, sync panel status, auto/manual, on-load/off-load, low oil pressure warning and shutdown, hot wate | |||||||
| ENERGY AND METERING | |||||||||||
| 5 | Multi-function meter — LT panel feeder Substation · GF · LT room | 40 | 800 | ||||||||
| i | Protocol integration (soft points) | 800 | ● | MOVED from the BMS I/O Summary and re-based at 20 registers per meter. The SCADA polls these meters once; the BMS reads a 5-parameter subset from the SCADA serv | |||||||
| SYSTEM HEALTH | |||||||||||
| 6 | SCADA PLC panel health monitoring Substation · GF · SCADA room | 1 | |||||||||
| i | Panel Door Open Status | 1 | ● | ● | |||||||
| ii | Panel Auxiliary Supply Healthy Status | 1 | ● | ● | PLC auxiliary supply is from the substation UPS / DC system; loss of it stops event recording. |
| Device | Quantity | Principal application |
|---|---|---|
| Transformer WTI/OTI with 4-20 mA Output | 4 | Power / distribution transformer (4) |
| Flame Proof Level Switch | 4 | DG set with synchronising panel (4) |
| Fuel Level Transmitter | 4 | DG set with synchronising panel (4) |
| DC Voltage Transducer | 2 | DG set with synchronising panel (2) |
| Subsystem | Units | SI | Per unit | Nature |
|---|---|---|---|---|
| HT breaker (33 kV / 11 kV) | 4 | 80 | 20 | Modbus/BACnet Integration — MFM at 20 registers per breaker |
| LT main ACB / bus coupler / capacitor source | 6 | 120 | 20 | Modbus/BACnet Integration — MFM at 20 registers per breaker |
| DG set with synchronising panel | 2 | 60 | 30 | Modbus/BACnet Integration — 30 parameters per set: start/stop, sync panel status, auto/manual, on-load/off-load, low oil pressure warning and shutdown, hot wate |
| Multi-function meter — LT panel feeder | 40 | 800 | 20 | MOVED from the BMS I/O Summary and re-based at 20 registers per meter. The SCADA polls these meters once; the BMS reads a 5-parameter subset from the SCADA serv |
| Panel | Location | Trunk | Ctrl | DI | DO | AI | AO | Modules | Spare ch. | Equipment |
|---|---|---|---|---|---|---|---|---|---|---|
| RTU-GF-01 | Substation · floor GF · DG room | NLC-01/T1 | 1 | 6 | 0 | 6 | 0 | 2 | 12 | DG-01, DG-02 |
| RTU-GF-02 | Substation · floor GF · HT room | NLC-01/T1 | 1 | 12 | 0 | 0 | 0 | 1 | 4 | HT-VCB-01, HT-VCB-02, HT-VCB-03, HT-VCB-04 |
| RTU-GF-03 | Substation · floor GF · LT room | NLC-01/T1 | 1 | 24 | 12 | 0 | 0 | 4 | 12 | LT-ACB-01, LT-ACB-02, LT-ACB-03, LT-ACB-04, LT-ACB-05, LT-ACB-06 |
| RTU-GF-04 | Substation · floor GF · SCADA room | NLC-01/T1 | 1 | 2 | 0 | 0 | 0 | 1 | 14 | SCADA-PLC |
| RTU-GF-05 | Substation · floor GF · Transformer bay | NLC-01/T1 | 1 | 12 | 0 | 4 | 0 | 2 | 8 | TR-01, TR-02 |
| Item | Qty | Note |
|---|---|---|
| BMS server (head-end) with software licence | 2 | hot standby |
| Operator workstation with 2 × 24" monitors | 2 | |
| Core network switch (L3, managed) | 1 | |
| Network-level controller (NLC / supervisory) | 1 | BACnet/IP backbone |
| RTU / PLC panel enclosure IP54 | 5 | |
| DDC controller | 5 | ≤ 256 points each |
| DI module, 16 channels | 6 | |
| DO module, 8 channels | 2 | |
| AI module, 8 channels | 2 | |
| Third-party integration (gateway / driver licence) | 4 | HT breaker (33 kV / 11 kV), LT main ACB / bus coupler / capacitor source, DG set with synchronising panel, Multi-function meter — LT panel feeder |
Worked from this project’s own inputs and results — each value can be traced to the schedules above.
Indian code edition: NBCS 2026 (SP 7:2026) — National Building Construction Standards (replaced NBC 2016 on 30 Apr 2026).
| NBCS 2026 clause | PDF page | Governs |
|---|---|---|
| Part D Sec 2 cl. 4.2 | 1671– | Substation and switch rooms — HV, transformer and LV switchgear monitored by the SCADA |
| Part D Sec 2 cl. 4.2.1 (jj) | 1674–1675 | Fire and life-safety loads on normal + standby supply with changeover |
| Part D Sec 2 cl. 4.3–4.5 | 1680–1681 | DG sets; battery storage with gas monitoring; multiple sources — synchronisation and priority |
| Part D Sec 2 cl. 4.8 | 1682 | Substation safety |
| Part D Sec 2 cl. 10.4.2 | 1748 | Integration of substation, renewable and standby generation with the BMS |
| Standard | Title | Used for |
|---|---|---|
| ISO 16484 (Parts 1–6) | Building automation and control systems | System design, hardware, functions, data communication (BACnet) for the BMS |
| ASHRAE Standard 135 / ISO 16484-5 (BACnet) | Data communication protocol for building automation and control networks | Backbone and controller network protocol |
| ASHRAE Guideline 36 | High-performance sequences of operation for HVAC systems | Control narratives for AHUs, plants and zones |
| ASHRAE Guideline 13 | Specifying building automation systems | Point classification, spare capacity, graphics and alarm philosophy |
| Modbus Application Protocol V1.1b3 / Serial Line V1.02 | Modbus protocol specifications | Third-party integration of drives, meters, chillers, UPS and plant PLCs |
| IEC 61131-2 / -3 | Programmable controllers — equipment requirements and programming languages | PLC panels for tunnel / car-park ventilation, lighting and electrical SCADA |
| IEC 61439-1/2:2020 / IS/IEC 61439 | Low-voltage switchgear and controlgear assemblies | Panel construction (TTA/PTTA), busbar short-time withstand (Icw 1 s), temperature rise, IP rating |
| IEC 62443 (series) | Security for industrial automation and control systems | Zones and conduits, user management, hardening of the automation network |
| IEC 61850 | Communication networks and systems for power utility automation | Substation SCADA — relays, IEDs, GOOSE / MMS |
| IEC 60870-5-104 | Telecontrol equipment and systems — network access | Electrical SCADA telecontrol over TCP/IP |
| NBCS 2026 (SP 7:2026) Part D Sec 2 | National Building Construction Standards — Electrical and allied installations | Load assessment and diversity, circuits, cables (4-core), earthing, lightning protection, standby supply for fire & life-safety loads |
| NBCS 2026 (SP 7:2026) Part D Sec 3 | National Building Construction Standards — Air conditioning, heating and mechanical ventilation | Design conditions (Table 3), ventilation (Table 7), duct velocities (Table 18), clean rooms (Table 31), automation |
| NBCS 2026 (SP 7:2026) Part D Sec 5 | National Building Construction Standards — Lifts, escalators, moving walks and power-driven parking | Lift traffic, fire-fighting lifts, controls |
| NBCS 2026 (SP 7:2026) Part D Sec 6 | National Building Construction Standards — Information and communication enabled installations | Structured cabling, Wi-Fi (IEEE 802.11ax/be), ICT spaces |
| NBCS 2026 (SP 7:2026) Part F | National Building Construction Standards — Fire and life safety | Means of egress (Tables 2–4, cl. 4.4.2), staircase / lobby / lift-well pressurisation (cl. 4.4.2.5, Table 5), emergency lighting (cl. 3.5.6), fire-fighting installations by occupancy (Tables 7A–7J), demand, pumps and duration (Tables 7K / 7M), mains (Table 8), hydrant pressure 3.5–7 bar (cl. 5.1.1 f), sprinklers (cl. 5.1.3), gaseous suppression (cl. 5.1.6 / 5.1.9) |
| CEA (Measures relating to Safety and Electric Supply) Regulations, 2023 | Central Electricity Authority safety regulations | Statutory safety requirements for installations |
| IS 732:2019 | Code of practice for electrical wiring installations | Voltage-drop limits, cable selection, protection coordination (adopts IEC 60364) |
| IS 3043:2018 | Code of practice for earthing | Earth bus, strip sizing, earthing of panels (future earthing tool) |
| CPWD General Specifications for Electrical Works Part VI (BMS) | Building management system specification | Panels, cabling, controllers and head end for CPWD works |
Results are design aids computed by designlink calc (calc.designlink.in) and must be reviewed by a qualified engineer before issue. Ground levels marked "assumed" have no survey level within reach — verify.