Seismic restraint of MEP equipment

Sample project — Tower A · Structure & architecture
Generated 28 Nov 2026 16:09
Design seismic force on non-structural equipment (IS 1893 Part 1 cl. 7.13 or ASCE 7-16 ch.…
Project code SAMPLE
Fp
7.063 kN
Fp / Wp
0.144
Overturning
8.476 kN·m
Tension / anchor
0.0 kN
Anchor
M8 × 4

1. Inputs

GroupInputValueUnit
Code and siteCodeIS 1893 (Part 1):2016 cl. 7.13 — Indian
Code and siteSeismic zone (IS 1893)IV — Z 0.24
Code and siteImportance factor Ip1.5 — life-safety / essential (fire pumps, hospitals, DG, emergency power)
Code and siteBuilding height30m
Code and siteHeight of the equipment floor above base30m
EquipmentEquipmentChiller / cooling tower / rigid plant (ap 1.0, Rp 2.5)
EquipmentOperating weight5000kg
EquipmentHeight of the centre of gravity1.2m
EquipmentAnchor spacing across (short direction)1.2m
EquipmentAnchor spacing along2.4m
EquipmentAnchors4
EquipmentOn vibration isolators (restrained springs / snubbers)False
EquipmentConcreteM25

2. Results

Seismic force

ItemValueUnitNote / basis
Code basisIS 1893 (Part 1):2016 — kept by NBCS 2026 Part C Sec 1 cl. 5 (good practice C-1(6))
BasisFp = (Z/2)(1 + x/h)(ap/Rp)·Ip·Wp = (0.24/2)(1 + 30/30)(1.0/2.5)·1.5·49.0 — IS 1893 (Part 1):2016 cl. 7.13.3 (NBCS 2026 C1 cl. 5 → C-1(6))
ap / Rp1.0 / 2.5
Ip1.5
Fp7.06kN
Fp / Wp0.144g
Vertical component Ev3.92kNEv = (2/3)·(Z/2)·Wp — IS 1893 (Part 1):2016 cl. 6.4.6 (vertical = 2/3 horizontal; zero-period value, rigid equipment)

Overturning and anchors

ItemValueUnitNote / basis
Overturning moment Fp·hcg8.48kN·m
Resisting (Wp − Ev)·b/227.08kN·m
Tension per anchor0.0kN2 anchors on the uplift side
Shear per anchor1.77kN
AnchorM8 — 2.4 kN / 3.6 kN
Utilisation × 1.50.7358
Restraintrigid anchors (no isolators)
Free-body elevation (short direction)Fp = 7.06 kNWp = 49.05 kNEv = 3.92 kNhcg 1.2 mb = 1.2 m (anchor spacing)T = 0.00 kN/anchorV = 1.77 kN/anchorMot = Fp·hcg = 8.48 kN·m · Mr = (Wp − Ev)·b/2 = 27.08 kN·m4 × M8 anchors, 2 on the uplift sideFp / Wp vs height in the building — IS 1893 (Part 1):2016 cl. 7.13.300.050.10.150.200.20.40.60.81x / h (equipment level / building height)Fp / Wpminimum 0.1 Wpthis equipment 0.144

3. Checks

CheckResultNote
Anchors M8 × 4: utilisation 0.74 ≤ 1.0 (SF 1.5)PASS
Overturning resisted by self-weightPASS

4. Worked example

Worked from this project’s own inputs and results — each value can be traced to the schedules above.

Seismic restraint — chiller, 5,000 kg at x = 30 m of h = 30 m
this project's own inputs; IS 1893 (Part 1):2016 cl. 7.13.3
Given: Site zone IV, Z = 0.24 · Equipment Wp = 49.05 kN, ap = 1.0, Rp = 2.5, Ip = 1.5, hcg = 1.2 m, b = 1.2 m, 4 anchors
1. Design force: Fp = (Z/2)(1 + x/h)(ap/Rp)·Ip·Wp = (0.24/2)(1 + 30/30)(1.0/2.5) × 1.5 × 49.05 = 7.06 kN
2. Minimum: Fp ≥ 0.1·Wp → 7.06 vs 4.91 → 7.06 kN PASS (cl. 7.13.3)
3. Vertical component: Ev = (2/3)(Z/2)·Wp = (2/3)(0.24/2) × 49.05 = 3.92 kN (IS 1893 cl. 6.4.6)
4. Overturning: Mot = Fp·hcg = 7.06 × 1.2 = 8.48 kN·m
5. Resisting: Mr = (Wp − Ev)·b/2 = (49.05 − 3.92) × 1.2/2 = 27.08 kN·m
6. Tension per anchor: T = (Mot − Mr)/b/(n/2) ≥ 0 = (8.48 − 27.08) / 1.2 / 2 = 0 kN
7. Shear per anchor: V = Fp/n = 7.06 / 4 = 1.77 kN
8. Anchor M8: (T/N + V/Vrec) × 1.5 ≤ 1 → (0.00/2.4 + 1.77/3.6) × 1.5 = 0.74 PASS