SAMPLE Auto single line diagram — this is what your report looks like, generated from demo inputs. Generate yours → 2 free designs every day for every signed-in account · 1 design free on sign-in · ₹99 + GST per design (report + Excel + DXF) · free for DesignLink companies
Report ready — use Print → Save as PDF (A3 landscape).
Design Linkcalc.designlink.in

Single line diagram — summary report

Sample building · Indian regime · NBCS 2026 (SP 7:2026) Part D Sec 2
Generated 28 Nov 2026 16:09
AUTO SLD from the voltage-drop cascade
Project code SAMPLE
Panels
2
Feeders
9
Connected load
319.0 kW
DL(N) demand
319.0 kW
DL(F) F&LS
105.0 kW
F&LS feeders
2

1. Single line diagram (preview)

11 KV DISCOM SUPPLYRMU 11.0 KV11KV XLPE CABLEHT PANEL 11.0 KV11KV XLPE CABLEMLTP-01 · MAIN LT PANELCL 319.0 kW · DL(N) 319.0 kW · DL(F) 105.0 kW1600A 4P BUS · 50 kA1600A 4P ACB 50kA EDO TYPETRTR-1 1000 kVA 11KV/0.433KV1250A 4P ACB 50kA MDO TYPEGDG-1 750 kVAF1 SMDB-1F2 LIFT-1 · F&LSF3 CHILLER-1F4 SPARE1600A 4P BUS · 50 kA1600A 4P ACB 50kA EDO TYPETRTR-2 1000 kVA 11KV/0.433KVF5 FIRE PUMP PANEL · F&LSF6 SPAREBC-1DB-01 · SMDB-1CL 34.0 kW · DL(N) 34.0 kW · DL(F) 0.0 kW63A 4P BUS · 25 kA63A 4P MCCB 25kAFROM MAIN LT PANELF1 AHU-1F2 LDB-1F3 SPARE

Preview of the AutoCAD DXF drawing (same layout). Red = fire & life-safety (DL(F)) feeders, dashed = spares. Breakers, cables and loads from the voltage-drop schedule; bus kA by panel type (set per panel or link a short-circuit study).

2. Panels

TagPanelKindSectionsBus A / kAIncomer(s)CL kWDL(N) kWDL(F) kWFed from
MLTP-01MAIN LT PANELmain21600A 50kA / 1600A 50kAS1: 1600A 4P ACB 50kA EDO TYPE (TR-1 1000 kVA 11KV/0.433KV) + 1250A 4P ACB 50kA MDO TYPE (DG-1 750 kVA)
S2: 1600A 4P ACB 50kA EDO TYPE (TR-2 1000 kVA 11KV/0.433KV)
319.0319.0105.0source
DB-01SMDB-1db163A 25kAS1: 63A 4P MCCB 25kA (FROM MAIN LT PANEL)34.034.00.0MLTP-01 F1 · 1RX4CX10SQMM. CU AR XLPE CABLE

3. Feeder schedule

PanelSecF-noDescriptionBreakerCableL mDL(N) kWCum VD %F&LS
MLTP-01S1F1SMDB-1 (panel)63A FP MCB 50kA1RX4CX10SQMM. CU AR XLPE CABLE4034.01.81
MLTP-01S1F2LIFT-125A FP MCB 50kA1RX4CX6SQMM. CU FRLS FS CABLE8015.02.66F&LS FS
MLTP-01S1F3CHILLER-1315A 4P MCCB 50kA1RX4CX185SQMM. AL AR XLPE CABLE50180.01.23
MLTP-01S2F5FIRE PUMP PANEL160A 4P MCCB 50kA1RX4CX70SQMM. AL FRLS FS CABLE6090.01.86F&LS FS
MLTP-01+ 2 spare feeder(s) (20 % per section)
DB-01S1F1AHU-140A FP MCB 25kA1RX4CX4SQMM. CU AR XLPE CABLE3522.04.37
DB-01S1F2LDB-125A FP MCB 25kA1RX4CX4SQMM. CU AR XLPE CABLE3012.03.01
DB-01+ 1 spare feeder(s) (20 % per section)

4. Fire & life-safety supply

NBCS 2026 (SP 7:2026) Part D Sec 2 cl. 4.2.1(jj): emergency power for fire pumps, pressurisation and smoke venting, fireman's and all lifts, exit and emergency lighting, fire alarm, PA (voice evacuation), magnetic door hold-open devices and fire-control-room lighting — from the normal and the standby-generator supply with changeover; the generator takes the starting current of all of them; the F&LS panel / DB is in a fire-safe zone and the cables are fire-survival as far as possible. Four-pole incomers / bus with full-size neutral (cl. 8.2.9.1) and four-core cables (cl. 5.3.7.1).

PanelSecF-noF&LS loadBreakerCableDL(F) kWBasisFire-survival cable
MLTP-01S1F2LIFT-125A FP MCB 50kA1RX4CX6SQMM. CU FRLS FS CABLE15.0flagged F&LSYES
MLTP-01S2F5FIRE PUMP PANEL160A 4P MCCB 50kA1RX4CX70SQMM. AL FRLS FS CABLE90.0flagged F&LSYES

5. Panel notes

  1. MLTP-01: DG SET FEEDS ITS BUS SECTION THROUGH THE DG INCOMER (AMF); MAINS AND DG INCOMERS ELECTRICALLY & MECHANICALLY INTERLOCKED.
  2. MLTP-01: HT SUPPLY 11 kV FROM DISCOM (250 MVA FAULT LEVEL ASSUMED), HT METERING; RMU / HT PANEL / TRANSFORMER PROTECTION AS PER CEA REGULATIONS & DISCOM NORMS.

6. Standards and code references

StandardTitleUsed for
IEC 60617 / IS 12032Graphical symbols for diagramsSLD symbols (breakers, CT, PT, relays, transformer, generator)
IEEE C37.2-2008Standard electrical power system device function numbers (ANSI)Relay codes 50, 51, 50N, 51N, 64, 86, 95, 27, 59, 25, 32
IEC 61439-1/2:2020 / IS/IEC 61439Low-voltage switchgear and controlgear assembliesPanel construction (TTA/PTTA), busbar short-time withstand (Icw 1 s), temperature rise, IP rating
IS 8623 (Part 1):1993Low-voltage switchgear and controlgear assembliesPanel construction (superseded in part by IS/IEC 61439)
IEC 61643-11:2011Surge protective devices connected to low-voltage power systemsSPD ratings (Iimp, In, Up)
IEC 62305-1..4:2010 / IS/IEC 62305Protection against lightningSPD type 1/2 selection, risk assessment (future)
IS 3043:2018Code of practice for earthingEarth bus, strip sizing, earthing of panels (future earthing tool)
CPWD General Specifications for Electrical Works (Part I Internal, Part IV Substation)CPWD specificationsVoltage-drop cascade limits, cable/wiring practice, panel and metering requirements
CEA (Measures relating to Safety and Electric Supply) Regulations, 2023Central Electricity Authority safety regulationsStatutory safety requirements for installations
NBCS 2026 (SP 7:2026) Part D Sec 2National Building Construction Standards — Electrical and allied installationsLoad assessment and diversity, circuits, cables (4-core), earthing, lightning protection, standby supply for fire & life-safety loads
NBCS 2026 (SP 7:2026) Part FNational Building Construction Standards — Fire and life safetyMeans of egress (Tables 2–4, cl. 4.4.2), staircase / lobby / lift-well pressurisation (cl. 4.4.2.5, Table 5), emergency lighting (cl. 3.5.6), fire-fighting installations by occupancy (Tables 7A–7J), demand, pumps and duration (Tables 7K / 7M), mains (Table 8), hydrant pressure 3.5–7 bar (cl. 5.1.1 f), sprinklers (cl. 5.1.3), gaseous suppression (cl. 5.1.6 / 5.1.9)
IS 732:2019Code of practice for electrical wiring installationsVoltage-drop limits, cable selection, protection coordination (adopts IEC 60364)
IEC 60364-5-52:2009Low-voltage electrical installations — Selection and erection of wiring systemsCurrent-carrying capacity, derating (temperature, grouping, installation method), voltage drop ≤ 3–5 %
IEC 60364-4-43:2008Protection against overcurrentIb ≤ In ≤ Iz, adiabatic cable withstand I²t ≤ k²S² with k = 143 (Cu XLPE), 115 (Cu PVC), 94 (Al XLPE), 76 (Al PVC)
IS 1554 (Part 1):1988PVC insulated (heavy duty) electric cables up to 1100 VCable ratings, resistance and reactance data
IS 3961 (Part 2):1967 (reaffirmed)Recommended current ratings for cables — PVC insulated and PVC sheathed heavy duty cablesRating factors for ambient / ground temperature, soil thermal resistivity, depth of laying and grouping; installation categories (in air, in ground, in ducts)
IEC 60287-1-1 / 60287-2-1Electric cables — Calculation of the current ratingTemperature correction √((θmax−θamb)/(θmax−θref)) and depth-of-laying correction
IS 7098 (Part 1):1988Cross-linked polyethylene insulated PVC sheathed cables up to 1100 VXLPE cable ratings (90 °C), resistance and reactance data
IS 694:2010PVC insulated cables for working voltages up to 1100 VFRLS wiring conductors
IEC 60947-2:2016 / IS/IEC 60947-2Low-voltage switchgear — Circuit-breakersACB/MCCB ratings Icu, Ics, Icw; release characteristics (L-S-I-G); selectivity definitions
IEC 60898-1:2015 / IS/IEC 60898-1Circuit-breakers for overcurrent protection for household and similar installations (MCB)B/C/D tripping bands (C: 5–10 × In), thermal tripping 1.13/1.45 × In
IS 13703 / IEC 60269-1Low-voltage fusesI2 = 1.6 In for gG fuses in the overload rule
IEEE 141-1993 (Red Book)Recommended practice for electric power distribution for industrial plantsMotor starting voltage dip (≥ 80–85 % at terminals), phase unbalance practice
IEC 60909-0:2016Short-circuit currents in three-phase a.c. systems — Calculation of currentsImpedance method, voltage factor c (1.05 / 1.10 max, 0.95 min), peak factor κ = 1.02 + 0.98·e^(−3R/X), Ik" = c·Un/(√3·Zk)
Prepared by
Checked by
Approved by

Results are design aids computed by designlink calc (calc.designlink.in). Verify against the approved drawings, the panel manufacturer's data and the Authority's requirements before issue.