SAMPLE Transformer, DG & UPS sizing — this is what your report looks like, generated from demo inputs. Generate yours → 2 free designs every day for every signed-in account · 1 design free on sign-in · ₹99 + GST per design (report + Excel + DXF) · free for DesignLink companies
Report ready — use Print → Save as PDF (A4 landscape).
Design Linkcalc.designlink.in

Source sizing — transformers, DG, UPS

Sample project — Tower A · Indian regime · NBCS 2026 · growth 20 %
Generated 28 Nov 2026 16:09
From the classified load list
Project code SAMPLE
Transformers
3 × 400 kVA
DG sets
1 × 400 kVA
UPS
2 × 100 kVA
Utility demand
514.5 kVA
DG demand
265.1 kVA
Checks
all pass

1. Load classification

LoadPanelKindClassF&LSConnected kWDemand kWStartingStarting kVANote
LDB-GFdbEssential (DG-backed)25.025.0no motor / static
PDB-GFdbNon-essential (utility only)40.040.0no motor / static
HVAC PANELhvacNon-essential (utility only)180.0180.0VFD (1.2 ×)282.4
LIFT-1liftEssential (DG-backed)●15.015.0VFD (1.2 ×)23.5
FIRE PUMPpumpFire-fighting (DG / dedicated)●75.075.0star-delta (2.5 ×)245.1
SERVER ROOMupsCritical (UPS)60.060.0no motor / static
WATER PUMPSpumpEssential (DG-backed)22.022.0DOL (6 × FLC)172.5

F&LS = fire and life-safety load per NBCS 2026 Part D Sec 2 cl. 4.2.1(jj) / Part F 3.5.5.2: fire pumps, pressurisation and smoke venting, fireman's lifts including all lifts, exit and emergency lighting, fire alarm, PA, door hold-open devices, fire-control-room lighting — normal + standby generator with changeover.

ClassDemand kWDiversityDiversified kW
Essential (DG-backed)62.00.955.8
Non-essential (utility only)220.00.85187.0
Critical (UPS)60.01.060.0
Fire-fighting (DG / dedicated)75.01.075.0

2. Transformers

ItemValue
Utility demand (all classes, UPS as input kVA, +growth)514.5 kVA
Units in service / installed2 / 3 (N+1)
Required per unit at ≤ loading321.6 kVA
Selected3 × 400 kVA
Loading with all units64.3 %
Loading with one unit out64.3 %
LV full-load current per unit556 A
Prospective LV fault (Z 5.0 %)11.1 kA per unit

3. DG sets

ItemValue
DG demand (essential + fire + UPS input, +growth)265.1 kVA
Site derating× 0.991 (altitude 300 m → −0.0 %, ambient 45 °C → −0.9 %)
Largest single step245.1 kVA → rating ≥ 176.5 kVA for the 20 % dip, ≥ 350.1 kVA for the 70 % step
Governed byF&LS simultaneous start (step)
All F&LS starting together (NBCS 4.2.1 jj)268.6 kVA in one step → rating ≥ 193.4 kVA (dip), ≥ 383.7 kVA (step); dip at the selected set 10.9 %
Selected1 × 400 kVA (396.4 kVA each at site)
Loading66.9 %
Fuel at 75 % load (approx.)63.0 L/h

Loading sequence

StepLoadKindStep kVARunning kVABefore kVATransient dip %Result
1FIRE PUMPFire-fighting · star-delta (2.5 ×)245.183.30.010.0PASS
2WATER PUMPSEssential · DOL (6 × FLC)172.524.483.37.3PASS
3LIFT-1Essential · VFD (1.2 ×)23.516.7107.81.1PASS
4LDB-GFblock load (static)25.025.0124.41.1PASS
5UPS input (rectifier walk-in)UPS90.890.8149.44.0PASS

Transient dip per step ΔV ≈ X''d·S / (G + X''d·S) with X''d = 18 % — confirm with the alternator's transient curve; fire pump starts first on an unloaded set.

DG loading steps — 1 × 400 kVA (396.4 kVA at site in service)0100200300400500step (see the table above)kVA0510152025dip %1 · load before the step kVA: 02 · load before the step kVA: 83.33 · load before the step kVA: 1084 · load before the step kVA: 1245 · load before the step kVA: 1491 · step kVA: 2452 · step kVA: 1723 · step kVA: 23.54 · step kVA: 255 · step kVA: 90.8123451: 1010102: 7.37.37.33: 1.11.11.14: 1.11.11.15: 444dip limit 20 %load before the step kVAstep kVAtransient dip %
Source loading against the limits (black tick = limit)020406080100120% of ratingTransformers, 2 in serviceTransformers, 2 in service: 64.3 % (limit 80 %)64.3 %Transformers, one unit out (N+1)Transformers, one unit out (N+1): 64.3 % (limit 100 %)64.3 %DG, 1 set(s) in serviceDG, 1 set(s) in service: 66.9 % (limit 80 %)66.9 %Largest DG step (FIRE PUMP)Largest DG step (FIRE PUMP): 61.8 % (limit 70 %)61.8 %All F&LS starting togetherAll F&LS starting together: 67.8 % (limit 70 %)67.8 %

4. UPS

ItemValue
UPS2 × 100 kVA
Design load72.0 kW
Battery4 × 32 × 75 Ah blocks
Bank capacity300 Ah C10
Input current126.3 A
Heat to room2.437 TR

UPS rating

ItemValueNote
Load with growth72.0 kW
Load kVA at pf 0.9080.0 kVA
Required rating (kW / UPS pf, ÷ max loading)100.0 kVA
Per module100.0 kVA
Selected module100 kVA
ConfigurationN+1 — 2 modules
Installed capacity200 kVA

Battery bank (per UPS system)

ItemValueNote
DC bus / cells / blocks384 V · 192 cells · 32 × 12 V blocks
End voltage of bank336.0 V
Battery power (kW ÷ inverter η)75.79 kW
Average discharge current210.53 A
C10 capacity for 30 min (Peukert k = 1.30)210.14 Ah
Design capacity × ageing × temperature × margin288.95 Ah
Block / strings75 Ah × 4 string(s)
Blocks total128 nos
Approx. weight2880.0 kg
Recharge current (0.1 C)30.0 A

Input & room

ItemValueNote
Input power (load ÷ η + charger)89.84 kW
Input kVA90.75 kVA
Input current per system126.25 A
Heat rejected8.57 kW≈ 2.44 TR
Battery room ventilation (hydrogen) — VRLA20,736 m³/h IEC 62485 basis: Q = 0.05 · n · I_gas · 5 (approx.)

Protection and NBCS 2026 D2 cl. 10.3.2 / 10.3.4

ItemValueNote
UPS output (N capacity, one system)100 kVA
Output current139.12 A415 V three-phase
Input circuit breaker160 A 4P ≥ 1.25 × 126 A input current
Output circuit breaker200 A 4P 10.3.2 (e): 4-pole for 3-phase UPS, double-pole for single-phase
Isolation transformer (10.3.2 a)not provided (optional)
Runtime at 100 % design load — new / end of life48 / 36 minrequired 30 min
Output protection (10.3.4 c)shut-down on overload / short circuit; warning label where auto-restoration is enabled

5. Checks

CheckResult
Transformer loading ≤ 80 % with 2 unit(s) in servicePASS
N+1: full load carried with one transformer out (≤ 100 %)PASS
DG loading ≤ 80 % of site ratingPASS
DG loading ≥ 30 % (no wet stacking)PASS
Every loading step: transient dip ≤ 20 % and step ≤ 70 % of site ratingPASS
Fire pumps on the DG (NBCS 4.2.1 jj: normal + standby generator with changeover)PASS
Generator takes the starting current of all F&LS loads together (NBCS 4.2.1 jj / Part F 3.5.5.2): 268.6 kVA in one step → dip 10.9 % ≤ 20 %, step ≤ 70 % of ratingPASS
All lifts on the standby (DG) supply — fireman's lifts including all lifts are F&LS loads (NBCS 4.2.1 jj 3)PASS
UPS 2 × 100 kVA for 80.0 kVA / 72.0 kW at ≤ 80 % loadingPASS
Battery 4 string(s) × 32 blocks × 75 Ah → 300 Ah ≥ 289 AhPASS
Dedicated UPS neutral earth pits (IT), interconnected below soil with the other earth pitsPASS
UPS room ventilated / air-conditioned against thermal runawayPASS
Battery space well ventilated (H₂ / O₂ evolution)PASS
Acid-resistant tiles / coating on the battery-room floorPASS
UPS-fed circuits marked so that mains isolation is not taken as deadPASS
Circuit breakers: input 4P 160 A ≥ 1.25 × 126 A, output 4P 200 A ≥ 1.25 × 139 APASS

6. Room areas — NBCS 2026 Part D Sec 2 Annex C / D (guidance)

SpaceAreaBasis
Transformer room, min (Annex C)49.5 m²row 3 × 400 kVA
Substation incl. HV / MV panels, without generators (Annex C)167 m²suggested face width 18 m; clear height = equipment + 1 200 mm below the beam soffit (Note 2 / 4.2.1 ff)
Generator room, each set (Annex D) × 1100 m² each → 100 m²row 480 kVA; clear height 4.2 m below the beam soffit; covers the day tank, not bulk fuel (Note 3)

7. Worked examples — from this project

Worked from this project’s own inputs and results — each value can be traced to the schedules above.

Transformer — 3 × 400 kVA
utility source for every load class
1. Diversified — Essential: P = Σ Pd × DF = 62 × 0.9 = 55.8 kW
2. Diversified — Non-essential: P = Σ Pd × DF = 220 × 0.85 = 187 kW
3. Diversified — Critical: P = Σ Pd × DF = 60 × 1.0 = 60 kW
4. Diversified — Fire-fighting: P = Σ Pd × DF = 75 × 1.0 = 75 kW
5. Utility demand: S = (Pess + Pnon + Pfire) / cosφ × (1 + g) + SUPS,in = (55.8 + 187 + 75) / 0.9 × 1.2 + 90.8 = 514.5 kVA
6. Per unit: Sunit = S / loading / n = 514.5 / 0.8 / 2 = 321.6 kVA (next standard size ≥ this from 250, 315, 400, 500, 630, 800, 1000, 1250 … kVA)
7. Selected: 2 in service + 1 standby (N+1) = 3 × 400 kVA
8. Loading: S / (n · Sr) ≤ 80 % → 514.5 / (2 × 400) = 64.3 % PASS
9. One unit out: S / ((N+1−1) · Sr) ≤ 100 % → 64.3 % PASS
10. LV full-load current: I = Sr / (√3 · U) = 400,000 / (1.732 · 415) = 556 A
11. Prospective LV fault: Ik = I / z = 556 / 0.05 = 11.1 kA (infinite source, per unit)
DG — 1 × 400 kVA
governed by F&LS simultaneous start (step)
1. DG demand: S = (Pess + Pfire) / cosφ × (1 + g) + SUPS,in = (55.8 + 75) / 0.9 × 1.2 + 90.8 = 265.1 kVA
2. Site derating: f = 1 − 3.5 %/300 m above 1000 m − 1 %/5.5 °C above 40 °C = altitude 300 m → −0.0 %, ambient 45 °C → −0.9 % = 0.991 (ISO 3046 / ISO 8528 practice)
3. Running requirement per set: S / loading / n / f = 265.1 / 0.8 / 1 / 0.991 = 334.4 kVA
4. Largest start — FIRE PUMP: Sst = Pm / η / cosφ × kstart = 75 / 0.9 / 0.85 × 2.5 = 245.1 kVA (star-delta (2.5 ×))
5. Rating for the voltage dip: G ≥ X″d · Sst · (1 − d) / d = 0.18 · 245.1 · 0.8 / 0.2 = 176.5 kVA
6. Rating for the step capability: G ≥ Sst / step = 245.1 / 0.7 = 350.1 kVA
7. Required per set: max(running, dip, step) / n / f = max(334.4, 178.1, 353.4) = 387.2 kVA (next standard size from 200, 250, 320, 380, 400, 500, 600, 625 … kVA)
8. Dip at step 1: ΔV = X″d · S / (Gsite + X″d · S) ≤ 20 % → 0.18 · 245.1 / (396.4 + 0.18 · 245.1) = 10.0 % PASS
9. All F&LS loads starting together: SF&LS = Σ Sst (motors) + Σ S (static F&LS) = 23.5 + 245.1 = 268.6 kVA (NBCS 4.2.1(jj) / Part F 3.5.5.2: LIFT-1, FIRE PUMP)
10. Rating for that one step: G ≥ max(X″d · S · (1 − d) / d, S / step) = max(0.18 · 268.6 · 0.8 / 0.2, 268.6 / 0.7) = 383.7 kVA (added to the max() above)
11. F&LS simultaneous start: ΔV ≤ 20 % and S ≤ 70 % of Gsite → 10.9 %, 268.6 / 396.4 kVA PASS
12. Selected: 1 in service = 1 × 400 kVA (396.4 kVA each at site)
13. Loading: S / Gsite ≤ 80 % → 265.1 / 396.4 = 66.9 % PASS
UPS — 2 × 100 kVA, battery 4 × 32 × 75 Ah
critical (UPS) loads of this project
Given: Critical load 60 kW (UPS class × 1.0) · Backup 30 min, VRLA, 384 V DC
1. Load with growth: P = Pc × (1 + g) = 60 × 1.2 = 72 kW
2. Required rating: S = max(P / cosφ, P / pfUPS) / loading = max(72.0 / 0.9, 72.0 / 0.9) / 0.8 = 100 kVA (module 100 kVA, N+1 — 2 modules)
3. Battery power: Pdc = P / ηinv = 72.0 / 0.95 = 75.79 kW
4. Average current: I = Pdc / ((Udc + Uend) / 2) = 75,790 / ((384 + 336.0) / 2) = 210.53 A
5. Capacity (Peukert): C10 = I · 10 · (t / 10)1/k = 210.53 · 10 · (0.500 / 10)1/1.3 = 210.14 Ah
6. Design capacity: C = C10 × ageing 1.25 × temperature 1.0 × margin 1.1 = 210.14 × 1.375 = 288.95 Ah (IEEE 485 ageing factor)
7. Bank: strings × block Ah ≥ C → 75 Ah × 4 string(s) = 300 Ah PASS
8. UPS input to the DG / transformer: Sin = (P / η + Pcharger) / pfin = 89.84 / 0.99 = 90.75 kVA (used above as SUPS,in = 90.8 kVA)

8. Standards applied

StandardUsed for
IS 10002 / ISO 8528Diesel generating sets — rating, derating, transient classes
IS 1180 / IEC 60076Distribution transformers
CPWD General Specifications for Electrical Works Part VII (DG sets)DG selection, installation
NBCS 2026 (SP 7:2026) Part D Sec 24.2.1(jj) F&LS supply — generator takes the starting current of all F&LS loads; 4.3 DG location, room, day tank; 5.2.5 / 10.7.3 EV not on DG; Annex C / D room areas
NBCS 2026 Part F3.5.5.2 emergency power for F&LS (all lifts), 3.5.5.4 standby supply
IEEE 485 / IS 16242Battery sizing / UPS
CEA (Technical Standards for Connectivity)Standby generation
Prepared by
Checked by
Approved by

Results are design aids computed by designlink calc (calc.designlink.in) and must be reviewed by a qualified engineer before issue. Ground levels marked "assumed" have no survey level within reach — verify.