SAMPLEMEP supports — tray / duct / pipe spans, members, anchors — this is what your report looks like, generated from demo inputs.Generate yours →2 free designs every day for every signed-in account · 1 design free on sign-in · ₹99 + GST per design (report + Excel + DXF) · free for DesignLink companies
Report ready — use Print → Save as PDF (A4 landscape).
Steel: IS 800:2007 limit state method is the default (NBCS 2026 Part C Sec 6A); the 0.66 fy allowable-stress option reproduces the withdrawn IS 800:1984 / AISC ASD check for comparison. Lateral-torsional buckling (cl. 8.2.2) is not checked — short members restrained by the services assumed.
Anchor capacities are indicative recommended loads (cracked concrete); take the final values from the anchor manufacturer's ETA / ICC report and check edge distance and spacing.
Trays: IEC 61537 / SMACNA practice — supports at 1.5 m (ladder up to 2.0 m), a 90 kg point load for maintenance; seismic bracing per the seismic calculator. Outdoor / rooftop racks: add wind per NBCS Part C Sec 1 cl. 4.
6. Standards and references
ASHRAE Handbook — HVAC Applications ch. 51 — Service water heating: Hot-water demand, storage and recovery
IS 800:2007 / IS 800:1984 — General construction in steel — code of practice: Allowable bending stress 0.66 fy, deflection limits for MEP support members
IS 1367 / IS 1363 — Threaded fasteners — technical supply conditions; hexagon bolts: Hanger rods and anchor bolts (property class 4.6 / 8.8)
ETAG 001 / EAD 330232 (EN 1992-4) — Metal anchors for use in concrete: Anchor tension / shear capacities, cracked concrete, seismic categories
SMACNA HVAC Duct Construction Standards — Duct construction, hangers and supports, seismic restraint: Duct hanger spacing and sizes; seismic bracing spacing
NBCS 2026 (SP 7:2026) Part C Sec 1 — National Building Construction Standards — Loads and load effects: Imposed loads, impact allowance (cl. 3.6), wind, seismic by IS 1893 (Part 1)
IEC 61537:2006 / IS 17237 — Cable management — cable tray and cable ladder systems: Safe working load, support spacing and deflection of trays and ladders
Prepared by
Checked by
Approved by
Results are design aids computed by designlink calc (calc.designlink.in) and must be reviewed by a qualified engineer before issue. Ground levels marked "assumed" have no survey level within reach — verify.