calc.designlink.inTransformer losses, regulation & payback
Sample project — Tower A · Electrical
Generated 28 Nov 2026 17:16
Losses and efficiency at any load from the no-load and load losses, the load of maximum ef…
Project code SAMPLE
Max efficiency at
40.2 % load
Energy loss
34384.6 kWh/yr
1. Inputs
| Group | Input | Value | Unit |
|---|
| Transformer (option A) | Rating | 1000 | kVA |
| Transformer (option A) | No-load loss | 1700 | W |
| Transformer (option A) | Load loss at rated current (75 °C) | 10500 | W |
| Transformer (option A) | Impedance | 5.0 | % |
| Transformer (option A) | Price | 1500000 | ₹ |
| Option B (more efficient) — 0 to skip | No-load loss | 1300 | W |
| Option B (more efficient) — 0 to skip | Load loss | 8500 | W |
| Option B (more efficient) — 0 to skip | Price | 1750000 | ₹ |
| Load and energy | Load (for efficiency and regulation) | 60 | % of rating |
| Load and energy | Load power factor | 0.9 | |
| Load and energy | Peak load | 75 | % of rating |
| Load and energy | Annual load factor | 0.55 | |
| Load and energy | Energy cost | 8.0 | ₹/kWh |
| Load and energy | Evaluation period | 20 | years |
| Load and energy | Discount rate | 8 | % |
2. Results
At the given load
| Item | Value | Unit | Note / basis |
|---|
| Load | 60.0 | % | |
| Output | 540.0 | kW | |
| Losses P0 + β²·Pk | 5.48 | kW | |
| Efficiency | 99.0 | % | |
| Load of maximum efficiency √(P0/Pk) | 40.24 | % | |
| Maximum efficiency | 99.07 | % | |
Regulation
| Item | Value | Unit | Note / basis |
|---|
| Resistance εr = Pk / S | 1.05 | % | |
| Reactance εx = √(Z² − εr²) | 4.89 | % | |
| Regulation | 1.87 | % | β(εr cosφ + εx sinφ) + [β(εx cosφ − εr sinφ)]² / 200 |
Energy and owning cost
| Item | Value | Unit | Note / basis |
|---|
| Loss load factor 0.3·LF + 0.7·LF² | 0.3768 | | typical |
| Annual energy loss | 34384.57 | kWh | |
| Annual loss cost | 275076.59 | ₹ | |
| A factor (₹ per kW no-load loss) | 688055.77 | ₹/kW | |
| B factor (₹ per kW load loss) | 145814.07 | ₹/kW | |
| Total owning cost (A) | 4200742.53 | ₹ | |
Options
| P0 W | Pk W | Loss kWh/yr | Price ₹ | TOC ₹ |
|---|
| Option A | 1700 | 10500 | 34,385 | 1,500,000 | 4,200,743 |
| Option B | 1300 | 8500 | 27,168 | 1,750,000 | 3,883,892 |
3. Checks
| Check | Result | Note |
|---|
| Regulation 1.87 % at 60 % load, pf 0.9 | PASS | ≤ 5 % (typical design target) |
| Option B has the lower total owning cost | PASS | TOC A ₹ 4,200,743 vs B ₹ 3,883,892 |
4. Worked example
η = 540.0 / (540.0 + 1.7 + 0.60² × 10.5) = 99.00 %
εr = 10500 / (1000 × 1000) × 100 = 1.05 %; εx = √(5² − 1.05²) = 4.89 %; regulation = 1.87 %
A = 8 × 8760 × PVF 9.82 = ₹ 688,056/kW; B = A × LLF 0.377 × 0.75² = ₹ 145,814/kW
Payback = Δprice / Δloss cost = 250,000 / 57,735 = 4.3 years
5. Notes
- IS 1180 sets maximum total losses at 50 % and 100 % load by energy-efficiency level for distribution transformers; compare the certificate values with the level asked for in the specification.
- Loss load factor 0.3·LF + 0.7·LF² is the usual distribution-practice approximation.
6. Standards and references
- IS 1180 (Part 1):2014 — Outdoor type oil-immersed distribution transformers up to 2500 kVA, 33 kV: Typical impedance (%Z) by rating
- IS 2026 (Part 1):2011 / IEC 60076-1 — Power transformers: Impedance voltage, ratings, Dyn11 vector group
- IEC 60076 (series) — Power transformers: Impedance, ratings and losses used for the fault study source model
Prepared by
Checked by
Approved by
Results are design aids computed by designlink calc (calc.designlink.in) and must be reviewed by a qualified engineer before issue. Ground levels marked "assumed" have no survey level within reach — verify.