Design regime: Indian — code edition NBCS 2026 (SP 7:2026) Part D Sec 2 (replaces NBC 2016 Part 8 Sec 2): VD basis — Split — ≤ 6 % transformer → final DB plus ≤ 3 % final DB → last point (9 % at the last point) (NBCS 2026 (SP 7:2026) Part D Sec 2 cl. 6.2 / 5.6 Note a): voltage drop ≤ 6 % transformer → final DB and ≤ 3 % DB → last point (cl. 6.2, 5.6 Note a), four-core cables only and Cu up to 25 sq mm (cl. 5.3.7.1), full-size neutral (cl. 8.2.9.1), F&LS supplies (cl. 4.2.1 jj); IS 732:2019 (harmonised with IEC 60364), IS 1554 / IS 7098 cables, CPWD General Specifications cascade limits (stricter than NBCS), with the IEC standards they adopt.
| Panel | Connected kW | DF | Demand kW | Ib A | Incomer breaker | Incoming cable |
|---|---|---|---|---|---|---|
| MLP | 159.0 | 1.00 | 159.0 | 250.4 | 315A MCCB | 4C X 185 Sq.mm, AL × 1 |
| LP-1 | 39.0 | 1.00 | 39.0 | 74.7 | 100A MCCB | 4C X 35 Sq.mm, Cu × 1 |
| # | From | To | Ph | Load kW | L m | Laying | Cable / bus duct | Runs | Ib A | Breaker | k (derating) | Iz2 A | VD % | Cum. % | Limit % | Status |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | TR-1 (1000 kVA) | MLP (panel) | 3φ | 159.0 Σ159.0×1.00 | 40 | In air – perforated tray / ladder / clipped direct | 4C X 185 Sq.mm, AL | 1 | 250.4 | 315A MCCB 4P | 1.00 θ 1.00 · ρ 1.00 · d 1.00 · grp 1.00 (1) · lay 1.00 | 329 | 1.14 | 1.14 | 4.0 | PASS |
| 2 | MLP | LP-1 (panel) | 3φ | 39.0 Σ39.0×1.00 | 60 | In air – perforated tray / ladder / clipped direct | 4C X 35 Sq.mm, Cu | 1 | 74.7 | 100A MCCB 4P | 1.00 θ 1.00 · ρ 1.00 · d 1.00 · grp 1.00 (1) · lay 1.00 | 146 | 2.05 | 3.19 | 5.0 | PASS |
| 3 | MLP | PP-1 (Pumps) | 3φ | 75.0 | 80 | In air – perforated tray / ladder / clipped direct | 4C X 50 Sq.mm, AL | 1 | 109.8 | 125A MCCB 4P | 1.00 θ 1.00 · ρ 1.00 · d 1.00 · grp 1.00 (1) · lay 1.00 | 138 | 2.96 | 4.09 | 5.0 | PASS |
| 4 | MLP | AHU-1 | 3φ | 45.0 | 55 | In air – perforated tray / ladder / clipped direct | 4C X 25 Sq.mm, Cu | 1 | 65.9 | 100A MCCB 4P | 1.00 θ 1.00 · ρ 1.00 · d 1.00 · grp 1.00 (1) · lay 1.00 | 122 | 1.34 | 2.47 | 5.0 | PASS |
| 5 | LP-1 | Lighting — floor 1 | 1φ | 12.0 | 35 | In air – perforated tray / ladder / clipped direct | 3C X 25 Sq.mm, Cu | 1 | 52.7 | 63A MCB DP | 1.00 θ 1.00 · ρ 1.00 · d 1.00 · grp 1.00 (1) · lay 1.00 | 122 | 1.36 | 4.55 | 5.0 | PASS |
| 6 | LP-1 | Lighting — floor 2 | 1φ | 12.0 | 42 | In air – perforated tray / ladder / clipped direct | 3C X 25 Sq.mm, Cu | 1 | 52.7 | 63A MCB DP | 1.00 θ 1.00 · ρ 1.00 · d 1.00 · grp 1.00 (1) · lay 1.00 | 122 | 1.63 | 4.82 | 5.0 | PASS |
| 7 | LP-1 | Lift-1 | 3φ | 15.0 | 70 | In air – perforated tray / ladder / clipped direct | 4C X 10 Sq.mm, Cu | 1 | 22.0 | 25A MCB FP | 1.00 θ 1.00 · ρ 1.00 · d 1.00 · grp 1.00 (1) · lay 1.00 | 74 | 1.40 | 4.59 | 5.0 | PASS |
| Node | Fed from | Cable × runs | L m | Segment VD % | Cumulative VD % | Limit % | Check |
|---|---|---|---|---|---|---|---|
| TR-1 (1000 KVA) source · connected 159.0 kW · demand 159.0 kW (DF 1.00) | 0.00 | 4.0 | |||||
| └ MLP (panel) | TR-1 (1000 kVA) | 4C X 185 Sq.mm, AL × 1 | 40 | 1.14 | 1.14 | 4.0 | PASS |
| └ LP-1 (panel) | MLP | 4C X 35 Sq.mm, Cu × 1 | 60 | 2.05 | 3.19 | 5.0 | PASS |
| └ Lighting — floor 1 | LP-1 | 3C X 25 Sq.mm, Cu × 1 | 35 | 1.36 | 4.55 | 5.0 | PASS |
| └ Lighting — floor 2 | LP-1 | 3C X 25 Sq.mm, Cu × 1 | 42 | 1.63 | 4.82 | 5.0 | PASS |
| └ Lift-1 | LP-1 | 4C X 10 Sq.mm, Cu × 1 | 70 | 1.40 | 4.59 | 5.0 | PASS |
| └ PP-1 (Pumps) | MLP | 4C X 50 Sq.mm, AL × 1 | 80 | 2.96 | 4.09 | 5.0 | PASS |
| └ AHU-1 | MLP | 4C X 25 Sq.mm, Cu × 1 | 55 | 1.34 | 2.47 | 5.0 | PASS |
Single-phase loads are placed on their tagged phase or on the least-loaded phase of their panel; three-phase loads are split equally unless a split is entered. Design current Ib = worst-phase current (IEC 60364-5-52 cl. 523.6.3); neutral current IN = |IR + a·IY + a²·IB| adds to the worst-phase voltage drop. Unbalance = (Imax − Iavg)/Iavg; limit 10 % (design practice / IEEE 141 / CEA).
| Panel | kW R | kW Y | kW B | I R A | I Y A | I B A | I N A | Unbalance % | Limit % | Check |
|---|---|---|---|---|---|---|---|---|---|---|
| TR-1 (1000 KVA) (source) | 57.0 | 57.0 | 45.0 | 250.4 | 250.4 | 197.7 | 52.7 | 8 | 10 | PASS |
| MLP | 57.0 | 57.0 | 45.0 | 250.4 | 250.4 | 197.7 | 52.7 | 8 | 10 | PASS |
| LP-1 | 17.0 | 17.0 | 5.0 | 74.7 | 74.7 | 22.0 | 52.7 | 31 | 10 | FAIL |
Single-phase loads and their phases:
| From | To (1φ load) | Phase | kW | Ib A |
|---|---|---|---|---|
| LP-1 | Lighting — floor 1 | R | 12.00 | 52.7 |
| LP-1 | Lighting — floor 2 | Y | 12.00 | 52.7 |
3rd-harmonic content of the line current ≤ 15 %: no reduction; 15–33 %: factor 0.86 on the line current; 33–45 %: factor 0.86 applied to the neutral current IN = 3·h3·IL; > 45 %: cable sized for the neutral current. Project default h3 = 0 %.
No feeder with 3rd-harmonic content above 0 % — no harmonic derating applied.
Istart = m · Ib (DOL 6 ×, star-delta 2.5 ×, soft starter 3 ×, VFD 1.5 ×) at pf 0.3; dip at the motor terminals = upstream running VD + starting VD of the motor feeder ≤ 15 % (IEEE 141 / IS 732 guidance; upstream feeders assumed at running load).
No feeder is marked as a motor (Load details ▸ Load type).
Ib ≤ In ≤ Iz and I2 ≤ 1.45·Iz, where I2 = 1.45·In for MCB (IS/IEC 60898-1), 1.30·In for MCCB / ACB (IEC 60947-2) and 1.60·In for gG fuses (IS 13703 / IEC 60269). With the rule on, the cable is sized so that Iz2 ≥ In (the second condition is then automatically satisfied for breakers).
| From | To | Ib A | In A · type | Iz2 A | I2 A | 1.45·Iz A | Ib ≤ In ≤ Iz | I2 ≤ 1.45 Iz |
|---|---|---|---|---|---|---|---|---|
| TR-1 (1000 kVA) | MLP | 250.4 | 315 MCCB | 329.0 | 1.30 × In = 409.5 | 477.1 | PASS | PASS |
| MLP | LP-1 | 74.7 | 100 MCCB | 146.0 | 1.30 × In = 130.0 | 211.7 | PASS | PASS |
| MLP | PP-1 (Pumps) | 109.8 | 125 MCCB | 138.0 | 1.30 × In = 162.5 | 200.1 | PASS | PASS |
| MLP | AHU-1 | 65.9 | 100 MCCB | 122.0 | 1.30 × In = 130.0 | 176.9 | PASS | PASS |
| LP-1 | Lighting — floor 1 | 52.7 | 63 MCB | 122.0 | 1.45 × In = 91.3 | 176.9 | PASS | PASS |
| LP-1 | Lighting — floor 2 | 52.7 | 63 MCB | 122.0 | 1.45 × In = 91.3 | 176.9 | PASS | PASS |
| LP-1 | Lift-1 | 22.0 | 25 MCB | 74.0 | 1.45 × In = 36.2 | 107.3 | PASS | PASS |
S ≥ Ik·√t / k with k = 143 (Cu XLPE), 115 (Cu PVC), 94 (Al XLPE), 76 (Al PVC) — Table 43A; Ik = three-phase fault level at the upstream bus, cascaded from the source (36 kA at each source panel unless set per panel) through cable impedances Ik = Uph/|Z| (screening, c = 1; see the Short-circuit tool for the IEC 60909 study); t = clearing time of the feeder's own breaker (MCB 0.01 s, MCCB 0.03 s, ACB 0.4 s). Parallel runs share the fault current (S = size × runs).
| From (bus) | To | Ik at bus kA | Ik at To kA | Breaker | t s / let-through I²t | k | S min sqmm | Cable × runs | S sqmm | Check | Ik source |
|---|---|---|---|---|---|---|---|---|---|---|---|
| TR-1 (1000 kVA) | MLP | 36.00 | 18.64 | 315 MCCB | 0.030 s | 94 | 66.3 | 4C X 185 Sq.mm, AL × 1 | 185 | PASS | default |
| MLP | LP-1 | 18.64 | 4.82 | 100 MCCB | 0.030 s | 143 | 22.6 | 4C X 35 Sq.mm, Cu × 1 | 35 | PASS | cascaded |
| MLP | PP-1 (Pumps) | 18.64 | 3.15 | 125 MCCB | 0.030 s | 94 | 34.3 | 4C X 50 Sq.mm, AL × 1 | 50 | PASS | cascaded |
| MLP | AHU-1 | 18.64 | 4.01 | 100 MCCB | 0.030 s | 143 | 22.6 | 4C X 25 Sq.mm, Cu × 1 | 25 | PASS | cascaded |
| LP-1 | Lighting — floor 1 | 4.82 | 2.96 | 63 MCB | I²t 51,570 A²s | 143 | 1.6 | 3C X 25 Sq.mm, Cu × 1 | 25 | PASS | cascaded |
| LP-1 | Lighting — floor 2 | 4.82 | 2.75 | 63 MCB | I²t 51,570 A²s | 143 | 1.6 | 3C X 25 Sq.mm, Cu × 1 | 25 | PASS | cascaded |
| LP-1 | Lift-1 | 4.82 | 1.16 | 25 MCB | I²t 35,197 A²s | 143 | 1.3 | 4C X 10 Sq.mm, Cu × 1 | 10 | PASS | cascaded |
MCB-protected feeders (In ≤ 63 A): k²S² ≥ let-through I²t of an energy-limiting class 3 MCB at the prospective current (IEC 60898-1 Annex ZC, type C values; IEC 60364-4-43 cl. 434.5.2). Other feeders: adiabatic S ≥ Ik·√t / k with the device clearing time.
Four-core cables (cl. 5.3.7.1): only four-core cables are used for internal installations (four-core in place of 3½-core below 50 sq mm) and all sizes up to 25 sq mm are copper — auto-sizing picks 4C Cu up to 35 sq mm, then 4C Al. No 3½-core cable in this schedule.
Neutral (cl. 8.2.9.1 Note): neutral of the same size as the phase conductor (half-size neutral no longer acceptable with non-linear loads); the neutral-current term in the voltage drop uses zN = z for 4C cables.
Voltage drop (cl. 6.2, 5.6 Note a): ≤ 6 % from the transformer to the final distribution board and ≤ 3 % from the distribution board to the last point — read either as split (6 % + 3 %) or as total (6 % to the last point incl. ≤ 3 % final circuit); the project chooses (Settings ▸ VD basis).
Voltage-drop basis: Split — ≤ 6 % transformer → final DB plus ≤ 3 % final DB → last point (9 % at the last point) — NBCS 2026 (SP 7:2026) Part D Sec 2 cl. 6.2 / 5.6 Note a. This project: first hop ≤ 4.0 %, total ≤ 5.0 %, final circuits ≤ 3.0 % on the segment; final-circuit rows add their segment limit on top of the DB's own cumulative drop. (stricter than NBCS — CPWD practice)
No row is marked as a final circuit (Load details ▸ Final circuit) — the 3 % DB → last-point check applies to final-circuit rows.
Fire & life-safety supplies (cl. 4.2.1 jj): fire pumps, pressurisation / smoke venting, fireman's and all lifts, exit and emergency lighting, fire alarm, PA, door hold-open devices and fire-control-room lighting are fed from the normal and the standby-generator supply with changeover; the generator takes the starting current of all F&LS loads; the F&LS panel / DB is in a fire-safe zone; cables are fire-survival (circuit integrity) as far as possible. F&LS rows are auto-sized in the fire-survival (FS) cable family.
No feeder is marked F&LS (Load details ▸ F&LS feeder).
Worked from this schedule’s own inputs and results — the values can be traced to the cable schedule (section 3) and the cascade (section 4).
| Cable | Feeders | Runs | Length (m) | Terminations |
|---|---|---|---|---|
| 4C X 50 Sq.mm, AL | 1 | 1 | 80 | 2 |
| 3C X 25 Sq.mm, Cu | 2 | 2 | 77 | 4 |
| 4C X 10 Sq.mm, Cu | 1 | 1 | 70 | 2 |
| 4C X 35 Sq.mm, Cu | 1 | 1 | 60 | 2 |
| 4C X 25 Sq.mm, Cu | 1 | 1 | 55 | 2 |
| 4C X 185 Sq.mm, AL | 1 | 1 | 40 | 2 |
MLP → LP-1: Phase unbalance 31 % > 10 %
| Setting | Value |
|---|---|
| voltage | 415 |
| pf | 0.95 |
| k1_temp | 0.95 |
| k2_group | 0.86 |
| k3_tray | 0.92 |
| max_size | 300 |
| max_runs | 8 |
| cu_upto_size | 35 |
| default_cores_small | 4 |
| default_cores_large | 4 |
| limit_first_hop | 4.0 |
| limit_total | 5.0 |
| bbt_vd | 2.0 |
| seg_limit_align | True |
| min_breaker | 25 |
| termination_per_run | 2 |
| size_for_breaker | False |
| parent_share | 0.6 |
| default_material | auto |
| default_df | 1.0 |
| mcb_max | 63 |
| mccb_max | 630 |
| derating_mode | tables |
| overload_rule | True |
| unbalance_limit | 10 |
| thd3 | 0 |
| motor_start_pf | 0.3 |
| motor_start_limit | 15 |
| sc_check | True |
| sc_source_ka | 36 |
| regime | indian |
| limit_final | 3.0 |
| code_edition | nbcs2026 |
| vd_basis | split |
| derating.insulation | XLPE |
| derating.air_temp | 40 |
| derating.ground_temp | 30 |
| derating.soil_rho | 1.5 |
| derating.depth | 0.9 |
| derating.n_circuits | 1 |
| derating.spacing | touching |
| derating.trays | 1 |
| Quantity | Formula | Reference / clause | Notes |
|---|---|---|---|
| Design current (3φ) | Ib = P / (√3 · U · cosφ) | IEC 60364-5-52:2009 cl. 523 / IS 732:2019 Sec. 5.2 | P in kW × 1000, U = 415 V line voltage; 1φ: Ib = P / (U_ph · cosφ) |
| Current-carrying capacity (derated) | Iz2 = n · Ir · k_θ · k_ρ · k_d · k_grp · k_lay (manual mode: n · Ir · k1 · k2 · k3 · k_lay) | IEC 60364-5-52:2009 cl. 523.1; Table A.52.3 (reference methods B, C, E, F, D1, D2); B.52.14 (air temperature), B.52.15 (ground temperature), B.52.16 (soil thermal resistivity), B.52.17 / B.52.20 / B.52.21 (grouping in air), B.52.18 (direct buried), B.52.19 (in ducts); IS 3961 Pt 2 (rating factors, depth); IEC 60287-2-1 (k_θ = √((θmax−θamb)/(θmax−θref)), depth); IS 1554 Pt 1 / IS 7098 Pt 1 base ratings | Base ratings at 40 °C air / 30 °C ground / 1.5 K·m/W / 0.9 m / single circuit; parallel runs counted as circuits in k_grp; grouping rows for n above the table use the next larger row (conservative); Ib ≤ In ≤ Iz (IEC 60364-4-43 cl. 433.1) |
| Voltage drop (3φ, impedance method) | ΔU = √3 · Ib · L · (R·cosφ + X·sinφ) / (1000 · n) | IEC 60364-5-52:2009 Annex G (G.1); IS 732:2019 Annex on voltage drop; conductor R, X per IS 1554 / IS 7098 / IS 8130 | R, X in Ω/km at operating temperature; 1φ: ΔU = 2 · Ib · L · (R·cosφ + X·sinφ)/1000 |
| Voltage drop, percent | ΔU% = ΔU / Un × 100 | NBCS 2026 (SP 7:2026) Part D Sec 2 cl. 6.2 / 5.6 Note a — Split — ≤ 6 % transformer → final DB plus ≤ 3 % final DB → last point (9 % at the last point); IEC 60364-5-52:2009 Annex G Table G.52.1 (≤ 3 % lighting, ≤ 5 % other, from origin); CPWD General Specifications Pt I (2013) cl. on voltage drop | Cascade: first hop from source panel ≤ limit_first_hop, cumulative to last point ≤ limit_total |
| Bus-duct voltage drop | ΔU = √3 · Ib · L · (R·cosφ + X·sinφ) / 1000 | IEC 61439-6:2012 (busbar trunking systems) Annex — voltage drop from manufacturer R, X per metre | Checked against the bus-duct VD allowance (default 2 %) |
| Panel demand (diversity) | DL(N) = Σ connected × DF ; DL(F) = Σ fire/essential loads × 1.0 | NBCS 2026 Part D Sec 2 cl. 4.2.2.2 (diversity) and 4.2.1 (jj) (fire & life-safety supplies); CPWD GS Pt I | DF per panel, default 1.0; cable sized for the diversified demand |
| Breaker rating | In = next standard switchgear rating ≥ max(Ib, I_min) ; standard steps 25, 32, 40, 63, 100, 125, 160, 200, 250, 315, 400, 630, 800, 1000, 1250, 1600, 2000, 2500, 3200, 4000, 5000, 6300 A ; I_min = 25 A default (user-settable) ; MCB ≤ 63 A, MCCB ≤ 630 A, ACB above (configurable) | IEC 60364-4-43:2008 cl. 433.1 (Ib ≤ In ≤ Iz, I2 ≤ 1.45 Iz); IEC 60898-1 (MCB); IEC 60947-2 (MCCB/ACB) | |
| Design current with unbalance | I_b = max(I_R, I_Y, I_B) ; I_N = |I_R + a·I_Y + a²·I_B| ; unbalance = (I_max − I_avg)/I_avg | IEC 60364-5-52:2009 cl. 523.6.3 (neutral carrying current); IEEE 141 / CEA practice ≤ 10 % | 1φ loads on tagged or least-loaded phase; worst-phase VD = L·(I_max·z + I_N·z_N)/(1000·n)/U_ph, z_N = 2z for reduced neutral (3.5-core) |
| Harmonic reduction factor | h3 ≤ 15 %: 1.0 on I_L ; 15–33 %: 0.86 on I_L ; 33–45 %: 0.86 on I_N = 3·h3·I_L ; > 45 %: 1.0 on I_N | IEC 60364-5-52:2009 Annex E, Table E.52.1 | Applied to 4-core / 3.5-core three-phase circuits with neutral |
| Motor starting voltage dip | I_start = m·I_b (DOL 6, Y-Δ 2.5, soft 3, VFD 1.5) ; ΔU_start % = upstream running VD + segment VD at I_start, pf_start 0.3 ≤ 15 % | IEEE 141-1993 cl. 3.11 (starting voltage ≥ 80–85 %); IS 732:2019 cl. 525 note; IEC 60364-5-52 Annex G | Upstream circuits taken at running load (screening) |
| Overload protection rule | I_b ≤ I_n ≤ I_z ; I_2 ≤ 1.45·I_z (I_2 = 1.45 I_n MCB, 1.30 I_n MCCB/ACB, 1.60 I_n gG fuse) | IS 732:2019 cl. 433.1 = IEC 60364-4-43:2008 cl. 433.1; IS/IEC 60898-1 cl. 8.6.2; IEC 60947-2 cl. 7.2.1.2.4; IS 13703 / IEC 60269-1 | Rule on → cable sized for I_n |
| Cable short-circuit withstand (in VD) | S_min = I_k·√t / k ; I_k(bus) = U_ph / |Z_source + Σ(R + jX)·L/(1000·n)| | IS 732:2019 / IEC 60364-4-43:2008 cl. 434.5.2, Table 43A (k); IEC 60909-0 (c = 1 screening) | t = clearing time of the feeder breaker (MCB 0.01 s, MCCB 0.03 s, ACB 0.4 s); parallel runs share the fault current |
| Standard | Title | Used for |
|---|---|---|
| IS 732:2019 | Code of practice for electrical wiring installations | Voltage-drop limits, cable selection, protection coordination (adopts IEC 60364) |
| IEC 60364-5-52:2009 | Low-voltage electrical installations — Selection and erection of wiring systems | Current-carrying capacity, derating (temperature, grouping, installation method), voltage drop ≤ 3–5 % |
| IEC 60364-4-43:2008 | Protection against overcurrent | Ib ≤ In ≤ Iz, adiabatic cable withstand I²t ≤ k²S² with k = 143 (Cu XLPE), 115 (Cu PVC), 94 (Al XLPE), 76 (Al PVC) |
| IS 1554 (Part 1):1988 | PVC insulated (heavy duty) electric cables up to 1100 V | Cable ratings, resistance and reactance data |
| IS 3961 (Part 2):1967 (reaffirmed) | Recommended current ratings for cables — PVC insulated and PVC sheathed heavy duty cables | Rating factors for ambient / ground temperature, soil thermal resistivity, depth of laying and grouping; installation categories (in air, in ground, in ducts) |
| IEC 60287-1-1 / 60287-2-1 | Electric cables — Calculation of the current rating | Temperature correction √((θmax−θamb)/(θmax−θref)) and depth-of-laying correction |
| IS 7098 (Part 1):1988 | Cross-linked polyethylene insulated PVC sheathed cables up to 1100 V | XLPE cable ratings (90 °C), resistance and reactance data |
| IS 694:2010 | PVC insulated cables for working voltages up to 1100 V | FRLS wiring conductors |
| CPWD General Specifications for Electrical Works (Part I Internal, Part IV Substation) | CPWD specifications | Voltage-drop cascade limits, cable/wiring practice, panel and metering requirements |
| IEC 60947-2:2016 / IS/IEC 60947-2 | Low-voltage switchgear — Circuit-breakers | ACB/MCCB ratings Icu, Ics, Icw; release characteristics (L-S-I-G); selectivity definitions |
| IEC 60898-1:2015 / IS/IEC 60898-1 | Circuit-breakers for overcurrent protection for household and similar installations (MCB) | B/C/D tripping bands (C: 5–10 × In), thermal tripping 1.13/1.45 × In |
| IS 13703 / IEC 60269-1 | Low-voltage fuses | I2 = 1.6 In for gG fuses in the overload rule |
| IEEE 141-1993 (Red Book) | Recommended practice for electric power distribution for industrial plants | Motor starting voltage dip (≥ 80–85 % at terminals), phase unbalance practice |
| IEC 60909-0:2016 | Short-circuit currents in three-phase a.c. systems — Calculation of currents | Impedance method, voltage factor c (1.05 / 1.10 max, 0.95 min), peak factor κ = 1.02 + 0.98·e^(−3R/X), Ik" = c·Un/(√3·Zk) |
| NBCS 2026 (SP 7:2026) Part D Sec 2 | National Building Construction Standards — Electrical and allied installations | Load assessment and diversity, circuits, cables (4-core), earthing, lightning protection, standby supply for fire & life-safety loads |
Results are design aids computed by designlink calc (calc.designlink.in). Verify against the applicable code and manufacturer cable data before issue.