SAMPLE Wi-Fi heat map & AP design — this is what your report looks like, generated from demo inputs. Generate yours → 2 free designs every day for every signed-in account · 1 design free on sign-in · ₹99 + GST per design (report + Excel + DXF) · free for DesignLink companies
Report ready — use Print → Save as PDF (A4 landscape).
Design Linkcalc.designlink.in

Wi-Fi heat map & AP design

Sample project — Tower A · Sample project — Tower A · 5 GHz · 4 APs
Generated 28 Nov 2026 16:09
Predictive coverage · ITU-R P.1238 multi-wall
Project code SAMPLE
Floors
1
Access points
4
Served area
442 m²
m² per AP
110
Users
83
Primary coverage
96.8 %
Checks
1 to review

1. Design basis

ItemValueBasis
Band5 GHzdesign band for coverage (2.4 GHz covers further; 5 / 6 GHz carry the capacity)
EnvironmentOffice / hotelITU-R P.1238 distance exponent
AP modelWi-Fi 6 indoor, 2×2 / 4×4 (standard office)EIRP, gain, design clients per AP
Targetsprimary ≥ -65 dBm on ≥ 95 % of the area, SNR ≥ 25 dBenterprise WLAN design practice (voice / data grade)
Path lossL = L₀(1 m, f) + 10·n·log₁₀(d) + Σ wall losses (material × band); RSSI = EIRP − LITU-R P.1238 / COST-231 multi-wall model
Placementgreedy coverage on a sample grid, then a capacity split where an AP exceeds its design clients, then channel colouring of neighboursproject
HeightsAP 2.8 m · client 1.0 mproject
Wallsdefault drywall; per room overridematerial loss table
Floorsevaluated floor by floor (no slab leakage)ITU-R P.1238 floor penetration
CodeNBCS 2026 (SP 7:2026) Part D Sec 6 — APs ≥ IEEE 802.11ax / be; horizontal ≤ 90 m, extra TR above 930 m²; coverage, capacity and interference planned with this planning tool and confirmed by a site survey and periodic monitoringcl. 3.2.5, 3.1.3.2, 3.4.1.1, A-6.3
Cable routeTR → AP drop = (|Δx| + |Δy|) × 1.25 + 8.0 m (rise / fall, slack); TR at the floor's 'tr' point, else the centre of the served area; longest 25.3 mpermanent link ≤ 90 m

2. Checks

CheckResult
Primary coverage ≥ 95 % of the served area at ≥ -65 dBm on every floorPASS
Minimum SNR ≥ 25 dB in every roomCHECK
Every AP within its design client loadPASS
Neighbouring APs on different channelsPASS
Every AP supports IEEE 802.11ax / be or later (NBCS 2026 Part D Sec 6 cl. 3.2.5 (b))PASS
Horizontal cable TR → AP ≤ 90 m incl. slack, + 10 m cords (NBCS 2026 Part D Sec 6 cl. 3.1.3.2 / 3.4.1.1 (a))PASS

3. Ground — 4 APs · coverage 96.8 % / secondary 76.2 % · 82.6 users

Office 1100.0 % · min -64.1 dBm · 11.5 usersMeeting room100.0 % · min -43.5 dBm · 48.0 usersCorridor100.0 % · min -53.6 dBm · 2.0 usersOpen office100.0 % · min -63.0 dBm · 15.6 usersPlant room74.5 % · min -69.3 dBm · 5.5 usersLift shaftAP-GR-01 ch 36 · 31.0 usersAP-GR-01AP-GR-02 ch 40 · 10.8 usersAP-GR-02AP-GR-03 ch 44 · 15.9 usersAP-GR-03AP-GR-04 ch 48 · 24.9 usersAP-GR-04-85 dBm-45 dBmRSSI dBm (best AP)

Channel plan

Ground — channel plan (5 GHz, 4 channels in use)36AP-GR-0140AP-GR-0244AP-GR-0348AP-GR-04ch 36ch 40ch 44ch 48same colour = same channel; a red dashed line marks two APs on the same channel within 18 m

Access points

APRoomModelTx dBmChannelMountUsersArea m²Drop mOK
AP-GR-01C1Wi-Fi 6 indoor, 2×2 / 4×4 (standard office)2336ceiling31.0310.88.2PASS
AP-GR-02R2Wi-Fi 6 indoor, 2×2 / 4×4 (standard office)2340ceiling10.839.814.4PASS
AP-GR-03R2Wi-Fi 6 indoor, 2×2 / 4×4 (standard office)2344ceiling15.931.821.5PASS
AP-GR-04R2Wi-Fi 6 indoor, 2×2 / 4×4 (standard office)2348ceiling24.959.825.3PASS

Rooms

RoomAreaUsersRSSI min / meanCoverageSNR minRate minAPsOK
Office 196.011.5-64.1 / -56.5 dBm100.0 %28.9648 MbpsAP-GR-01, AP-GR-02PASS
Meeting room96.048.0-43.5 / -35.2 dBm100.0 %49.51201 MbpsAP-GR-02, AP-GR-03, AP-GR-04PASS
Corridor65.02.0-53.6 / -43.5 dBm100.0 %39.4960 MbpsAP-GR-01, AP-GR-04PASS
Open office130.015.6-63.0 / -55.1 dBm100.0 %30.0648 MbpsAP-GR-01PASS
Plant room55.05.5-69.3 / -61.6 dBm74.5 %23.7576 MbpsAP-GR-01, AP-GR-02, AP-GR-04CHECK
Lift shaft9.0None—not servedNone

4. Coverage distribution and horizontal cabling

Coverage CDF — % of served area with RSSI ≥ x-90-80-70-60-50-40-300 %25 %50 %75 %100 %target -65 dBm95 %Ground — 96.8 % at -65 dBmRSSI dBm (best server)
FloorTR at (x, y)Served m²TRs (930 m² each)Longest dropMean dropOver 90 m
Ground13.04, 9.36 (assumed centre)442.0125.3 m17.4 mnone

5. Bill of quantities

ItemQtyUnit
Access point — Wi-Fi 6 indoor, 2×2 / 4×4 (standard office)4nos
Cat 6A drops to APs8nos
Cat 6A cable360m
PoE switch ports4nos

6. Worked examples — from this project

Worked from this project’s own inputs and results — each value can be traced to the schedules above.

Ground — Plant room: weakest point of the weakest room
lowest minimum RSSI in this project (-69.3 dBm); best server AP-GR-04
Given: AP AP-GR-04 Wi-Fi 6 indoor, 2×2 / 4×4 (standard office) at (21.5, 4) m, Tx 23 dBm, gain 4 dBi · Point (25.75, 15.75) m · Band 5 GHz (5500 MHz), Office / hotel n = 3.0
1. EIRP: EIRP = Ptx + Gant = 23 + 4 = 27 dBm
2. Free-space loss at 1 m: L0 = 20·log10(4π·f/c) = 20·log10(4π × 5500·106 / 3·108) = 47.25 dB
3. Distance (3-D): d = √(Δx² + Δy² + Δz²) = √(12.49² + 1.8²) = 12.62 m (AP 2.8 m, client 1.0 m)
4. Distance loss: 10·n·log10(d) = 10 × 3.0 × log10(12.62) = 33.04 dB
5. Wall losses: Σ Lwall (material × band) = 4 × drywall 4 dB = 16 dB
6. Path loss: L = L0 + 10·n·log10(d) + Σ Lwall = 47.25 + 33.04 + 16 = 96.28 dB
7. RSSI: RSSI = EIRP − L + Gclient = 27 − 96.28 + 0 = -69.3 dBm (engine -69.3 dBm)
8. Signal at the weakest point: RSSI ≥ -65 dBm → -69.3 dBm CHECK (the target applies to ≥ 95 % of the area, not every point)
9. SNR: SNR = RSSI − noise floor = -69.3 − (-93) = 23.7 dB (rate ≈ 576 Mbps from the SNR → MCS table)
10. Minimum SNR: SNR ≥ 25 dB → 23.7 dB CHECK
11. Room coverage: area ≥ -65 dBm ≥ 95 % → 74.5 % CHECK (add an AP in the room or lower the wall loss)
Ground — capacity of AP-GR-01
the most loaded AP (users ÷ design clients) in this project
Given: Association each user joins the strongest AP; AP-GR-01 is best server over 310.8 m² of the rooms below — only the users in that area load it
1. Users — Office 1: N = density × served area = 0.12 /m² × 96 m² = 11.5 (density from the room-type table)
2. Users — Corridor: N = density × served area = 0.03 /m² × 65 m² = 2 (density from the room-type table)
3. Users — Open office: N = density × served area = 0.12 /m² × 130 m² = 15.6 (density from the room-type table)
4. Users — Plant room: N = density × served area = 0.1 /m² × 55 m² = 5.5 (density from the room-type table)
5. AP client load: users ≤ design clients → 31.0 ≤ 35 PASS (max 60 associated)
6. APs on the floor: coverage pass + capacity split = 1 + 3 = 4 (442 m² served → 110 m²/AP)
7. Cable (project): drops × length = 4 APs × 2 × 45 m = 360 m

Predictive design — a post-installation validation survey (−65 / −67 dBm, SNR, roaming) confirms the coverage; wall losses are typical values and should be adjusted to the actual construction.

7. Codes and standards

Indian code edition: NBCS 2026 (SP 7:2026). NBCS gives no RSSI / SNR values — the coverage targets are industry design practice.

NBCS 2026 clausePDF pageGoverns
Part D Sec 6 cl. 3.2.5 (b)2476Access points support at least IEEE 802.11 ax / be; centralised controller; secure access by the owner
Part D Sec 6 cl. 3.2.5 (last para)2476Spacing to avoid frequency overlap; materials, configuration, furnishings; site survey and planning tool; periodic monitoring
Part D Sec 6 cl. 3.1.3.22471Horizontal cable ≤ 90 m incl. slack; additional TR above 930 m² served
Part D Sec 6 cl. 3.4.1.1 (a)2483Four-pair UTP / ScTP 90 m with 10 m patch cords
Part D Sec 6 Table 12473Category 6A / Class EA cabling
Part D Sec 6 Annex A-6.32499Coverage by user density, interference management (frequency planning, power control), capacity planning
StandardTitleUsed for
NBCS 2026 (SP 7:2026) Part D Sec 6National Building Construction Standards — Information and communication enabled installationsStructured cabling, Wi-Fi (IEEE 802.11ax/be), ICT spaces
ITU-R P.1238-12Propagation data and prediction methods for the planning of indoor radiocommunication systemsIndoor path-loss model (distance exponent, wall losses)
IEEE 802.11ax / beWireless LANWi-Fi 6E / 7
ANSI/TIA-568 series (568.0-E, .1-E, .2-D, .3-E)Telecommunications cabling standardsCopper / fibre categories and testing
ANSI/TIA-569-ETelecommunications pathways and spacesTelecom rooms and pathways
ISO/IEC 11801-1:2017Generic cabling for customer premisesCabling classes
Prepared by
Checked by
Approved by

Results are design aids computed by designlink calc (calc.designlink.in) and must be reviewed by a qualified engineer before issue. Ground levels marked "assumed" have no survey level within reach — verify.