Domestic water supply — risers & branches

Sample project — Tower A · Indian regime · NBCS 2026 (SP 7:2026) Part E Sec 1 · flush-tank · private
Generated 28 Nov 2026 16:09
Fixture units → probable flow → pipe sizes → pressure at the critical fixture → booster
Project code SAMPLE
Risers
2
Fixtures
180
WSFU
260.0
Probable flow
6.31 L/s
Largest riser
50 mm
Boosted risers
2

1. Design basis

ItemValueReference
Fixture unitsprivate use, flush-tank systemNBCS 2026 Part E Sec 1 Table 2 (Hunter's method; Note 9 hot / cold ¾)
Probable flowNBCS 2026 Part E Sec 1 Table 3 (flush-tank column)NBCS 2026 Part E Sec 1 Table 3 / Fig. 2 (to 10 000 FU, linear between the table values)
PipeCPVC (IS 15778) · C = 140 · actual bore · velocity ≤ 2.0 m/s risers, 2.4 m/s branchesHazen–Williams; NBCS 2026 cl. 4.8.6 v ≤ 2.4 m/s (copper hot water 1.5 m/s)
Pressure limitstatic ≤ 4.2 bar at the outlets — PRV stations in the riser / downcomer (1 working + 1 standby, strainer, isolation valves, gauges), the next station where the pressure below one passes the limit again, set 2.0 barNBCS 2026 Part E Sec 1 cl. 4.7.5 (0.42 N/mm², PRV above); zoning cl. 4.8.6 (7–9 floors)
Boosterwhere gravity falls short — the top floors down to the lowest short floor · head to suitproject
Residual pressure0.5 bar at fixtures, 1.0 bar at flush valvesNBCS 2026 Part E Sec 1 cl. 3.1.2 (0.18 bar at taps, 0.5 bar some fixtures, 1.0 bar flush valves)
Sourceoht — water level 36 mproject
Fittings allowance30 % of pipe frictionpractice

2. Fixture units and probable demand

FixtureNosWSFU eachWSFU
WC — flush tank40280
Wash basin801.5120.0
Shower40280
Kitchen sink20240
Probable demand vs fixture units — NBCS 2026 Part E Sec 1 Table 3 / Fig. 21110101001001,0001,00010,000fixture units (WSFU, log scale)probable demand, L/min (log scale)flush valvesflush tanksCR-1● CR-1: 170 FU → 223 L/min■ CR-1 booster: 17 FU → 46.2 L/minHR-1● HR-1: 90 FU → 155 L/min■ HR-1 booster: 27 FU → 68.9 L/min

Each riser plotted at its total WSFU and probable demand — NBCS 2026 Table 3 runs to 10 000 FU; flush-valve and flush-tank demands are the same above 1 000 FU (Table 2 Note 4).

3. Riser diagram

CR-1 · COLD · downfeed · gravity + booster50 mm · 170 WSFU · 3.722 L/s25 · 0.77F920 mm · 17 FU · 0.77 L/s1.17/0.5 bar · BOOST50 · 3.507F820 mm · 17 FU · 0.77 L/s0.51/0.5 bar50 · 3.286F720 mm · 17 FU · 0.77 L/s0.82/0.5 bar50 · 3.045F620 mm · 17 FU · 0.77 L/s1.12/0.5 bar50 · 2.803F520 mm · 17 FU · 0.77 L/s1.43/0.5 bar40 · 2.492F420 mm · 17 FU · 0.77 L/s1.72/0.5 bar40 · 2.17F320 mm · 17 FU · 0.77 L/s2.01/0.5 bar32 · 1.849F220 mm · 17 FU · 0.77 L/s2.29/0.5 bar32 · 1.388F120 mm · 17 FU · 0.77 L/s2.59/0.5 bar25 · 0.77GF20 mm · 17 FU · 0.77 L/s2.88/0.5 barOHT + BOOSTERBooster 46.2 L/min (2.77 m³/h) @ 10 m — F9HR-1 · HOT · downfeed · gravity + booster40 mm · 90 WSFU · 2.587 L/s25 · 1.148F915 mm · 9 FU · 0.487 L/s0.7/0.5 bar · BOOST25 · 0.808F815 mm · 9 FU · 0.487 L/s0.99/0.5 bar · BOOST20 · 0.487F715 mm · 9 FU · 0.487 L/s1.27/0.5 bar · BOOST40 · 2.075F615 mm · 9 FU · 0.487 L/s0.59/0.5 bar32 · 1.905F515 mm · 9 FU · 0.487 L/s0.86/0.5 bar32 · 1.703F415 mm · 9 FU · 0.487 L/s1.15/0.5 bar32 · 1.451F315 mm · 9 FU · 0.487 L/s1.44/0.5 bar25 · 1.148F215 mm · 9 FU · 0.487 L/s1.7/0.5 bar25 · 0.808F115 mm · 9 FU · 0.487 L/s1.98/0.5 bar20 · 0.487GF15 mm · 9 FU · 0.487 L/s2.26/0.5 barOHT + BOOSTERBooster 68.9 L/min (4.13 m³/h) @ 11.1 m — F9, F8, F7

4. Risers

CR-1 — cold riser, downfeed, 50 mm · 170 WSFU · 3.722 L/s

FloorLevel mFixturesWSFUBranch L/sBranch mmv m/sZoneRiser fromΣ WSFU carriedRiser L/sRiser mmv m/sStatic mFriction mAvailable barStatic barRequired barPRVResult
F929.74 × WC, 4 × Wash basin, 2 × Shower, 1 × Kitchen sink17.00.77202.08boosterBOOSTER17.00.77251.3115.13.181.171.480.5N/APASS booster
F826.44 × WC, 4 × Wash basin, 2 × Shower, 1 × Kitchen sink17.00.77202.08gravityOHT153.03.507501.588.43.190.510.820.5N/APASS
F723.14 × WC, 4 × Wash basin, 2 × Shower, 1 × Kitchen sink17.00.77202.08gravityF8136.03.286501.4811.73.390.821.150.5N/APASS
F619.84 × WC, 4 × Wash basin, 2 × Shower, 1 × Kitchen sink17.00.77202.08gravityF7119.03.045501.3715.03.561.121.470.5N/APASS
F516.54 × WC, 4 × Wash basin, 2 × Shower, 1 × Kitchen sink17.00.77202.08gravityF6102.02.803501.2718.33.711.431.790.5N/APASS
F413.24 × WC, 4 × Wash basin, 2 × Shower, 1 × Kitchen sink17.00.77202.08gravityF585.02.492401.8121.64.081.722.120.5N/APASS
F39.94 × WC, 4 × Wash basin, 2 × Shower, 1 × Kitchen sink17.00.77202.08gravityF468.02.17401.5724.94.372.012.440.5N/APASS
F26.64 × WC, 4 × Wash basin, 2 × Shower, 1 × Kitchen sink17.00.77202.08gravityF351.01.849321.8228.24.822.292.760.5N/APASS
F13.34 × WC, 4 × Wash basin, 2 × Shower, 1 × Kitchen sink17.00.77202.08gravityF234.01.388321.3631.55.092.593.090.5N/APASS
GF0.04 × WC, 4 × Wash basin, 2 × Shower, 1 × Kitchen sink17.00.77202.08gravityF117.00.77251.3134.85.432.883.410.5N/APASS

Booster (combination system: these floors on the booster, the rest by gravity): hydro-pneumatic booster set (variable speed) at the OHT / terrace for the top floors — separate boosted riser — floors F9, 17.0 WSFU → 0.77 L/s (46.2 L/min, 2.77 m³/h) at 10.0 m (to give the critical boosted floor its residual + 2 m), boosted riser 25 mm, ≈ 0.14 kW hydraulic · N+1 (duty + standby).

HR-1 — hot riser, downfeed, 40 mm · 90 WSFU · 2.587 L/s

FloorLevel mFixturesWSFUBranch L/sBranch mmv m/sZoneRiser fromΣ WSFU carriedRiser L/sRiser mmv m/sStatic mFriction mAvailable barStatic barRequired barPRVResult
F929.74 × Wash basin, 2 × Shower, 1 × Kitchen sink9.00.487152.39boosterBOOSTER27.01.148251.9516.26.010.71.590.5N/APASS booster
F826.44 × Wash basin, 2 × Shower, 1 × Kitchen sink9.00.487152.39boosterF918.00.808251.3719.56.380.991.910.5N/APASS booster
F723.14 × Wash basin, 2 × Shower, 1 × Kitchen sink9.00.487152.39boosterF89.00.487201.3222.86.831.272.240.5N/APASS booster
F619.84 × Wash basin, 2 × Shower, 1 × Kitchen sink9.00.487152.39gravityOHT63.02.075401.5115.05.970.591.470.5N/APASS
F516.54 × Wash basin, 2 × Shower, 1 × Kitchen sink9.00.487152.39gravityF654.01.905321.8718.36.450.861.790.5N/APASS
F413.24 × Wash basin, 2 × Shower, 1 × Kitchen sink9.00.487152.39gravityF545.01.703321.6721.66.841.152.120.5N/APASS
F39.94 × Wash basin, 2 × Shower, 1 × Kitchen sink9.00.487152.39gravityF436.01.451321.4324.97.131.442.440.5N/APASS
F26.64 × Wash basin, 2 × Shower, 1 × Kitchen sink9.00.487152.39gravityF327.01.148251.9528.27.831.72.760.5N/APASS
F13.34 × Wash basin, 2 × Shower, 1 × Kitchen sink9.00.487152.39gravityF218.00.808251.3731.58.21.983.090.5N/APASS
GF0.04 × Wash basin, 2 × Shower, 1 × Kitchen sink9.00.487152.39gravityF19.00.487201.3234.88.652.263.410.5N/APASS

Booster (combination system: these floors on the booster, the rest by gravity): hydro-pneumatic booster set (variable speed) at the OHT / terrace for the top floors — separate boosted riser — floors F9, F8, F7, 27.0 WSFU → 1.148 L/s (68.9 L/min, 4.13 m³/h) at 11.1 m (to give the critical boosted floor its residual + 2 m), boosted riser 25 mm, ≈ 0.23 kW hydraulic · N+1 (duty + standby).

Zoning (NBCS 2026 Part E Sec 1 cl. 4.8.6): every pressure zone spans ≤ 9 floors (largest 9).

5. Bill of quantities

ItemQtyUnit
CPVC (IS 15778) pipe 15 mm80.0m
CPVC (IS 15778) pipe 20 mm86.6m
CPVC (IS 15778) pipe 25 mm25.8m
CPVC (IS 15778) pipe 32 mm16.5m
CPVC (IS 15778) pipe 40 mm22.8m
CPVC (IS 15778) pipe 50 mm19.5m
Hydro-pneumatic booster set — CR-1 (2.77 m³/h @ 10.0 m, duty + standby)1set
Hydro-pneumatic booster set — HR-1 (4.13 m³/h @ 11.1 m, duty + standby)1set
WC — flush tank40nos (taps / stop valves)
Wash basin80nos (taps / stop valves)
Shower40nos (taps / stop valves)
Kitchen sink20nos (taps / stop valves)

6. Checks

CheckResult
Velocity ≤ 2 m/s in risers, ≤ 2.4 m/s in branchesPASS
Residual ≥ 0.5 bar at every fixture (1.0 bar at flush valves) — by gravity or on the boosterPASS
Static pressure at the outlets ≤ 4.2 bar — PRVs in the riser / downcomer set to 2 barPASS
Every riser within the standard sizesPASS

7. Worked examples — from this project

Worked from this project’s own inputs and results — each value can be traced to the schedules above.

Riser CR-1 — F8 branch (critical fixture)
largest riser (170 WSFU, cold, downfeed); the floor with the least pressure margin
Given: Fixtures 4 × WC, 4 × Wash basin, 2 × Shower, 1 × Kitchen sink · Pipe C = 140, fittings + 30 % of friction, branch 8 m
1. Fixture units: WSFU = Σ n · u (two-temperature fixtures × hot / cold share) = 4 × 2 + 4 × 1.5 × 0.75 + 2 × 2 × 0.75 + 1 × 2 × 0.75 = 17 WSFU (NBCS 2026 Part E Sec 1 Table 2, private use)
2. Probable flow (Hunter): Q = f(WSFU) = NBCS 2026 Part E Sec 1 Table 3 (flush-tank column): 10 FU → 30.3 L/min, 20 FU → 53 L/min → 46.19 L/min ÷ 60 = 0.77 L/s (engine 0.77 L/s)
3. Branch velocity at 20 mm (bore 21.7 mm): v = Q / (π d² / 4) = 0.770×10⁻³ / (π × 0.0217² / 4) = 2.08 m/s (15 mm would give 3.78 m/s)
4. Branch size: smallest size with v ≤ 2.4 m/s → 20 mm at 2.08 m/s PASS
5. Branch friction: h = 10.67 · L · Q1.852 / (C1.852 · d4.87) × (1 + fittings) = 10.67 × 8 × (0.770×10⁻³)1.852 / (1401.852 × 0.02174.87) × 1.3 = 2.54 m (engine 2.54 m)
Riser CR-1 — OHT → F8 (full gravity riser flow)
the first length off the source carries every floor of its zone downstream
Given: Carried Σ 153 WSFU, 9.6 m
1. Probable flow (Hunter): Q = f(Σ WSFU) = NBCS 2026 Part E Sec 1 Table 3 (flush-tank column): 140 FU → 200.6 L/min, 180 FU → 230.9 L/min → 210.45 L/min ÷ 60 = 3.507 L/s (engine 3.507 L/s)
2. Riser velocity at 50 mm (bore 53.1 mm): v = Q / (π d² / 4) = 3.507×10⁻³ / (π × 0.0531² / 4) = 1.58 m/s (40 mm would give 2.54 m/s)
3. Riser size: smallest size with v ≤ 2 m/s → 50 mm at 1.58 m/s PASS
4. Friction: h = 10.67 · L · Q1.852 / (C1.852 · d4.87) × (1 + fittings) = 10.67 × 9.6 × (3.507×10⁻³)1.852 / (1401.852 × 0.05314.87) × 1.3 = 0.648 m (engine 0.648 m)
Residual pressure — CR-1 at F8
pressure traced from the source to the critical fixture (outlet ≈ 1.2 m above the floor)
1. Static head: Hs = zOHT water level − zfloor − 1.2 = 36 − 26.4 − 1.2 = 8.4 m
2. Friction to the fixture: Σ hriser (source → floor) + hbranch = 3.19 m (branch 2.54 m)
3. Available: P = (Hs − Σ h) / 10.2 − meter − heater = (8.4 − 3.19) / 10.2 = 0.51 bar (engine 0.51 bar)
4. Residual at the fixture: P ≥ 0.5 bar → 0.51 bar PASS
5. Booster flow: Q = f(Σ WSFU of the boosted floors) = 17 WSFU → NBCS 2026 Part E Sec 1 Table 3 (flush-tank column) = 0.77 L/s (46.2 L/min · 2.77 m³/h)
6. Booster head: H = max(largest gravity deficit of the boosted floors × 10.2 + 2, 10) = 10 m (the boosted floors get their residual)
7. Hydraulic power: P = 9.81 · Q · H / 0.55 = 9.81 × 0.77×10⁻³ × 10 / 0.55 = 0.14 kW (engine 0.14 kW)

8. Standards applied

StandardUsed for
NBCS 2026 (SP 7:2026) Part E Sec 1Water supply — Table 2 fixture units, Table 3 / Fig. 2 probable demand, cl. 3.1.2 / 4.7.5 pressures, cl. 4.8.6 zoning and velocity
IS 2065:1983Code of practice for water supply in buildings
IS 15778 / IS 1239 / IS 15801CPVC / GI / PP-R pipes
CPHEEO Manual on Water SupplyDemand, storage