Design Link calc Short-circuit analysis · IEC 60909

Direct calculation — one source, one cable

Minimum inputs; everything else defaults to standard values (editable).
Transformers / DG sets / utility infeeds sit on a bus (the source panel in the cascade, e.g. TRANSFORMER or MAIN LT PANEL). Sources on the same bus act in parallel.
NameBusTypekVA%Z / Xd"%X/RUpstream MVADG ∥ TROnZ (mΩ)Ik" alone (kA)

%Z and X/R default by kVA (IS 1180 / IS 2026 typical) when left blank. DG: Xd" default 16 %. Utility with blank MVA = infinite bus. DG-only case (transformer off) gives the minimum fault level for protection sensitivity.

Fault level at each panel bus

Segments come from the voltage-drop cascade (cable, runs, length, breaker). Breaker Icu is picked for the fault level at the upstream bus; the cable is checked adiabatically (I²t ≤ k²S²) for that same fault.
#From busToLinkCable / bus ductRunsL mBreakert clr s R+jX seg mΩZ cum mΩX/RIk" From kAIk" To kAip kAIcu ≥ kAS min / haveI²tIk" DG kA
Discrimination (selectivity)For a fault below any breaker, only that breaker should trip — the upstream one must stay closed. Each upstream / downstream pair is checked from the downstream pick-up up to the fault level Ik" at that bus, with tolerance bands (±10 % current, ±20 % time). Set Ir, tr, Isd, tsd, Ii per breaker below; defaults by type are in Settings.

Breaker settings

multiples: Ir = ×In · Isd = ×Ir · Ii = ×In (0 = OFF)
#Breaker (feeder)TypeIn AIr ×Intr s @6IrIsd ×Irtsd sIi ×Inti sIr AIsd AIi AIk" bus kA

Upstream ↔ downstream pairs

Time-current curves

click a pair

System & IEC 60909 factors

Cable withstand (k, clearing time)

Breaker kA steps

Source defaults

Transformer defaults by kVA (used when %Z / X/R left blank)

Breaker trip defaults by type (discrimination)

Method — IEC 60909 impedance method (LV radial)

ZT = %Z/100 · U²/S   (R, X split by X/R)
ZQ = c·U²/S"kQ (utility, in series with the transformer)
ZG = Xd"/100 · U²/S (DG)
Zcable = (R·f20°C + jX) · L / 1000 / runs
Ik" = c · Un / (√3 · |Zk|)   c = 1.05 (max), 0.95 (min)
κ = 1.02 + 0.98·e−3R/X  ·  ip = κ · √2 · Ik"

Breaker breaking capacity

Each feeder breaker sits on its upstream bus, so it must break the fault level of that bus: Icu ≥ Ik" at "From". The next standard step is shown (6 / 10 / 16 / 25 / 36 / 50 / 65 / 80 / 100 kA …, editable).

Cable withstand (IEC 60364-4-43)

I²t ≤ k²S² → Smin = Ik"·√t / k with k = 143 (Cu XLPE), 115 (Cu PVC), 94 (Al XLPE), 76 (Al PVC) and t = fault clearing time of the upstream breaker (MCB 0.01 s, MCCB 0.03 s, ACB 0.4 s with short-time delay — editable per feeder). Parallel runs share the fault: S = size × runs.

Discrimination (selectivity)

Trip model: long-time I²t inverse with asymptote at Ir (t = tr·35/((I/Ir)²−1), tr = time at 6×Ir), short-time definite delay tsd above Isd, instantaneous ti above Ii. Bands ±10 % current, ±20 % time. Downstream discriminates at a current when its slowest trip is still faster than the upstream's fastest. The selectivity limit is the highest fault current for which this holds. Full = limit ≥ Ik" at the bus; partial = limit below Ik" (typical when the upstream instantaneous Ii is inside the fault range → raise Ii, use an ACB with Ii OFF and tsd, or rely on the manufacturer's selectivity tables / zone selectivity).

DG-only case

Transformer and utility off, DG on: minimum fault level with c = 0.95 — use it to check that protection still trips at the far end when running on DG.

Results are design aids; verify with manufacturer data (transformer test certificate %Z, breaker let-through, cable k) before issue.