Direct calculation — one source, one cable
Minimum inputs; everything else defaults to standard values (editable).| Name | Bus | Type | kVA | %Z / Xd"% | X/R | Upstream MVA | DG ∥ TR | On | Z (mΩ) | Ik" alone (kA) |
|---|
%Z and X/R default by kVA (IS 1180 / IS 2026 typical) when left blank. DG: Xd" default 16 %. Utility with blank MVA = infinite bus. DG-only case (transformer off) gives the minimum fault level for protection sensitivity.
Fault level at each panel bus
| # | From bus | To | Link | Cable / bus duct | Runs | L m | Breaker | t clr s | R+jX seg mΩ | Z cum mΩ | X/R | Ik" From kA | Ik" To kA | ip kA | Icu ≥ kA | S min / have | I²t | Ik" DG kA |
|---|
Breaker settings
multiples: Ir = ×In · Isd = ×Ir · Ii = ×In (0 = OFF)| # | Breaker (feeder) | Type | In A | Ir ×In | tr s @6Ir | Isd ×Ir | tsd s | Ii ×In | ti s | Ir A | Isd A | Ii A | Ik" bus kA |
|---|
Upstream ↔ downstream pairs
Time-current curves
click a pairSystem & IEC 60909 factors
Cable withstand (k, clearing time)
Breaker kA steps
Source defaults
Transformer defaults by kVA (used when %Z / X/R left blank)
Breaker trip defaults by type (discrimination)
Method — IEC 60909 impedance method (LV radial)
ZT = %Z/100 · U²/S (R, X split by X/R)
ZQ = c·U²/S"kQ (utility, in series with the transformer)
ZG = Xd"/100 · U²/S (DG)
Zcable = (R·f20°C + jX) · L / 1000 / runs
Ik" = c · Un / (√3 · |Zk|) c = 1.05 (max), 0.95 (min)
κ = 1.02 + 0.98·e−3R/X · ip = κ · √2 · Ik"
Breaker breaking capacity
Each feeder breaker sits on its upstream bus, so it must break the fault level of that bus: Icu ≥ Ik" at "From". The next standard step is shown (6 / 10 / 16 / 25 / 36 / 50 / 65 / 80 / 100 kA …, editable).
Cable withstand (IEC 60364-4-43)
I²t ≤ k²S² → Smin = Ik"·√t / k with k = 143 (Cu XLPE), 115 (Cu PVC), 94 (Al XLPE), 76 (Al PVC) and t = fault clearing time of the upstream breaker (MCB 0.01 s, MCCB 0.03 s, ACB 0.4 s with short-time delay — editable per feeder). Parallel runs share the fault: S = size × runs.
Discrimination (selectivity)
Trip model: long-time I²t inverse with asymptote at Ir (t = tr·35/((I/Ir)²−1), tr = time at 6×Ir), short-time definite delay tsd above Isd, instantaneous ti above Ii. Bands ±10 % current, ±20 % time. Downstream discriminates at a current when its slowest trip is still faster than the upstream's fastest. The selectivity limit is the highest fault current for which this holds. Full = limit ≥ Ik" at the bus; partial = limit below Ik" (typical when the upstream instantaneous Ii is inside the fault range → raise Ii, use an ACB with Ii OFF and tsd, or rely on the manufacturer's selectivity tables / zone selectivity).
DG-only case
Transformer and utility off, DG on: minimum fault level with c = 0.95 — use it to check that protection still trips at the far end when running on DG.
Results are design aids; verify with manufacturer data (transformer test certificate %Z, breaker let-through, cable k) before issue.