Until now the heat-load inputs were measured by hand: a polyline around each room, wall lengths per direction, glass per wall, typed into a sheet. This tool reads the architect's drawing instead. You tell it which layers are the walls, doors, windows and room names; it finds every enclosed room, measures each wall, works out its compass direction from the north arrow, sees what is on the other side of the wall (outside, another AC room, or a non-AC space such as a toilet or corridor), attaches the windows to the right walls, and stacks the floors so it knows which rooms have an exposed roof, a floor on the ground, or another room above and below.
You check the result on the plan (rooms coloured by service, exposed walls in red, glass in blue) and in a 3D view, fix anything the drawing made ambiguous (merge two rooms, draw a room, rename, delete a courtyard), set the service of each room (AC, ventilation, exhaust, none) and hand over to the heat-load tool. The same model will feed lighting, sprinkler and plumbing tools.
| Item | What the tool reads | Typical layer names |
|---|---|---|
| Walls | Lines, polylines, hatches or blocks that outline the walls (double-line walls are expected; single-line walls also work). Everything on the chosen layers is used. | A-WALL, WALL, WALLS, ARCH-WALL |
| Doors | Door blocks or door leaf + swing arc. Each door seals its opening so the room does not "leak" into the corridor. | A-DOOR, DOOR |
| Windows / glass | Lines or blocks in the wall. The length along the wall × the storey glass height = glass area. | A-GLAZ, WINDOW, WIN |
| Room names | TEXT / MTEXT inside each room ("MASTER BEDROOM", "OFFICE 3"). Dimension-like texts (4500x3600) are ignored. | A-ANNO-TEXT, TXT, ROOM-NAME |
| North | Not read from the drawing — you type the angle of the north arrow (0 if north is up). | — |
The screen: Steps and the Storeys and Layers lists on the left, the Plan in the middle (drag to pan, wheel to zoom, 2D / 3D buttons), the step editor on the right and the Room schedule table at the bottom.
If detection finds far too few rooms (everything merged into one), the walls have gaps: add the door layer, or raise Close gaps ≤ m in the project step (0.3–1.2 m) and detect again. Too many small rooms: raise Min room m².
Click a room to see its name, type and every wall: direction, what it faces (outside / room name / void), length, glass and door length. Fix tools:
| Tool | Use it when | How |
|---|---|---|
| Merge two | A room was split by a low wall, a column line or a furniture line | Click the two rooms |
| Draw room | A room was not enclosed at all (open-plan area, glass partition not on the wall layer) | Click its corners on the plan, then Finish |
| Delete | Courtyards, shafts, voids, the space between the outer wall and the site boundary | Click the room |
| Rename / type | Text was missing or wrong | Edit in the room panel or in the schedule table |
| Reset all fixes / Re-detect | Start again after changing layers or parameters | Buttons at the bottom of the panel |
Fixes are remembered and re-applied if you detect again with other settings.
Every storey is extruded: blue rooms are AC, green ventilation, amber exhaust, grey none; light-blue panes are the glass. Drag to rotate, shift-drag to pan, wheel to zoom, click a room for its data (what is above and below it). Use "Show storeys up to" to look inside. If a room is missing or a wall has no glass where it should, go back to Step 4.
The table at the bottom lists every room of every storey. Set the Type (office, bedroom, kitchen, server…) — it brings the ASHRAE / ECBC defaults for occupancy, lighting, equipment and fresh air — and the Service: AC, Ventilation (enter ACPH), Exhaust (ACPH) or None. Type a value in any column to override a default. "Set all rooms of type … to …" applies a service in one go (e.g. all toilets → Exhaust).
All wall, window and door lines are cut at their intersections and every enclosed face is found. Thin faces (narrower than the maximum wall thickness, 0.30 m) are wall bands; small faces touching a door are the door swing and are added to their room; the rest are rooms. Missing jamb lines at door openings are reconstructed by joining loose wall ends closer than the jamb gap (0.5 m). Each room boundary is then walked wall by wall: the direction comes from the wall's outward normal and the north angle; the neighbour is found by probing a short distance outside the wall — another room, the outside (beyond the building outline) or a void. Windows are matched to the nearest wall within 0.6 m. Storeys are stacked by overlap: a room with ≥ 50 % of its area under rooms above has "room above", otherwise an exposed roof; the ground floor has a floor on the ground.
The walls are on many layers. Click all of them under the walls role.
Rooms are named with the room number, not the function. Rename in the schedule, or set the type directly — the type drives the defaults, the name is only a label.
The drawing has the whole building on one DXF with floors side by side. Save one DXF per floor (WBLOCK), or upload the same DXF for each storey and delete the rooms that belong to the other floors — cleaner to split the file.
Glass height varies (shopfront on the ground floor, windows above). Set the glass height per storey; for a single wall that differs, the heat-load tool lets you override the glass area per room.
Can I skip the drawing? Not for this tool — the drawing is the point. For a quick estimate use the heat-load tool's per-room override fields on a rough model.