It takes every AC room of the building model — floor area, height, each exposed wall with its direction and glass, partitions to non-AC spaces, roof and floor condition, the room type with its occupancy, lighting, equipment and fresh-air defaults — and fills the E20 form for it: wall and roof loads from the Carrier equivalent-temperature-difference tables (or ASHRAE sol-air CLTD), glass conduction and solar gain from the ASHRAE clear-sky model for your latitude, month and hour, people, lights, equipment, ventilation with the bypass-factor method, duct gains and safety factors, then the sensible heat ratio, apparatus dew point, supply air CFM, TR and the check figures. It does this for summer, monsoon and winter, at a fixed hour or by searching 8–18 h for each room's peak and the building's block peak.
Outputs: the E20 workbook (Master, Tables, one sheet per room with formulas that recalculate when you change a U-value or an area, and a Sumup), the HAP 6 spaces spreadsheet, a printable report, and a DXF plan of every storey with the TR / CFM written in each room.
Room table (independent) — no drawing needed. Open calc.designlink.in → Heat load and choose New heat-load project (IP: ft², ft, W/ft², cfm, °F, or SI: m², m, W/m², L/s, °C), or download the input template, fill it and Upload filled Excel. Each row is one AC space: storey, name, room type, floor area, height, exposed wall gross area and glass / door area per exposure (N … NW), roof / above (exposed, non-AC above, AC above), floor / below (on ground, exposed, non-AC below, AC below), partitions and glass partitions to non-AC, then people, activity, lighting, equipment, fresh air and inside design. Blank load cells take the room-type default (ASHRAE 62.1 / 90.1 or ECBC 2017).
Building model — in the Building Model tool every room has a type and a service; AC rooms get a load, walls, glass, orientation and what is above / below come from the plans. Type known values in the room schedule; blank cells take the room-type default. The city of the model is used for the weather. A building heat load can be turned into a room table with Independent copy.
| Setting | Options | When to use |
|---|---|---|
| Calculation method | Carrier E20 (Tables 19 / 20 with the design-condition correction, glass solar from the clear-sky model × SC × storage factor) · Carrier E20 — MSPL sheet (exactly the office sheet: same tables, fixed 16:00 glass factors) · ASHRAE (CLTD calculated from the sol-air cycle, mass-class lag and decrement) | Carrier E20 for normal work and matching HAP-style inputs; MSPL to reproduce old projects; ASHRAE when the client asks for ASHRAE |
| Design hour | fixed sun time (16:00 default) or peak search 8–18 h | Peak search gives each room its own worst hour (east rooms in the morning, west in the afternoon) and the building block load with diversity — use it for plant sizing |
| Defaults standard | ASHRAE 62.1 / 90.1 or ECBC 2017 | ECBC for Indian projects that must show ECBC compliance (lighting W/m²) |
Pick the exposed wall (230 mm brick U 0.35, AAC, RCC, ECBC wall…), roof (RCC slab, insulated, ECBC roof), floor, partition, glass (single clear SC 0.95, tinted, reflective, DGU, low-e, ECBC) and internal shading. Each choice sets U, weight (for the ETD table) and SC. Factors: bypass factor 0.15, supply duct gain 10 %, return duct 5 %, safety factors, ballast multiplier (1.25 fluorescent, 1.0 LED), solar storage factor 0.85, partition ΔT (To − Ti) − 10, ground ΔT 10, a selected supply temperature (blank = the calculated ADP rounded down) and infiltration ACPH.
The same layout as the office sheet, with summer, monsoon and winter side by side: for each exposed wall the net area, U, TD and Btu/h; roof; floor; partitions; glass conduction; glass solar per direction (area × SC × factor); lights; equipment; people; ventilation bypass; space sensible; duct gain and safety; RSH; the latent rows; RLH; outside air on the coil; return duct; grand total; TR; then SHR, ADP, supply temperature, dehumidified air CFM and the check figures. The ETD correction and the ETD / solar factors used are shown so the sheet can be checked line by line against the Carrier tables.
| Check | Typical range | If outside |
|---|---|---|
| ft² / TR | 140 – 400 offices and residences; 80 – 150 dense (restaurants, halls); 30 – 60 server rooms | Too low: check glass area / SC, equipment W/ft², fresh air; too high: exposed walls or roof missing (room "none" above?) |
| CFM / ft² | 1.0 – 2.0 | Low ADP or a high supply temperature raises the CFM — check the selected supply temperature |
| CFM / TR | 350 – 500 | High latent load (people, fresh air) lowers it |
| Glass solar vs total | 10 – 40 % on west / south rooms | Verify the north angle in the model if east rooms peak in the afternoon |
Why do I get a different value from my old sheet? Choose the MSPL method with the same hour, conditions and U-values to reproduce it; the Carrier and ASHRAE methods compute the glass solar for the actual latitude, month and hour instead of the sheet's fixed 16:00 factors, and take people gains from the table for the room temperature.
Where do partitions come from? From the model: a wall facing a room whose service is not AC (corridor set to ventilation, toilets to exhaust, stores to none) is a partition to a non-AC space; walls between two AC rooms carry no load. Set the services right in the model first.
One room needs different glass. Override the room's glass area in the E20 workbook (yellow cells) or add the room's own U / SC in the schedule notes for the next model update; per-room construction overrides are planned.
Heating. The winter column uses the winter DB / WB with negative ΔT and no solar, as the E20 sheet does; the heating Btu/h per room is in the Rooms tab.
Which ASHRAE tables are used? Clear-sky solar (A, B, C coefficients), DSA-glass transmittance / absorptance for SHGF, the daily temperature profile, sol-air temperature and Hyland-Wexler psychrometrics from the Handbook — Fundamentals; ventilation and occupant density from 62.1; lighting from 90.1 (or ECBC 2017).